Settings
Adjust menu
These adjustment parameters can be modified with the speed controller stopped or
running. Ensure that changes made during operation do not present any danger.
Changes should preferably be made with the speed controller stopped.
(1) In is the nominal speed controller current shown in the catalogue and on the speed controller rating plate.
Code
Assignment
Adjustment
range
Factory
setting
-LFr
Speed reference via the display module.
This parameter appears with the remote display module option if control of
the speed controller via the display module is enabled : LCC parameter in I-
O- menu.
LSP to HSP
-rPI
PI reference
This parameter appears if analog input AIC/AI2 is assigned to the internal PI
function (AIC = PII).
0.0 to 100.0 % 0.0
-rOt
Direction of operation.
This parameter appears if the "local control" option is present .
It defines the direction of operation :
- forward : For, - reverse : rrS
For - rrS
For
-ACC
-dEC
Acceleration and deceleration ramp times.
Defined to range from 0 to nominal motor frequency (FrS)
0,0 to 3600 s
0.0 to 3600 s
3 s
3 s
-AC2
-dE2
2nd acceleration ramp time
2nd deceleration ramp time
These parameters are accessible if the ramp switching threshold (Frt
parameter in the drC- menu) is other than 0 Hz or if a logic input is assigned
to ramp switching.
0,0 to 3600 s
0.0 to 3600 s
5 s
5 s
-LSP
Low speed
0 to HSP
0 Hz
-HSP
High speed : ensure that this setting is appropriate for the motor and the
application.
LSP to tFr
bFr
-ItH
Current used for the motor thermal protection. Set ItH to the nominal current
marked on the motor rating plate.
To disable thermal protection, increase the value to the maximum (ntH
displayed).
0,50 to 1,15
In (1)
In (1)
The parameters in shaded boxes appear if the corresponding functions have been configured
in the drC- or I-O- menus.
SEt-