Configuration
I/O assignment menu
The parameters can only be modified when the speed controller is stopped and locked.
The functions are defined in the section "Configurable I/O Application Functions".
Code
Assignment
Factory
setting
-tCC
Configuration of terminal block control : 2-wire or 3-wire control.
2C = 2-wire, 3C = -wire, OPt = presence of the local control option, operation is then identical
to 3-wire control.
2-wire control : The open or closed state of the input controls running or stopping.
Wiring example :
LI1 : forward
LIX : reverse
3-wire control (pulse control) : one pulse is all that is needed to control start-up.
Wiring example :
LI1 : stop
LI2 : forward
LIx : reverse
Changing the assignment of tCC returns the logic inputs to
factory setting :
• tCC = 2C : LI1 : "Forward", cannot be reassigned LI2 : rrS ("Reverse")
LI3 : PS2 LI4 : PS4
• tCC = 3C : LI1 : Stop, cannot be reassigned LI2 : For ("Forward"), cannot be reassigned
LI3 : rrS ("Reverse") LI4 : JOG
• tCC = OPt : LI1 : no, cannot be reassigned LI2 : PS2
LI3 : PS4 LI4 : PS8
2C
-LCC
Parameter only accessible with the remote display module option : no - YES
Enables control of the speed controller using the STOP/RESET, RUN and FWD/REV
buttons on the display module. The speed reference is then given by parameter LFr in the
SEt- menu. Only the freewheel, fast stop and DC injection stop commands remain active on
the terminal block. If the speed controller / display module link is broken, the speed controller
locks on an SLF fault.
no