4.0  

Input Setup

Below is the menu structure for the INPUT SETUP selection.

Max RPM cut-off - 4.1

To Select a maximum motor RPM. 
Input the maximum RPM value.

Max Flowrate - 4.2

To calibrate your pump. This setting is 
pre-configured at the factory based on 
the tube size supplied when ordered. 
Pump has been calibrated with water. 
You can re-calibrate pump. Input the 
calibrated ml/min at 100% motor speed.

Input Modes - 4.3

To configure your pump’s Run Modes. 
Use this menu to setup your desired 
operating mode. This manual will cover 
each step in detail later.

Contact Input - 4.4

(remote start/stop)
Contact Closure Input feature is used to 
Start and Stop pump remotely. Default 
setting is DISABLE.

Set FVS  - 4.5

(Flow Verification System)
Set Flow Verification time delay. Use this 
feature if you are using a Blue-White 
flow verification sensor to monitor flow 
output. Default setting is OFF.

Set TFD - 4.6

(Tube Failure Detection)
Set Tube Failure Detection sensitivity. 
Use this feature to increase the sensitiv-
ity to your chemical. Default setting is 
75%.

Set Remote/Local control - 4.7

(Control panel touch pad lockout)
Select remote to disable the touch pad 
buttons enabling input signal control 
only. When remote is selected, the user 
must select an input operating mode.
Select Local to disable all input signals 
and allow local touch pad control only.

Set Revolution Alarm - 4.8

(number of roller revolutions)
Set the number of revolutions required 
to trigger the display alarm (display turns 
red) and to trigger the output contact 
closure.

Flex-Pro

Max = 999999999
Press ENTER to set.

- Set FVS

- Max Flowrate

   Input Max Flowrate:

Flowrate = ML/min
Press ENTER to set.

0000.0

1

- Contact Input

    Close: Stop Pump
    Open: Stop Pump

   Input Time Delay:

OFF = 000
Range = 1-255 sec

    Disable

00

0

- Input Setup

+ 4-20 mA Input

+ Frequency Input
+ Pulse Input

+ 0-10 VDC Input

+ Manual Adjust

+ Dispensing

+ Proportional
   <- Esc

+ Manual Dosing

+ Cycle Adjustment

Hidden

Done

(select one)

+ Configuration

- Menu

+ Input Setup

+ Output Setup

<- Esc

+ Power Fail option

- Input Setup

+ Max RPM cut-off

+ Max Flowrate
+ Input Modes
+ Contact Input
+ Set FVS

<- Esc

Hidden

+ Remote/Local

+ Set TFD

+ Set Rev Alarm

- Input Setup

+ Max RPM cut-off

+ Max Flowrate

+ Input Modes
+ Contact Input
+ Set FVS

<- Esc

Hidden

+ Remote/Local

+ Set TFD

+ Set Rev Alarm

- Input Setup

+ Max RPM cut-off
+ Max Flowrate

+ Input Modes

+ Contact Input
+ Set FVS

<- Esc

Hidden

+ Remote/Local

+ Set TFD

+ Set Rev Alarm

- Input Setup

+ Max RPM cut-off
+ Max Flowrate
+ Input Modes

+ Contact Input

+ Set FVS

<- Esc

Hidden

+ Remote/Local

+ Set TFD

+ Set Rev Alarm

- Input Setup

+ Max RPM cut-off
+ Max Flowrate
+ Input Modes
+ Contact Input

+ Set FVS

<- Esc

Hidden

+ Remote/Local

+ Set TFD

+ Set Rev Alarm

- Input Setup

+ Max Flowrate
+ Input Modes
+ Contact Input
+ Set FVS

<- Esc

Hidden

+ Remote/Local
+ Set Rev Alarm

+ Set TFD

TFD Sensitivity

   % Sensitivity:

Enter TFD Sensor
Sensitivity %.

78.0

0

- Input Setup

+ Input Modes
+ Contact Input
+ Set FVS

<- Esc

Hidden

+ Set Rev Alarm

+ Set TFD

+ Remote/Local

- Remote/Local

    Remote Only
    Local Only
    Disable

Done

(select one)

- Remote Only Input Mode

   4-20 mA
   0-10 VDC
   Frequency

(select one)

Hidden

   Done

   Proportional

- Input Setup

+ Contact Input
+ Set FVS

<- Esc

+ Set TFD
+ Remote/Local

+ Set Rev Alarm

Revolution Alarm

    Rev Alarm Disable

(select one)

Revolution Alarm

   Set Revolution Alarm

00000000

0

   Pulse

    Rev Alarm Enable

Done

- Max RPM cut-off

25.0

1

Press ENTER to set.

