51
CHAPTER 6: Cable Test Descriptions
2. Press SUMMARY (F3) or ESC to return to the Length test summary
display.
NOTE
Detected impedance changes greater than the Fault Threshold are
displayed as anomalies (Anom1 and Anom2). Fault Threshold is pre-set
at the factory, but can be modified in the SETUP menu. See Chapter 9,
Setup, for Fault Threshold changes.
When the cable length is less than 20 feet, anomalies might not be
detected.
6.4 Attenuation
Attenuation measures the reduction in the signal level as it travels over the
length of a cable.
Attenuation is measured over a range of frequencies. The amount of
attenuation loss is expressed in decibels (dB). A signal is transmitted by
the remote unit and received by the main unit (the signal is one-way).
Attenuation is one of the tests run during Autotest and Quick Check.
It can also be run individually.
Attenuation detects one-way attenuation of each cable pair, poor
connections/terminations, substandard wire, and faulty connectors.
6.4.1 R
UNNING
A
TTENUATION
1. Set the SCAN-LAN VI dial to EXTENDED FUNCTIONS.
2. Press the arrow key to select Attenuation.
F1
F2
F3
F4