Code
Assignment
Adjustment
range
Factory
setting
-Atr
Automatic restart, after locking on a fault, if the fault has disappeared and
the other operating conditions permit the restart. The restart is performed by
a series of automatic attempts separated by increasingly longer waiting
periods : 1 s, 5 s, 10 s, then 1 min for the following attempts. If the restart
has not taken place after 6 min, the procedure is aborted and the speed
controller remains locked until it is powered down then powered up. The
following faults permit this function : OHF, OLF, USF, ObF, OSF, PHF, OPF,
SLF. The speed controller fault relay remains activated if this function is
active. The speed reference and the operating direction must be maintained.
This function can only be used in 2-wire control (tCC = 2C).
Check that any accidental start does not present any danger to
personnel or equipment.
- no : Function inactive
- YES : Function active
- USF : Function only active for the USF fault
no - YES -
USF
no
-OPL
Enables the motor phase failure fault.
(Inhibition of the fault if a switch is used between the speed controller and
the motor : no).
no : function inactive. YES : function active.
no - YES
YES
-IPL
Enables the line supply phase failure fault.
no : function inactive. YES : function active.
This parameter does not exist on the ER21-0.37K, -0.75K, -1.5K and -2.2K
for a single phase line supply.
The fault is only detected if the motor is on-load (around 0.7 times the
nominal power). At low load, single phase operation does not cause
damage.
no - YES
YES
-StP
Controlled stop on loss of line supply :
Controls the stopping of the motor when there is a loss of line supply,
following a ramp which automatically adapts according to the kinetic energy
restored.
no : function inactive. YES : function active.
no - YES
no