122
|
english
11. Technical data
Supply voltage
1×230 V ±10%, 50/60 Hz, PE
Motor protection
External motor protection is not required
Type of protection
IP 44 (EN 60529)
Winding category
Insulation category F
Temperature category
TF 110 (EN 60335-2-51)
Media temperature
+15°C to +110°C (ModulA RED)
+15°C to +85°C (ModulA BLUE)
Ambient temperature
max. 40°C
In transportation: –40 °C up to +70 °C
Maximum operating pressure
The maximum operating pressure is given on the nameplate:
PN 6: 6bar
PN 10: 10bar
PN 16: 16bar
Noise
Sound pressure level under 43 dB(A)
Leakage current
The mains filter of the pump causes a leakage current
to the earth of <3.5 during operation
Power consumption
when pump switched off
<3W
Performance factor cos-phi
The ModulA has an integrated performance factor correction filter
(PFC). This ensures that cos-phi is always between 0.98 and 0.99
and is therefore kept very close to the ideal value 1.
EMV (electromagnetic
compatibility)
EN 55014-1:2006, EN 55014-2:1997,
EN 61000-3-3:2008 and EN 61000-3-2:2006
12. Disposal
This ModulA circulation pump was developed with sustainability in mind. This also includes
waste prevention and recyclability of materials. This product as well as its parts must be
disposed of according to the local regulations.