28
www.blaubergventilatoren.de
KOMFORT EC DW
TECHNICAL MAINTENANCE
Regular technical supervision and maintenance of the unit are required to
ensure the product long service life and non-stop operation.
Disconnect the unit from power supply prior to any maintenance
operations.
Warning! Consider the unit sharp edges! Fulfil maintenance
operations in work gloves!
The recommended unit maintenance periodicity is 3-4 times per year. The
unit technical maintenance includes regular cleaning and other works:
1. Filter maintenance (3-4 times per year).
Dirty filters increase air resistance and decrease supply air volume. Clean the
filters with a vacuum cleaner or flush those with water. After two consecutive
cleanings the filter must be replaced. Install dry filters only! Contact a local
distributor to purchase the filters stated above in the «Technical data» section.
Dirty filters are not considered as a warranty case!
Replace humid and mouldy filters immediately!
Filter removal for
KOMFORT EC DW600-2 / EC DW1000-4
:
1. Remove the 5 screws and take the side service panel off.
2. Pull the filters until they slide off the guides.
Install the filters in the reverse order.
Supply filter
Extract filter
Filter removal for
KOMFORT EC DW2000-2 / EC DW3800-2
:
1. Lift the service panel latches.
2. Open the service panel carefully, supporting it with the hand.
3. Remove the filters from the unit.
2. Heat exchanger maintenance (once per year).
The heat exchanger must be regularly cleaned to maintain high heat
recovery efficiency even in case of the regular filter cleaning. Clean the
heat exchanger with warm detergent solution. Remove the heat exchanger
from the unit and flush it with warm detergent solution. Install the dry heat
exchanger back to the unit.
Heat exchanger removal for
KOMFORT EC DW600-2 / EC DW1000-4
:
1. Remove the 5 screws and take the side service panel off.
2. Pull the heat exchanger and remove it from the unit.
3. Disconnect the contact socket on the bypass wall and remove the
bypass.
4. Remove the second heat exchanger in the same way.
Assemble the parts in the reverse order.
Heat exchanger removal for
KOMFORT EC DW2000-2 / EC DW3800-2
:
1. Lift the service panel latches.
2. Open the service panels supporting those with the hand. Release the
drain pipe from the side of the water heater installation and lower it down.
Release the second drain pipe by pulling the drain pan aside. Install the drain
pan in the reverse order. The heat exchanger removal for further cleaning
should be made by the service department.
3. Fan maintenance (once per year).
The regular filter cleaning may not completely prevent the dust ingress
into the unit, which results in the unit performance decrease. Clean the fan
with a soft cloth or a brush. Cleaning with water, abrasive detergents, sharp
object or chemicals is not allowed.
QF
WARNING!
Cut power supply to the unit off by turning the automatic electric switch QF to OFF position prior to
any maintenance operations.
Take steps to prevent re-activation of the automatic switch.
!
KOMFORT EC DW v1(6)_EN.indd 28
10.08.2015 10:11:18