UPSI-2412
Revision 1
25
CONNECTOR
PART NO.
COUNTERPART NO.
V
IN
/V
OUT
(X1)
Würth Elektronik 691317510004
Würth Elektronik 691340500004
Relay (X6)
Würth Elektronik 68800211722
Würth Elektronik 688002113322
USB, type B socket (X3)
Würth Elektronik 61400416121
USB Typ B Stecker
USB, 2.54 mm pin header (X8) Würth Elektronik 61300511121
2.54 mm female header or equal
RS232, MicroMatch (X5)
Würth Elektronik 690367281076
MicroMatch pin connection (male),
IDC or equal
Battery power (X2)
Würth Elektronik 64900629522
Würth Elektronik 649006113322
Battery data (X4)
Würth Elektronik 62400821722
Würth Elektronik 624008213322
Temperature sensor (X7)
Hirose DF11-4DP-20S
Hirose DF11-4DS-2C
External status LED (JP4)
Würth Elektronik 61300211121
2.54 mm female header or equal
F8 Overview connector / Counterpart with description / Scope of delivery
SCOPE OF DELIVERY
QUANTITY
DESCRIPTION
1x device
UPSI-2412 - DC UPS
1x
V
IN
/ V
OUT
connector counterpart
1x
Relay cable, 50 cm, AWG 22
F9 Charging time
Charging times depend on energy storage, input voltage and the load current.
F10 Reverse polarity / Overcurrent / Short circuit
Reverse polarity:
The device has passive reverse polarity protection at the input. In the event of reverse polarity, the input fuse
trips irreversibly and the device goes into a safe state.
Overcurrent:
If the load current at the output is too high, the device switches it off. For maximally allowed current values
and peak current values refer to chapter D „Technical Data”. The status LED indicates the error status by means
of a very rapid flashing sequence. A restart attempt occurs every 10 seconds in normal mode. During battery
mode there is no restart attempt.