INSTALLATION (continued)
5
WARNING ELECTRIC
SHOCK HAZARD:
Brewer must be properly
grounded to prevent possible
shock hazard. DO NOT
assume a plumbing line will
provide such a ground.
Electrical shock will cause death
or serious injury.
IMPORTANT:
Supply power must match
nameplate for voltage and
phase. Connecting to the
wrong voltage will damage the
brewer or result in decreased
performance. Such damage is
not covered by warranty.
IMPORTANT:
Do not connect
brewer to electrical power until
you are ready to fill the tank.
See instructions on page 6.
IMPORTANT:
The ground
prong of the plug is part of a
system designed to protect you
from electrical shock in the
event of internal damage.
Never cut off the ground prong
nor twist a blade to fit an
existing receptacle. Contact a
licensed electrician to install the
proper circuit and receptacle.
The water line must terminate in a 1/4” male flare fitting, which
will connect to the provided flex line. See Figure 2 below.
In some areas, local codes require a backflow preventer (check
valve) to be installed on the inlet water line. If a backflow
preventer is used, you must install a
water hammer arrester
in
the incoming line, between the backflow preventer and the
brewer inlet, as far away from the brewer as space will allow.
This will relieve the excessive back pressures that can cause
faucet leaks and solenoid malfunctions.
ELECTRICIAN’S INSTALLATION INSTRUCTIONS
REFER TO ELECTRICAL SPECIFICATIONS - Page 1
Check the nameplate to determine correct electrical service
required for the Brewer to be installed.
IMPORTANT:
Before connecting to electricity, make sure
automatic brewers are connected to the water supply.
Model 1016BVM
is equipped with a cord and twist-lock plug.
It requires a 120/240 volt 30 amp circuit (50/60 Hz, 3 wire plus
ground, with NEMA L14-20R Twist-Lock Receptacle).
Fig. 2 Water Supply Installation