Page 14
®
FLEXFLO M1
Page 15
Remote
Local
% Speed
RPM
mA
Signal
RUN MODES
DISPLAY
M1
Remote
Start / Stop
FVS
Manual
Adjust
1. Press & Hold mA Input to Setup
2. Use Arrow Keys to Adjust
3. Press mA Input to Toggle Next
4. Press & Hold mA Input to Exit
MIN mA
MIN % Speed
MAX mA MAX % Speed
PERISTALTIC
METERING PUMP
4-20mA
Input
Remote
Local
% Speed
RPM
mA
Signal
RUN MODES
DISPLAY
M1
Remote
Start / Stop
FVS
Manual
Adjust
1. Press & Hold mA Input to Setup
2. Use Arrow Keys to Adjust
3. Press mA Input to Toggle Next
4. Press & Hold mA Input to Exit
MIN mA
MIN % Speed
MAX mA MAX % Speed
PERISTALTIC
METERING PUMP
4-20mA
Input
7.0
4-20mA Input
Proper eye and skin protection must be worn when installing and servicing the pump.
CAUTION
!
Directions
1
Confirm that pump is in the OFF position
2
Press 4-20mA Input button
1
7.1 Selecting 4-20mA input mode
Directions
1
Confirm that pump is in the OFF position.
2
Press and hold 4-20mA Input button.
3
MIN mA light will illuminate. Use arrow
keys to toggle min mA value for the pump
to operate at
4
Press 4-20mA Input button for MIN %
Speed light to illuminate
5
Use arrow keys to toggle MIN % Speed
value for the pump to operate.
6
Press 4-20mA Input button for MAX mA
light to illuminate.
7
Use arrow keys to toggle MAX mA value
for the pump to operate.
8
Press 4-20mA Input button for MAX %
Speed light to illuminate.
9
Use arrow keys to toggle MAX % Speed
value for the pump to operate.
10
Press and hold 4-20mA Input button to exit
programming mode.
1
3
7.2
Programming 4-20mA input mode
2
2
Risk of electric shock – cord connected models are supplied with a grounding conductor and
grounding-type attachment plug. To reduce risk of electric shock, be certain that it is connected only
to a properly grounded, grounding-type receptacle.
>
Use the voltage for which the power cord is rated.
>
Do not strap together control (input/output) cables and power cables.
>
When there is a power interruption, the pump, which has an auto-restart feature, will restore the pump to the
operating state it was in when the power was lost.
>
POWER: 115V60Hz (0.6A max.), 220V50Hz (0.3A max.), 230V60Hz (0.3A max.), 230V50Hz (0.3A max.),
240V50Hz (0.3A max.)
NOTE
: Contact a licensed electrician when there is doubt regarding the electrical installation.
Electrical connections and grounding (earthing) must conform to local wiring codes.
8.0
POWER CONNECTIONS
Ensure to connect the pump to the proper supply voltage. Using the incorrect voltage will damage
the pump and may result in injury. The voltage requirements is printed on the pump serial label.
WARNING
WARNING
WARNING
®