8.3.1 Connecting the EMD
The Environmental Monitor Device (EMD) connects to any serial port on the
console server
via a
special EMD Adapter and standard CAT5 cable. The EMD is powered over this serial connection
and communicates using a custom handshake protocol. It is not an RS-232 device and should not
be connected without the adapter:
Plug the male RJ plug on the EMD Adapter into EMD and
then connect it to the
console server
serial port using the
provided UTP cable. If the 6-foot (2-meter) UTP cable
provided with the EMD is not long enough, you can
replace it with a standard CAT5 UTP cable up to 33 feet
(10 meters) long.
Screw the bare wires on any smoke detector, water
detector, vibration sensor, open-door sensor, or general
purpose open/close status sensors into the terminals on
the EMD.
Note
:
You can attach two external sensors onto the terminals on EMDs that are connected to
LES1108A,
LES1116A, and LES1148A
console server
s.
LES1208A, LES1216A, and LES1248A
console server
s
only support attaching a single sensor to each EMD.
You can only use the EMD with a Black Box
console server
; you cannot connect it to standard
RS-232 serial ports on other appliances.
Select
Environmental
as the
Device Type
in the
Serial & Network: Serial Port
menu for the port
to which the EMD will be attached. No particular Common Settings are required.
Click
Apply.
Select the
Serial & Network: Environmental
menu. This will display all the EMD connections
that have already been configured.
Click
Add.