Password Protect

   Enter Password:

Use direction keys

890

7

Press ENTER to set.

Page 15

Flex-Pro

4.1   Max RPM cut-off

The maximum motor RPM can be limited to reduce the possibility of overfeeding 
chemical into the system. Note that the pump’s display will still reference values 
calculated from the 100% motor speed MAX Flowrate value (see section 4.2). Also, 
the pump % motor speed will still be referenced from 125 RPM, the maximum 
possible motor RPM. For example, if the pump speed is set for 25%, the display will 
indicate 32.3 RPM. The prime mode RPM is limited to the Max RPM value.

Select 

Max RPM cut-off 

and Press ENTER button. Use the direction arrows to 

enter the password 7890.

Press UP or DOWN arrow to scroll through 0 - 9 on selected digit.

Press RIGHT arrow to scroll over to next digit to right. If you pass your desired digit, 
you can easily scroll back by continuously pressing RIGHT button.

Press ENTER to save changes.

Select 

<-Esc 

on the main menu screen to exit the menu and enter the run mode.

- Max RPM cut-off

- Input Setup

+ Max RPM cut-off

+ Max Flowrate
+ Input Modes
+ Contact Input
+ Set FVS
+ Set TFD

25.0

1

Press ENTER to set.

4.2   MAX Flowrate (output calibration)

The MAX Flowrate value is equal to the pump’s measured fluid output in milliliters 
per minute, at the 100% motor speed adjustment setting. The pump uses the MAX 
flow rate value to calculate motor speed for various operating functions and to 
display output values. 

Each Flex-Pro pump is calibrated at the factory and shipped with a calibrated pump 
tube assembly installed. The MAX flow rate value can be adjusted at any time. To 
achieve high accuracy, a field calibration under the actual operating conditions 
should be performed and the Max Flowrate value changed to reflect the calibrated 
amount. Multiply the 

Max Flowrate

 value by the percentage of error at your 

calibrated flow rate to obtain the new 

Max Flowrate

 value.

Select 

Max Flowrate 

and Press ENTER button. 

Press UP or DOWN arrow to scroll through 0 - 9 on selected digit.

Press RIGHT arrow to scroll over to next digit to right. If you pass your desired digit, 
you can easily scroll back by continuously pressing RIGHT button.

Press ENTER to save changes.

Select 

<-Esc 

on the main menu screen to exit the menu structure and enter the run 

mode.

Every pump tube assembly model number has a published maximum flow rate 
value which is based on laboratory tests pumping water at room temperature at 36” 
suction lift against 0 psi back pressure. Your actual output may vary due to fluid 
viscosity, fluid temperature, suction lift height, piping system layout, manufacturing 
tolerances and to a lesser degree, variations in system pressure and tubing wear.

To achieve high accuracy, the pump’s output should be measured (calibrated), and 
the MAX Flowrate value (in milliliters per minute) updated, whenever any of the 
following conditions exist:

!

 At the initial pump start up.

!

 When a new tube assembly is installed. 

Run the pump with or without fluid for 

approximately 30 minutes prior to calibration.

 

!

 When the piping system configuration is changed.

!

 When the suction lift height is changed.

!

 Periodically during the life of the tube. 

Output variances are most noticeable prior 

to tube failure. 

- Input Setup

+ Max RPM cut-off

+ Max Flowrate

+ Input Modes
+ Contact Input
+ Set FVS

<- Esc

Hidden

+ Remote/Local

+ Set TFD

+ Set Rev Alarm

- Max Flowrate

   Input Max Flowrate:

Flowrate = ML/min
Press ENTER to set.

0000.0

1

To calculate the Max 

Flowrate:

To determine the amount of 
error at your output setting, 
divide the actual output 
amount by the indicated 
output. Then multiply the 
resulting percentage of error 
by the 

Max Flowrate

 value 

currently showing in the pump. 

Example: If the pump display 
indicates the output is 170 
ml/min but the actual 
measured output is 160 
ml/min, calculate the 
percentage of error by: 
160/170 = 0.941. Multiply the 

Max Flowrate

 value by 0.941 

and enter this new value.

Password Protect

   Enter Password:

Use direction keys

890

7

Press ENTER to set.

