Operating the F01-2000
Section 5: Operating the F01-2000
Figure 26
5.7
Remote Control
Place the 3-position selector in REMOTE to transfer the actuator control to a remote device.
Local OPEN or CLOSE operation will be inhibited. Only local STOP control remains active.
Using the “VIEW and SET-UP” features may configure different control modes. The remote
controls are opto-coupled.
A non-regulated 24 V DC voltage (variable from 23 to 27 V DC, max. 4 W) is available on
the actuator terminal board to supply the remote controls or external devices.
5.7.1
Remote Commands
Using the “VIEW and SET-UP” features may configure different control modes.
4 WIRES
(see the remote connections diagram) In “4 wires latched” (OPEN, CLOSE, STOP,
COMMON) mode, with the OPEN or CLOSE signal switched to ON, the motor is energized,
and it runs on after the signal returns to OFF. To stop the motor, press STOP. To reverse the
direction, press STOP and then press the button relevant to the opposite direction.
3 WIRES
(see the remote connections diagram) With option “3 wires” (OPEN, CLOSE,
COMMON), the actuator can be driven in either “push-to- run” or “latched with instant
reverse” mode.
In “ push-to-run ” mode, the actuator can be driven to the desired position by switching
the OPEN or CLOSE signal to ON. As the signal returns to OFF, the motor is de-energized.
In “latched with instant reverse” mode, when the OPEN or CLOSE signal switches to ON,
the motor is energized, and it runs on after the signal returns to OFF. If the signal relevant
to the opposite direction goes ON, the actuator reverses its direction and maintains the
new direction also if the signal returns to OFF.
5.6
Lock of the 3-Position Selector
The 3-position selector can be locked in any of its three positions by means of a padlock.