Thank you for buying this product, our company is sure that you will be
more than satisfied with the performance of the product.
This product is supplied with a “WARNINGS” leaflet and an
“INSTRUCTION MANUAL”. These should both be read carefully as
they provide important information about safety, installation,
operation and maintenance.
This product complies with recognized technical standards and safety
regulations. We declare that this product is in conformity with the
following European Directives: 89/336/EEC and 73/23/EEC (amended
by RL 91/263/EEC, 92/31/EEC and 93/68/EEC).

1) GENERAL OUTLINE

The POLLUCE 2M Mod. Unit is suitable for operating 1 or 2 ARM2
series controllers, and has been designed to automate various types of
overhead doors.
The unit can be: Included with the ARM2 series (fig. 1).
Fitted onto a wall panel (fig. 2) for use with the series without the control
unit (ARM2-SQ series). 2 possible configurations are available in case
two-motor overhead door automation is required:
No. 1 ARM2 + No. 1 ARM2-SQ.
No. 2 ARM2-SQ + No. 1 2M POLLUCE with panel, wall-mounted.

2) TECHNICAL SPECIFICATIONS

Power supply voltage:

230V

±

6% 50/60Hz (*)

No load current:

150 (varies depending
on accessories)

Max. absorbed rating:

300W for motor

Power supply to accessories:

24Vac 

±

 20%

Max. current for accessories:

0.25A (6VA)

Working temperature:

-20

°

 +60

°

C

Max. No. of manoeuvres in 24h:

40

Automatic closing time TCA:

adjustable 0 - 90 sec

Operation time TW:

adjustable 0 - 40 sec

Time-set courtesy light:

230V - 40W max. 90 sec

Blinker:

230V - 40W max.

(*) For 110V power supply see fuse values in figs. 1 - 2.

3) FUNCTION LOGIC
START: four-step logic: (DIP5 OFF)

gate closed:

opens

on opening:

stops and inserts TCA if configured

gate opened:

closes

on closing:

stops but will not insert TCA

after stopping:

moves to open

START: two-step logic: (DIP5 ON)

door closed:

opens

on opening:

stops and inserts TCA if configured

door opened:

closes

on closing:

opens

after stopping:

opens

STOP: Stops the gate until restart
PHOT: Photocell input

Configured by means of DIP3

SWO:

 

Stops door at end of opening stroke

SWC: stops door at end of closing stroke
SCA: Door open warning light

with door closed:

off

with door opening:

on

with door opened:

on

with door closing:

blinking

4) DIP-SWITCH SELECTION
DIP1: Swift Closure (SCL)

ON: When there is movement across the photocells, either on entry
or on exit, at the last disengagement of the photocells, the door closes
automatically without waiting for the TCA to end. This function is
recommended whenever the safety conditions of the installation allow
the configuration of DIP3-ON (the photocells are only active on closing).
OFF: Function deactivated.

DIP2:Blocks impulses on opening (IBL)

ON: Will not accept START commands during opening phase.
OFF: Accepts START commands during opening phase.

DIP3:Photocell on opening (FCH)

ON: Photocell is only active on closing.
OFF: Photocell is active both on closing and opening.

DIP4:Automatic closing time (TCA)

ON: Automatic closing time inserted (adjustable 0 - 90 sec with trimmer TW).
OFF: Automatic closing time excluded.

DIP5:Control logic (2P/4P)

ON: Activates two-step logic (see paragraph on start).
OFF: Activates four-step logic (see paragraph on start).

DIP6:Not used (always leave OFF).

5) TRIMMER ADJUSTMENT
TCA

Sets the automatic closing time, after which the door

closes automatically (adjustable from 0 to 90 sec).

TW

Sets the motor operating time, after which the motor stops

(adjustable from 0 to 40 sec). Allows the motor to be stopped  in  the
case where, for any reason, the limit microswitch is not detected.

6) MOTOR TORQUE SETTING

The POLLUCE 2M mod. board is supplied by a transformer which also
allows the electric motor torque to be selected.

DANGER: The transformer terminals are connected to the mains
power supply. Disconnect the mains power supply before doing
any work on the installation. To select the torque tap, remove the
transformer protection and remember to replace it afterwards.

The selection is carried out by moving connection “55” of the transformer
to one of the 4 taps “T1 - T2 - T3 - T4” as shown in figs. 1 -2.
In the case where the overhead door produces excessive friction,
which can be detected by the force required to open the door
manually, check the balancing or carry out the necessary maintenance
to eliminate it.

WARNING: Excessive torque adjustment may jeopardize the anti-
squash safety function.
On the other hand insufficient torque adjustment may not guarantee
correct opening or closing strokes.

7) POLLUCE 2M TERMINAL BOARD CONNECTIONS

 (fig. 3)

JP14

1-10

Single phase power supply 230V

±

6% 50/60Hz (1=L/10=N)

2-5

Not used

3-4

M1 motor capacitor

11-12-13

M1 Motor connection (12 common, 11-13 run)

6-7

M2 motor capacitor

14-15-16

M2 motor connection (15 common, 14-16 run)

8-17

Time-set courtesy light connection (25W max.)

9-18

Blinker connection 230V (40W max.)

