O
PERATION
WITH
B
-
TOUCH
A
IR
HEATER
en-58
en
Values for inputs 1 and 2
The function of input 3 is set via other functions in the
b-touch
control panel. In addition, the function of this parameter (60.3)
is controlled via the settings file or via Modbus.
Values for input 3
Release delay input 1
When you use input 1, you can make the effect of an input sig-
nal persist for some time after the signal has been given
(‘release delay’).
61. Function of outputs
The unit has a connection (terminal block X510) for three
output signals: these can be used for controlling the central
heating system, for example, or for transmitting status
reports to a Building Management System (BMS).
By default, output 3 is used for error messages.
The outputs work independently of each other.
V
ALUE
O
PTION
D
ESCRIPTION
0
No function
The input has no function.
1
Unit off locally – NO
The unit is switched OFF when the contact is closed. (This only works with
the units to which the input signal is directly connected (locally).)
6
Heating off
The heating is switched OFF when the contact is closed.
9
Release – NO
The user is allowed to switch the unit on and off when the contact is closed.
10
Dirty filter – NO
Displays a “dirty filter” warning if the contact is closed.
21
Switch all units on
All units are switched ON when the contact is closed.
51
Unit off locally – NC
The unit is switched OFF when the contact is open. (This only works with the
units to which the input signal is directly connected (locally).)
56
Heating on
(dependent on soft-
ware version)
The heating is switched ON when the contact is closed.
59
Release – NC
The user is allowed to switch the unit on and off when the contact is open.
60
Dirty filter – NC
Displays a “dirty filter” warning if the contact is open.
71
All units off
All units are switched OFF when the contact is closed.
V
ALUE
O
PTION
D
ESCRIPTION
21
Switch all units on
All units are switched ON when the contact is closed.
71
All units off
All units are switched OFF when the contact is closed.