MOUNTING
!
Safety precautions:
The unit must be mounted to a rigid and stable structure.
The unit must be suspended using anchor bolts. Before starting mounting check that the mounting structure has sufficient
loading capacity for the unit weight.
The unit mounting is allowed only after power cut-off and full stop of the rotating parts.
Restrictions:
• Do not operate the unit beyond the determined temperatures, in aggressive and in explosive medias.
• Do not connect the clothes dryer or other similar equipment to the ventilation system.
• Do not use the unit for air/dust mixture handling.
WARNING
The unit mounting position must provide condensate drainage and access
to the terminal box for electric connection and access to the service panel for
maintenance and filter replacement (Fig. 9).
Fig. 9. Minimum service access to the unit
A
- minimum required access distance for water heater installation.
The distance is selected depending on the installation conditions at the
discretion of the installer.
B
= min 850 mm for KOMFORT EC DW600-2
B
= min 800 mm for KOMFORT EC DW1000-4
A
- minimum required access distance for condensate drainage.
The distance is selected depending on the installation conditions at the
discretion of the installer.
B
- minimum required access distance for water heater installation and
condensate drainage. The distance is selected depending on the installation
conditions at the discretion of the installer.
C
- minimum required distance from the service panel to the floor.
C
= min 1000 mm for KOMFORT EC DW1000-2.
C
= min 1300 mm for KOMFORT EC DW3800-2.
KOMFORT EC DW600-2 / KOMFORT EC DW 1000-4
KOMFORT EC DW2000-2 / KOMFORT EC DW 3800-2
min 20 mm
min B
A
min 20 mm
B
A
min C
KOMFORT EC DW v1(6)_EN.indd 9