CHAPTER 8: Testing Twisted-Pair Cable
Test Results
Possible Solutions
NEXT test fails in
Check the terminations closest to where the faulty
one direction but
readings were detected. Follow procedure for “
NEXT
not in the other
test fails for one or more pairs
” to locate fault.
NEXT test indicates
Follow procedure for “
Split Pair
” in WIRE MAP section.
a split pair
NEXT test fails
Check actual results against expected results. Values
intermittently
may be borderline. Simply reterminating a connection
could correct the problem. Follow procedure for “
NEXT
test fails for one or more pairs
” to locate fault.
NEXT passes on
Patch cable may not be a twisted-pair cable. A common
segment from hub
mistake is to use untwisted telephone wire for data
to work-area wall
applications.
plate, but the work-
station has problems
Patch cable could be wired incorrectly. Check twisted
when connected with
pairs per the EIA/TIA pairing. Check patch cable and
its patch cord
rewire or replace as necessary.
Two pairs of the cable may be in use for data and the
other two pairs may be in use for voice.