108
|
english
5.2 Connection of the power supply
The pump must be protected on-site (min. 10 A, slow) and must be connected to an
external mains switch. All cables used must have a heat resistance of up to 85 °C.
They must not be in contact with the pipe or the pump and motor casing.
All cables must be connected in accordance with EN 60204-1 and EN 50174-2: 2000.
The electrical connection must be made as indicated on the nameplate.
ModulA…
Nominal current [A]
Output P
1
[W]
ModulA 25-4 180
0.10 – 0.39
11 – 52
ModulA 25-6 180
0.10 – 0.64
12 – 86
ModulA 25-8 180
0.10 – 0.91
11 – 120
ModulA 25-10 180
0.10 – 1.24
11 – 158
ModulA 25-12 180
0.10 – 1.47
11 – 188
ModulA 32-4 170
0.10 – 0.5
11 – 70
ModulA 32-6 170
0.10 – 0.79
11 – 105
ModulA 32-8 170
0.10 – 1.03
11 – 139
ModulA 32-10 170
0.10 – 1.35
11 – 175
ModulA 32-12 170
0.10 – 1.45
11 – 187
ModulA 32-4 180
0.10 – 0.50
11 – 70
ModulA 32-6 180, ModulA-D 32-6 180
0.10 – 0.79
11 – 105
ModulA 32-8 180, ModulA-D 32-8 180
0.10 – 1.03
11 – 139
ModulA 32-10 180
0.10 – 1.35
11 – 175
ModulA 32-12 180
0.10 – 1.45
11 – 187
ModulA 32F-6 220, ModulA-D 32F-6 220
0.10 – 0.79
11 – 105
ModulA 40-4 220
0.13 – 0.68
15 – 91
ModulA 40-6 220, ModulA-D 40-6 220
0.13 – 1.34
16 – 171
ModulA 40-11 250
0.11 – 1.52
13 – 189
ModulA 50-11 220
0.11 – 1.45
13 – 187
Example of a typical mains connection, 1x230V ±10%, 50 / 60Hz
FI
1
2
N
L
L
N
961807_01
2 Externer Schalter
1 Sicherung (min.10A, träge)
Legende:
Netzanschluss 1x230V
ModulA
Alpha-Stecker BA
CH-3110 Münsingen
Biral AG
Massstab
Zeichnungsnummer
1:1
I
II
Datum
Änd.Index
Visum
Ersetzt durch:
Ersatz für:
961807
Änd.Index
Freigabe
geprüft
gezeichnet 16.10.2014
PDM_Nr
TD-0026642
01
24.02.2015
24.02.2015
ts
ts
ts
01
ts
24.02.2015
Protection
(minimum 10A, inert)
external switch
Содержание 25-10 180