Electronic control/ignition p.c.b.
21
seconds. The lamps will flash a number of times corre-
sponding to the setting (Fig. 9.11).
4
To change the setting turn the knob B on a posi-
tion corresponding to the desired delay.
By turning the knob B, the lock---out signal lamp
D blinks quickly (2 per seconds) indicating that
the setting has changed and must be memo-
rised.
Setting No.
B
Delay (minutes)
1
4
2
3
5
6
7
0
1 1/2
3
4
5 1/2
7
8 1/2
Fig. 9.11
5
To memorize the setting keep pressed the reset
button C for about 5 seconds until the lights E
briefly blinks simultaneously.
6
To reset the boiler to the normal operation turn it
OFF and ON by the function selector knob A. In
any case, the boiler automatically resets to its nor-
mal operation after 10 minutes.
Factory setting = 3 minutes
9.8
Combi / C.H. only mode setting
Two different options are available on the Electronic
control/ignition p.c.b. and proper setting must be done
after a replacement of the p.c.b.
1
Remove the front panel of the case.
2
Turn ON the power supply. Lamps E give the in-
dication as in Fig. 9.12.
Where:
Lamp OFF
Lamp Flashing
Fig. 9.12
3
Position the function selector A as in NO TAG and
disconnect the C.h. temperature probe.
4
Keep pressed the reset button C for about 10 sec-
onds (Fig. 9.13) until the lock---out signal lamp D
blinks.
5
Connect the c.h.temperature probe.
C
E
D
A
B
Fig. 9.13
6
Press the reset button C repeatedly (2 times) until
the lamps E give the indication as in Fig. 9.14
(boiler mode).
Where:
Lamp OFF
Lamp ON
Fig. 9.14
At this step it is possible to visualize the current setting
by keeping the reset button C pressed for more than 5
seconds. The lamps E will flash a number of times
corresponding to the setting (Fig. 9.15).
B
M110B.24SM/...
M110B.32SM/...
1 flash
M110B.24SR/...
4 flashes
Fig. 9.15
7
To change the setting turn the knob B on a posi-
tion corresponding to the boiler models
(Fig. 9.15). By turning the knob B, the lock---out
signal lamp D blinks quickly (2 per seconds) indi-
cating that the setting has changed and must be
memorised.
8
To memorize the setting keep pressed the reset
button C for about 5 seconds until the lights E
briefly blinks simultaneously.
9
Press the reset button C once until the lamps E
give the indication as in Fig. 9.16 (boiler mode).
Where:
Lamp OFF
Lamp ON
Fig. 9.16
It’s now possible to check the current setting by pres-
sing reset button C for more than 5 seconds. The three
lamps E will flash a number of times corresponding to
the setting as in Fig. 9.17 (once for the combination and
four times for system boilers). At this point only the right
green light flashes.
B
M110B.24SM/...
M110B.32SM/...
1 flash
M110B.24SR/...
4 flashes