JP7

25

Control common terminal (corresponding to terminal 19)

19-20

Start button (opens - closes N.O.)

19-26

Lock button (N.C.). When not used leave bridged.

19-21

Electric edge or photocell input (N.C.).
When not used leave bridged.

19-22

Closing limit microswitch connection (SWC)

19-27

Opening limit microswitch connection (SWO)

28-23

24 Vac 0.25A max. (6VA) outlet (power supply to

                       photocell or other devices)
23-29

Gate open warning light 24V (3W max.)

24-30

Antenna input for radio receiver board (24 signal - 30 braid).

JP1

Radio receiver board connector. 1-2 channels.

JP8

Second radio channel output from the double-channel
receiving board (not fitted) (dry contact N.O.)

8) POLLUCE 2E TERMINAL BOARD CONNECTIONS

 (fig. 4)

Another version is also available which allows the connection of a 12V
electric lock. This version is known as POLLUCE 2E.
Fig. 4 only shows the part of the terminal board regarding the electric
lock connection. For all other connections, reference should made to
the terminal board in fig. 3.

GB

Содержание POLLUCE 2M

Страница 1: ...RUCTIONS INSTRUCTIONS MONTAGEANLEITUNG INSTRUCCIONES GB F D E CENTRALINA DI COMANDO CONTROL UNIT UNITÉ DE COMMANDE STEUERUNG CENTRAL DE MANDOS CENTRAL DE COMANDO POLLUCE 2M 2E D811199A ver 02 10 07 00 P 8 027908 113931 ...

Страница 2: ...le attive solo in chiusura OFF Fotocellule attive in chiusura ed apertura DIP4 Tempo di chiusura automatica TCA ON Tempo di chiusura automatica inserita regolabile da 0 a 90sec con Trimmer TW OFF Tempo di chiusura automatica escluso DIP5 Logica di comando 2P 4P ON Attiva logica a 2 passi vedere paragrafo start OFF Attiva logica a 4 passi vedere paragrafo start DIP6 Non utilizzato Lasciare sempre i...

Страница 3: ...phase DIP3 Photocell on opening FCH ON Photocell is only active on closing OFF Photocell is active both on closing and opening DIP4 Automatic closing time TCA ON Automaticclosingtimeinserted adjustable0 90secwithtrimmerTW OFF Automatic closing time excluded DIP5 Control logic 2P 4P ON Activates two step logic see paragraph on start OFF Activates four step logic see paragraph on start DIP6 Not used...

Страница 4: ...e START DIP3 Cellule photoélectriques en ouverture FCH ON Cellules photoélectriques actives seulement en fermeture OFF Cellules photoélectriques actives en fermeture et en ouverture DIP4 Temps de fermeture automatique TCA ON TCA Temps de fermeture automatique actif réglable de 0 à 90 s avec condensateur d équilibrage TW OFF Temps de fermeture automatique non actif DIP5 Logique de commande 2P 4P ON...

Страница 5: ...ichtschranken nur beim Schließvorgang aktiviert OFF Lichtschranken beim Öffnungs und Schließvorgang aktiviert DIP4 Dauer der automatischen Schließung TCA ON Automatische Schließzeit aktiviert einstellbar von 0 bis 99 Sek mit Trimmer TW OFF Automatische Schließzeit nicht aktiviert DIP5 Steuerlogik 2S 4S ON 2 Schritt Logik ist aktiviert siehe Absatz Start OFF 4 Schritt Logik ist aktiviert siehe Absa...

Страница 6: ...as en apertura FCH ON Fotocélulas activas sólo en el cierre OFF Fotocélulas activas en cierre y apertura DIP4 Tiempo de cierre automático TCA ON Tiempo de cierre automático conectado regulable de 0 a 90 seg con Trimmer TW OFF Tiempo de cierre automático excluido DIP5 Lógica de mando 2P 4P ON Activa lógica de 2 pasos véase párrafo start OFF Activa lógica de 4 pasos véase párrafo start DIP6 No utili...

Страница 7: ...m abertura FCH ON fotocélulas ativas só em fechamento OFF fotocélulas ativas em fechamento e abertura DIP4 tempo de fechamento automático TCA ON tempo de fechamento automático inserido ajustável de 0 a 90s com Trimmer TW OFF tempo de fechamento automático excluído DIP5 lógica de comando 2P 4P ON ativa a lógica a 2 passos ver parágrafo start OFF ativa a lógica a 2 passos ver parágrafo start DIP6 nã...

Страница 8: ...5A T 230V F2 T2 N T4 T3 T1 L JP3 L JP13 T JP2 N ON 6 5 4 3 2 1 JP14 11 33 12V 0V 12V JP5 0V JP6 12V JP8 CH2 JP4 12V 30 29 28 27 26 25 20 24 23 22 21 19 JP4 17 16 15 14 13 12 11 10 2 9 8 7 6 5 4 3 1 18 TW TCA 66 55 44 JP4 12V JP5 0V 11 33 22 JP6 12V 12V 0V JP2 N JP13 T JP3 L 0Vac 12V T1 120 230Vac T4 200 T3 170 T2 140 MAX 25W MAX 40W N 230V 6 F 230V 6 SCA NC OV 24V AC SWC NC SWO PHOT NC STOP START ...

Отзывы: