5
3) ELECTRICAL INSTALLATION
The electronics of this clock is protected by a fuse (F1).
Connect the keyboard to the clock
(terminals 1 to 4).
Connect the coded time line (AFNOR:
terminals 5 and 6 / Minute 24V: terminals
6 and 7). There is no polarity. Two wires
(brown / white) for connection on AFNOR
line or 24 V minute impulses depending on
the model.
Connect the 230 Volt 50/60 Hz mains power
supply (do not switch on before the control
panel and the time distribution are
connected).
Setting of the clock to the correct time is automatic in AFNOR mode and manual in the
autonomous or 24 V minute impulse version (see section 7,
page 6).
Programming and brightness adjustment are carried out with
the two programming keys “SELECT” and “+”.
4) POSITION OF “SELECT” AND “+” KEYS
- These two keys are on the back of the clock, on the right.
- The “Select” key is above the “+” key.
Time distribution
Power supply
To control panel
7
T- T+ 9VAC
Afnor
mminute 24V