Transformer Features

•  When plugged into 120VAC, the transformer automatically 

provides power to the battery charging circuitry. 

•  The transformer can be left connected to the wall outlet 

indefinitely. 

•  The transformer is designed for the system only, DO NOT 

use for any other purpose. 

PUMP INSTALLATION

The 12 Volt Advanced Notification System can be installed as 

a back-up system with a separate dedicated discharge line 

(Method 1), or tied into an existing sump pump line (Method 2).
1.   Verify that the existing AC pump is in good working order. If  

      the AC pump is questionable, replace with the same HP 

      pump or increase the HP rating if you have experienced 

      flooding or the pump is not keeping up with the inflow of 

      water.
2.  Remove any silt or accumulated debris from the sump pit 

and surrounding area.

3.   Make sure that disconnecting the AC pump will not create a 

      flood in your basement. A pump should be available to 

      evacuate water in the event incoming water rates should 

      change.

METHOD 1 (PREFERRED) - See Figure 1

1.  Locate the DC pump on a solid, level surface in the sump pit. Do 

NOT place the pump on a loose or sandy surface. Small stones or 

sand may damage the pump resulting in pump failure.

2.  This pump has a 1-1/2 in. NPT discharge. If a 1-1/4 in. 

discharge pipe is desired, an adapter (not included) will 

be necessary.  Smaller diameter piping will reduce pump       

flow-rate and performance. 

3.  A check valve is required in the discharge line of both the 

Main AC pump and the Back-Up DC Pump to prevent 

recirculation of water into the sump pit. The system will not 

function without two check valves.

4.   Cut a 4 ft. section of 1-1/4 in. or 1-1/2 in. diameter rigid PVC 

pipe. Cement 1-1/4 in. or 1-1/2 in. pipe to a threaded fitting. 

Cement 1-1/4 in. or 1-1/2 in. pipe into pipe coupling. Attach 

1-1/4 in. or 1-1/2 in. pipe section to the Back-Up DC Pump 

discharge adapter.

5.  Screw into pump discharge.
6.  Place the pump with the 4 ft. section of PVC pipe on a solid, 

level surface in the sump pit on an elevated surface. 

7.  Attach a rubber check valve (sold separately) to the top of 

the discharge pipe. This will allow the pump or check valve 

to be removed easily for servicing.

8.  Check valve is recommended for effective operation of 

system.

The remainder of the discharge pipe installation will vary 

depending on individual circumstances. Using sound plumbing 

practices, route the discharge pipe to an exterior wall by the 

shortest path. Keep turns to a minimum because they reduce 

flow output of the pump. The pipe that exits the building structure 

should be sloped downward so that water will not freeze in the 

pipe.
When installing the separate discharge pipe, drill through 

the outside wall with appropriate drilling equipment. Seal the 

hole to prevent water from entering.

 

Installation of this unit MAY take several hours.  

 

Before disabling your main pump, have a stand by 

pump ready or an appropriate means of evacuating the sump.

 

Electric shock hazard. DISCONNECT power  

 

before servicing. Apply a fixed lock or tag to 

prevent unexpected application of power.

 

DO NOT over tighten or cross-thread plastic 

 

fittings or check valves. USE rigid PVC or metal 

pipe for permanent installation.

 

BACK-UP PUMP:

1.   The pump will turn on when either the bottom or top float 

      rises.
2.   The pump motor will keep running for 15 seconds after the 

      float drops.
3.   An auto-test of the back-up pump will occur every 7 days 

      between the hours of 5pm-7pm. The controller will report 

      any known issues and record the date of the last auto-test 

      on the home screen.
4.   The last known float activated back-up pump run date can 

      be found by scrolling through the main menu selections.

CHART 1 - STANDBY POWER PUMPING CAPACITY

40 A-Hr

75 A-Hr

100 A-Hr

*Hours of Protection During A Rain Event  

If Your Sump Pump Runs...

12 Hours

23 Hours

31 Hours

1X Per  

Min

1X Every  

5 Min

1X Every  

10 Min

Deep Cycle  

Battery Size

53 Hours

100 Hours

134 Hours

92 Hours

172 Hours

230 Hours

*Assumes a typical 10 ft. rise on the discharge pipe, and 

Pump Installation

1.   Turn power to main pump off.
2.   Pump must be installed using 1-1/4 in. or 1-1/2 in. rigid 

      PVC piping.

