Specify the applicable UPSes, RPCs (and RPC outlets), and Environmental Sensors to
Apply Alert
To
.
Note
An alert notification (SNMP, SMTP etc) is only sent out when there is a transition to or from a
trigger event/level. For example, if a High temperature alert is set at 40 degrees with a 5 degree
hysteresis then an High alert notification will be sent when the sensor temperature reads 40
degrees. The next alert will be sent when the temperature falls below 35 degrees. If the temp was
over 40 degrees when the alert was first set, no high temp notification will be sent.
7.2.4 Configuring alarm sensor alert type
You can set an alert on sensor devices that may be attached to any EMD devices connected to the
console server
:
Select
Alarm Sensor Alert
and then set the time windows when these sensors will not be
monitored. For example, for a door open sensor, you may not want to deactivate the sensor
alert monitoring during the working day (and the default 00:00 settings actively monitor the
sensors 24/7).
Select the
Applicable Alarm Sensor(s)
for this alert and click
Apply.
7.3
Remote Log Storage
Before activating
Serial or Network Port Logging on any port or UPS logging, you must specify where
those logs are to be saved:
Select the
Alerts & Logging: Port Log
menu option and specify the
Server Type
to use, and the
details to enable log server access.