7.8. BOILER OPERATION WITH ACCUMULATING TANK
In some cases the heat energy can be delivered to the consuming devices by accumulating
tank. The formula for determining the minimum needed water quantity for accumulation tank is
given below.
V
sp
– Volume of the accumulation tank, litters.
Q
N
- Nominal heating output, kW.
T
b
- Burning time, h.
Q
H
- Premises heating load, kW.
Q
min
– Minimum heating output, kW.
The heating boiler, which uses not only one fuel type, should operate with accumulation tank,
dimensioned in compliance with the used fuel type requiring highest accumulation tank
volume. Usage of accumulation tank is not necessary when the defined volume is lower than
300 litres.
7.9. TRANSPORTATION AND STORAGE
The boilers for expedition are offered by the manufacturer on a wooden pallet and secured
against moving with cap bolts. The boilers should not be transported in position different from
their base (normal operating position).
It is necessary to ensure at least the minimum conditions for preservation of the boilers during
their storage and transportation.
During transportation and storage the boilers packages and cover panels should not be
pressed.
Danger
The boilers should not be moved or transported without using forklifts, transport
carts or other wheel based transport utilities.
Figure 16. Boiler transportation.