Control Box Features

 

Check valves MUST be installed in the 

 

discharge line of both the main AC pump and the 

back-up DC pump. Failure to install the check valves MAY allow water to 

recirculate into the sump pit. See Figures 1 and 2.

 

4

Operating Instructions and Parts Manual

 

www.blueangelpumps.com

Содержание DF12VSM

Страница 1: ...es not include 12 Volt DC deep cycle battery phone jack phone line pipe and necessary fittings Float Switch Security DC Pump Requires active telephone land line service STEP 2 DISCONNECT POWER If the...

Страница 2: ...Notes 2 Operating Instructions and Parts Manual www blueangelpumps com...

Страница 3: ...lure to follow these instructions WILL result in bodily injury or death Electric shock hazard Disconnect power before servicing Apply a fixed lock or tag to prevent unexpected application of power Ele...

Страница 4: ...low the pump or check valve to be removed easily for servicing 8 Check valve is recommended for effective operation of system The remainder of the discharge pipe installation will vary depending on in...

Страница 5: ...etal pipe is required for permanent installation 9 Glue a 45 elbow to the short pipe on the Back Up DC Pump Glue a Y adapter to the short pipe on the existing pump as shown in illustration for Method...

Страница 6: ...negative terminal of the battery The display should be lit up at this time If connected improperly an alarm will sound until corrected 4 Plug the pump and float switch connectors into the 12 Volt Adva...

Страница 7: ...umber hit ENTER then select the TEST option The system will immediately dial the desired phone number Upon answering the unit will play the following message This is a test of the back up system It wi...

Страница 8: ...cond time within three minutes The System keeps track of all the rings from the previous calls accumulates them until the total ring count matches its ring count number 5 or 10 and then it will answer...

Страница 9: ...determine the number of devices that may be connected to a telephone line Excessive REN s on a telephone line may result in the devices not ringing in response to an incoming call In most but not all...

Страница 10: ...ber at alarm location let ring three 3 times hang up 2 Make a second call to the System within 3 minutes the System will answer on the second ring 3 rings 2 rings System answers on fifth 5th ring 3 Li...

Страница 11: ...place if low or defective 5 Check to make sure the back up pump is not air locked Locate the vent hole inspect and clear the hole using a pipe cleaner Pump Cycles Too Frequently 1 Check valve problem...

Страница 12: ...allow limitations on how long an implied warranty lasts or do not allow the exclusions or limitations of incidental or consequential damages so the above lim i ta tions might not apply to you This li...

Страница 13: ...Interrupteur flotteur S curit Pompe c c Requiert un service de ligne terrestre t l phonique actif TAPE 2 METTRE HORS TENSION Si la source de courant n est pas visible verrouiller en position ouverte a...

Страница 14: ...Remarques 14 Fr Instructions d Utilisation et Manuel de Pi ces www blueangelpumps com...

Страница 15: ...que NE PAS marcher sur un sol mouill avant que le courant ne soit coup Faire appel un lectricien agr pour effectuer l entretien conform ment au Code national de l lectricit et aux codes locaux PROPOSI...

Страница 16: ...ser des pratiques de plomberie s res pour acheminer le tuyau de d charge vers un mur ext rieur par le chemin le plus court R duire le nombre de coudes au maximum dans la mesure o qu ils r duisent le d...

Страница 17: ...er un coude de 45 au tuyau court de la pompe de secours c c Coller un adaptateur en Y au tuyau court de la pompe existante comme indiqu sur l illustration de la m thode 2 10 Coller une section courte...

Страница 18: ...de la batterie puis connecter le fil noir sur la borne n gative de la batterie L affichage devrait alors s allumer En cas de branchement incorrect une alarme se d clenche jusqu ce que le probl me soit...

Страница 19: ...minuteries et toutes les erreurs sont effac es de la m moire du syst me maintenir le bouton RESET r initialisation enfonc pendant au moins 3 5 secondes 2 Appuyer sur le bouton MENU suivi de l option...

Страница 20: ...RIE VOCALE EST INSTALL SUR LA M ME LIGNE T L PHONIQUE Pour annuler la s quence d appel d alarme sortant suivre les tapes suivantes TAPES SUIVRE 1 Appeler le syst me le num ro de t l phone du site de l...

Страница 21: ...dant lorsqu un avis pr alable n est pas possible la compagnie de t l phone avisera le client d s que possible En outre vous serez inform de votre droit d poser une plainte aupr s de la FCC si vous le...