Содержание FLEX-PRO PROSERIES-M Flex-A-Chem M-3

Страница 1: ...e White com PROSERIES M M 3 and M 4 Operating and Maintenance Manual ProSeries by Blue White Ind TM FLEX PRO Peristaltic Metering Pump system TFD Tube Failure Detection Exclusive 5 FIVE YEAR WARRANTY...

Страница 2: ...onal Dosing 24 4 4 Contact Closure Input Remote start stop 25 4 5 Set FVS Flow Verification System 26 4 6 TFD Tube Failure Detection 27 4 6 1 TFD Adjustment 27 4 7 Remote Local Control 28 4 8 Set Revo...

Страница 3: ...2100 2100 RPM 125 125 125 PSI bar 65 65 65 4 5 4 5 4 5 65 4 5 PSI bar 125 8 6 125 8 6 125 8 6 PSI bar 50 3 4 50 3 4 F C 185 85 185 85 185 85 F C 130 54 130 54 F C 130 54 130 54 130 54 130 54 Flex A P...

Страница 4: ...e assembly maximum temperature ratings Ambient Operating Temperature O O O O 14 F to 115 F 10 C to 46 C Ambient Storage Temperature O O O O 40 F to 158 F 40 C to 70 C Operating Voltage M 3 MODELS 115V...

Страница 5: ...ustment No maintenance brushless variable speed motor Specially engineered tubing for long life at high pressures Patented Tube Failure Detection TFD system Senses tube failure by detecting chemical i...

Страница 6: ...valves should NOT be used as back flow preven tion valves unless adjusted to the minimum possible opening pressure Any additional pressure at the pump will reduce the life of the pump tube A pressure...

Страница 7: ...easy pump access in hard to reach areas Extended Brackets A B C D E 10 3 4 8 1 8 15 1 4 10 12 1 4 27 3 20 6 38 9 25 4 31 0 14 1 4 12 1 8 18 5 8 11 13 5 8 36 1 30 8 47 3 27 9 34 6 F 4 1 4 10 7 6 15 2...

Страница 8: ...nstalled and sealed Never strap control input output cables and power cables together Power Interruption This pump has a user programmable auto restart feature which will can either restore the pump t...

Страница 9: ...Form C 1 AMP MAX AT 125 VOLT AC 0 8 AMP MAX AT 30 VOLT DC 5A SLOW BLOW 20 X 5MM 1 2 3 T1 PULSE GND 4 20 1 2 3 T1 PULSE GND 4 20 0 10 15VDC 1 2 T2 0 1000 HZ MAX NEGATIVE POSITIVE POSITIVE NEGATIVE NO...

Страница 10: ...l Speed Adjust mode Press and hold to increase values progressively faster Press and release to stop the pump Press and release to select menu items Press and release when not in the configuration men...

Страница 11: ...s Scroll bar example While making a selection where only one choice is allowed you will see a radio button Radio button example In a screen where you are making changes you will see the word Done loca...

Страница 12: ...to exit the menu structure and enter the run mode Flex Pro Configuration Display Language Set Password Display Rate Esc Reset to Default Display Language English Spanish German Done French Display La...

Страница 13: ...display may be toggled through Speed RPM and your selected Display Rate by pressing the right arrow button Press MENU button to enter the menu structure Select Configuration and Press ENTER button Se...

Страница 14: ...set Set FVS Max Flowrate Input Max Flowrate Flowrate ML min Press ENTER to set 0000 0 1 Contact Input Close Stop Pump Open Stop Pump Input Time Delay OFF 000 Range 1 255 sec Disable 00 0 Input Setup 4...

Страница 15: ...Press ENTER button Press UP or DOWN arrow to scroll through 0 9 on selected digit Press RIGHT arrow to scroll over to next digit to right If you pass your desired digit you can easily scroll back by c...

Страница 16: ...ck out of the menu structure To do this you must select Esc at the bottom of every screen menu until you see the Run Mode screen displayed Tip The Manual Speed Adjust mode can be combined with Contact...

Страница 17: ...creen Continue this process until all four screens have been configured If you used short cut to enter 4 20 mA input setup press and hold the Mode button until the Run Mode screen is displayed If you...

Страница 18: ...ut is displayed in the top line of the display To configure the pump navigate to 0 10 VDC Input menu by using the short cut method described at the beginning of the section or by pressing MENU button...

Страница 19: ...RIGHT ARROW to select the digit to change press UP or DOWN arrow to scroll through 0 9 on selected digit Press enter to save changes and move to the next input screen To input flow rate values press...

Страница 20: ...an easily scroll back by continuously pressing the RIGHT button Press ENTER to save the changes Continue this process until all three screens have been configured If you used the short cut to enter Pu...

Страница 21: ...e screens have been configured If you used the short cut to enter Manual Cycle Adjustment setup press and hold Mode button until Run Mode screen is displayed If you used the Menu button to navigate to...

Страница 22: ...croll over to next digit to the right If you pass your desired digit you can easily scroll back by continuously pressing RIGHT button Press ENTER to save the changes Continue this process until two sc...

Страница 23: ...digit Press RIGHT arrow to scroll over to next digit to the right If you pass your desired digit you can easily scroll back by continuously pressing RIGHT button Press ENTER to save the changes Conti...

Страница 24: ...desired digit you can easily scroll back by continuously pressing RIGHT button Press ENTER to save the changes Continue this process until all four screens have been configured If you used the short...

Страница 25: ...prevent false triggering due to flickering high speed electrical switches a trigger delay time can be configured to delay the pump command The delay time unit of measure is seconds A two second delay...

Страница 26: ...value of 000 seconds disables FVS system If a FVS alarm occurs the pump will stop send an external signal if setup and the screen will flash FVS with an alarm icon To clear the FVS alarm you must pres...

Страница 27: ...Chemicals with a conductivity of less than 430 microsiemens will not be detected This patented system is capable of detecting the presence of a large number of chemicals including Sodium Hypochlorite...

Страница 28: ...s menu setting will return to the previous setting when REMOTE ONLY or DISABLED is selected Input Setup Input Modes Contact Input Set FVS Esc Hidden Set Rev Alarm Set TFD Remote Local Remote Local Rem...

Страница 29: ...top Frequency Mode Cycle Timer Mode Dispensing Mode Manual Dosing Prop Dosing 0 10 VDC Mode Pulse Mode Disable FVS TFD Pump Run Stop 4 20mA Mode Manual Mode Frequency Mode Cycle Timer Mode Dispensing...

Страница 30: ...Output 4 mA 100 Pump Output 20 mA Signal Output Frequency Output Disable Done 4 20 mA Output Default 4 20 mA output settings shown Signal Output Disable Done 4 20 mA Output Default Frequency Hz output...

Страница 31: ...sembly especially when injecting fluids that calcify such as sodium hypochlorite These lime deposits and other build ups can clog the fitting increasing the back pressure at the pump reducing tube lif...

Страница 32: ...y clean the Pump Head and Rotor The Rotor can be removed by pulling it straight out After the cleaning process push the Rotor back on the shaft See the drawing above for proper assembly Be sure the fr...

Страница 33: ...de discharge fitting into pump head tongue and groove Once discharge fitting is secured in pump head stop pump by pressing STOP button Replace pump head cover Pump will ask you if the tube was replace...

Страница 34: ...4 tri clamp Sanitary Fitting Flex A Prene NEE 0 093 ID Tube Assembly Quick Disconnect Flex A Prene NGG 0 187 ID A3 SNGG T A3 MNGG T A3 BNGG T A3 CNGG T 1 1 1 1 1 1 1 1 4 Tube Assembly 3 8 OD tube com...

Страница 35: ...ID Tube Assy 1 2 hose barb Multi Tube Flex A Thane GK GK 38 38 ID Tube Assy 1 2 Male NPT Multi Tube Flex A Thane GH GH 25 25 ID Tube Assy 1 2 Male NPT Multi Tube Flex A Thane GK GK 38 38 ID A4 BGHH T...

Страница 36: ...K MTK MGK MNGG MNEE MG2G Suction lift 3 ft 0 500 1000 1500 2000 2500 0 30 60 90 125 Motor RPM Flex Pro Model M 3 output of water vs motor rpm MNH MNJ MNK MTK MGK MNGG MNEE MG2G Suction lift 3 ft 0 200...

Страница 37: ...Model M 4 output of 200 cP fluid vs motor speed BNH BNJ BNL BNP MTK MGK Suction lift 3 ft 0 2000 4000 6000 8000 10000 12000 0 25 50 75 100 Motor Speed Flex Pro Model M 4 output of water vs motor speed...

Страница 38: ...Flex Pro Page 38 Intentionally Left Blank...

Страница 39: ...Page 39 Flex Pro Intentionally Left Blank...

Страница 40: ...injecting various chemicals especially those considered hazardous or dangerous Eye protection must be worn when working around this product or any other metering type of pump Should it become necessa...

Отзывы: