5.0 Output Setup (alarm relays)
Below is the menu structure for the Output Setup selection. The layout of the Output Setup menu is similar to
the Input Setup menu. Outputs were designed to directly communicate to SCADA systems, alarms, data
loggers, backup pumps, pumps to operate in sync, pumps to operate proportionally, and other external devices.
To prevent false alarms due to pump start-up and closed loop applications, a trigger delay time can be config-
ured to delay the relay switch action. The delay time unit of measure is seconds.
Flex-Pro
4.7 Remote/Local Control
The Flex-Pro can be configured for Remote control only, Local control only, or
either (disabled).
When set for Remote control only, all touch pad buttons except the menu button are
disabled. To completely lock out the menu, configure a password (see page 12,
section 8). If REMOTE ONLY is selected, the user is prompted to select an input
operating mode which must then be used when operating the pump.
When set for local control only, all input signals including the remote start/stop are
disabled. Note that the “contact closure input” menu setting (section 4.4) is
switched to “disabled” while
LOCAL ONLY
is selected. This menu setting will return
to the previous setting when
REMOTE ONLY
or
DISABLED
is selected.
- Input Setup
+ Input Modes
+ Contact Input
+ Set FVS
<- Esc
Hidden
+ Set Rev Alarm
+ Set TFD
+ Remote/Local
- Remote/Local
Remote Only
Local Only
Disable
Done
(select one)
- Remote Only Input Mode
4-20 mA
0-10 VDC
Frequency
(select one)
Hidden
Done
Proportional
Pulse
Removing the pump head
cover automatically puts
the pump into
“maintenance” mode,
allowing the operator to
replace the pump tube
without changing the
Remote/Local settings.
Tip!
MAINTENANCE MODE
Pump Cover Removed!
Press STOP to stop
- Cover was removed!
- Motor Speed = 6 RPM
MAINTENANCE MODE
Press START to run
Max = 999999999
Press ENTER to set.
- Input Setup
+ Contact Input
+ Set FVS
<- Esc
+ Set TFD
+ Remote/Local
+ Set Rev Alarm
Revolution Alarm
Rev Alarm Disable
(select one)
Revolution Alarm
Set Revolution Alarm
00000000
0
Rev Alarm Enable
Done
4.8 Set Revolution Alarm
One of the primary factors effecting tube life is the number of revolutions the tube
has operated. The Flex-Pro includes a roller revolution counter. A revolution alarm
set point can be input which will alert the user when the tube should be serviced.
When the set point is reached, the pump display will turn red and the words “REV
ALARM” will be displayed.
The pump will not stop.
An alarm output can be configured to close when the revolution set point is
reached. See section 10.0 Output Setup.
Page 29
Flex-Pro
Note:
Contact #1 shown only. Contact #2, and
Contact #3 use the same menu items.
- Output Setup
+ Signal Output
+ Relay Output
+ Contact #1
+ Contact #2
Output - Signal
+ Contact #3
<- Esc
Hidden
Output - Assign Relay
- Output Setup
+ Signal Output Modes
+ Contact #1
+ Contact #2
+ Contact #3
<- Esc
+ Relay Output
- 4-20 mA Output
Signal @ min % Motor:
Input
mA Signal
@ Min % Motor speed
- 4-20 mA Output
Minimum % Motor:
Input
Min % Motor
for mA Signal Output
- 4-20 mA Output
Signal @ Max % Motor:
Input
mA signal
@ Max % Motor Speed
- 4-20 mA Output
Maximum % Motor:
Input
Maximum % Motor
for mA Signal output
- Relay Output
Both, TFD/FVS
FVS
4-20mA Mode
- Signal Output
4-20 mA Output
Freq. Output
Disable
- Signal Output
4-20 mA Output
Freq. Output
Disable
Done
Done
- Freq. Output
Signal @ Min % Motor:
Input
Frequency (Hz)
@ Min % Motor Speed
000
0
- Freq. Output
Minimum % Motor:
Input
Min % Motor
for Freq. output
00.0
0
- Freq. Output
Signal @ Max % Motor:
Input Frequency
(Hz)
@ Max % Motor Speed
000
1
- Freq. Output
Maximum % Motor:
Input
Maximum % Motor
for Freq. Output
00.0
1
Monitor Input
Monitor Output
Monitor Run/Fail
Manual Mode
- Output Setup
+ Signal Output Modes
+ Relay Output
+ Contact #2
+ Contact #3
<- Esc
+ Contact #1
- Contact Closure #1
Monitor Input
Monitor Output
Monitor Run/Fail
Both, TFD/FVS
Disable
TFD
Hidden
Hidden
Hidden
Hidden
Output -
Contact Closure #1
(select one)
(select one)
0
00.0
0
4.00
1
00.00
2
0.00
Pump Run/Stop
Frequency Mode
Cycle Timer Mode
Dispensing Mode
Manual Dosing
Prop. Dosing
0-10 VDC Mode
Pulse Mode
Disable
FVS
TFD
Pump Run/Stop
4-20mA Mode
Manual Mode
Frequency Mode
Cycle Timer Mode
Dispensing Mode
Manual Dosing Acive
Prop. Dosing Active
0-10 VDC Mode
Pulse Mode
Remote Active
Remote Active
Done
Done
Revolution Alarm
Reverse Alarm
General Error
Revolution Alarm
Reverse Alarm
General Error
+ Configuration
- Menu
+ Input Setup
+ Output Setup
<- Esc
+ Power Fail option
Description of Relay and Contact Closure Output triggers
Selection:
Contact energizes when:
Pump Run/Stop ........
Motor turning (roller assembly is rotating).
Monitor Input .... ........
Incoming analog or digital signal is not received or out of range.
Monitor Output
.. ........Outgoing analog or digital signal not transmitted or out of range.
Monitor Run/Fail
........Motor fails to respond to commands.
Both TFD/FVS
.. ........Either TFD or FVS system triggers.
FVS
........ ........ ........After the programmed delay time, pulses are not received from flow sensor.
TFD
........ ........ ........Tube failure is detected by sensors in the head.
Active Mode
...... ........Use to monitor any changes to the active (run) mode selection.
Remote Active .. ........
Energized when Remote only is active.
Revolution Alarm.......
Revolution count set-point has been achieved.
Reverse Alarm.. ........
The motor revolution is reversed (turning clock-wise).
General Error.... ........
A motor overload or other internal error has occurred.
Disable
..... ........ ........Output contact is disabled.
Relay Out Delay
Input Relay Delay:
Max Delay = 999.9 (s)
Press ENTER to set
0
00.0
Contact 1 Delay
Input Relay Delay:
Max Delay = 999.9 (s)
Press ENTER to set
0
00.0
5.0 Output Setup (alarm relays)