Страница 22: ...g e 60 Batterie charg e 40 Batterie charg e 20 Batterie d charg e tat de la batterie sujet caution APPELT L PHONIQUE ALARME SONORE SIGNALDU SYST ME DE S CURIT Inverser la polarit Figure 6 Tableau des...

Страница 23: ...terie faible ou d fectueuse 3 Interrupteur flotteur coinc 4 Fusible d fectueux ou grill 1 V rifier toutes les connexions 2 V rifier la batterie et la remplacer si elle est faible ou d fectueuse 3 S as...

Страница 24: ...site de l alarme laisser sonner trois 3 sonneries puis raccrocher 2 Appeler le syst me une seconde fois dans les 3 minutes qui suivent le syst me r pondra au bout e deux sonneries 3 2 sonneries le sys...

Страница 25: ...clusion ou la limitation des dommages accessoires ou indirects en cons quence les limitations pr c dentes peuvent ne pas s appliquer tous les cas Cette garantie limit e vous conf re des droits juridiq...

Страница 26: ...dor Seguridad Bomba CC Requiere un servicio de tel fono de l nea activado PASO 2 DESCONECTE LA ENERG A Si la protecci n de desconexi n no est a la vista tr nquela en la posici n abierta y etiqu tela p...

Страница 27: ...Notas 27 Sp DF12VSM www blueangelpumps com...

Страница 28: ...u cable de corriente PUEDEN contener qu micos incluido plomo que son conocidos por el Estado de California como causantes de c ncer y defectos de nacimiento u otros da os reproductivos L vese las mano...

Страница 29: ...n para un funcionamiento eficaz del sistema El resto de la instalaci n de la tuber a de descarga variar dependiendo de las circunstancias individuales Dirija la tuber a de descarga hacia una pared ex...

Страница 30: ...segunda bomba 9 Pegue un codo de 45 al tubo corto en la bomba de respaldo de CC Pegue un adaptador en Y al tubo corto en la bomba existente como se muestra en la ilustraci n del M todo 2 10 Pegue una...

Страница 31: ...tiva de la bater a La pantalla debe iluminarse en este momento Si se conecta de forma incorrecta sonar una alarma hasta que se corrija 4 Enchufe la bomba y los conectores del interruptor de flotador e...

Страница 32: ...l nea telef nica est conectada y que la Home Screen pantalla de inicio no tenga mensajes de error 2 Presione el bot n MENU men seguido de la opci n Phone Setup configuraci n del tel fono 3 Despl cese...

Страница 33: ...NTESTADORA AUTOM TICA CORREO DE VOZ EN LA MISMA L NEA TELEF NICA Para cancelar la secuencia de llamadas de alarma haga lo siguiente PASOS QUE DEBE REALIZAR 1 Realice la llamada al Sistema n mero de te...

Страница 34: ...E LA RED TELEF NICA Si este Sistema causa da o a la red telef nica la compa a telef nica le notificar con anticipaci n que puede ser necesaria la suspensi n temporal del servicio Pero si el aviso con...

Страница 35: ...lente El motor zumba pero la bomba no funciona 1 Bater a defectuosa 2 El impulsor est bloqueado 1 Verifique la bater a y reempl cela si el flujo es bajo o defectuoso 2 Desconecte la bomba retire la re...

Страница 36: ...cionamiento de menos de 1 hora 1 Corte de energ a 2 Corte de energ a extendido 1 Notifique a la compa a de servicios p blicos 2 Prepare una bater a de repuesto Cambie la bater a 1 La bater a tiene poc...

Страница 37: ...est configurado a 5 repiques 1 Haga una llamada al Sistema n mero de tel fono de la ubicaci n de la alarma deje sonar 3 tres veces cuelgue 2 Realice una segunda llamada al Sistema en 3 minutos el Sist...

Страница 38: ...as garant as impl citas o no permiten las exclusiones o limitaciones de da os incidentales o consecuentes de manera que las limitaciones mencionadas anteriormente pueden no aplicarse en su caso Esta g...

Страница 39: ...Notes Remarques Notas 39 Sp DF12VSM www blueangelpumps com...

Страница 40: ...Notes Remarques Notas 40 Sp Manuel de Instrucciones y Lista de Piezas www blueangelpumps com...

Отзывы: