background image

- 19 -

Control unit

EN

6.3 

J5

 OUTPUTS/ACCESSORIES POWER SUPPLY

6.1

 

J1

 CONTROL UNIT  POWER SUPPLY

In order to reach the level of safety required by current regulations, follow these prescriptions carefully.
1)  Make all the connections in the terminal block after carefully reading the instructions given in this manual and observing the general
 

rules and technical standards concerning electrical systems installations.

2) Always fi t an omnipolar circuit breaker with a contact gap of at least 3 mm.
3)  Install a diff erential circuit breaker with a threshold of 30 mA.
4)  Check the eff ectiveness of the protective earth and connect to it all the parts of the automation fi tted with a terminal or grounding
 cable.
5)  Fit at least one external warning device, such as a traffi

  c light or fl ashing light, along with a warning or danger sign.

6)  Fit all the safety devices required by the type of installation, taking into consideration the risks it can cause.
7)  Separate in the ducts the power lines (1.5 mm

2  

min. section) from the low-voltage signal lines (0.5 mm

min. section).

230Vac 50/60Hz power supply.
Connect the LINE and NEUTRAL as shown on the board. Use cable type H07RN-F 2x1.5+E min.
Connect the yellow/green EARTH wire of the power supply mains to the earth terminal of the appliance.

6. INPUT AND OUTPUT FUNCTIONALITY AND CONNECTIONS

OUT24 

          

Output 24Vac, 1A max

OUT2 

       

Programmable dry relay output, max. 500mA 24 Vac/dc (parameter 



 - level 2)

 

 

OUT3 

        

 

Programmable dry relay output, max. 500mA 24 Vac/dc (parameter 



 - level 2)

OUT4 

         

Programmable dry relay output, max. 500mA 24 Vac/dc (parameter 



 - level 2)

OUT5/CH2 RX

Programmable dry relay output, max. 500mA 24 Vac/dc or

 

N.O. output of the 2nd radio receiver channel 

(parameter 



 - level 2)

OUT2

OUT2

OUT3

OUT3

OUT4

OUT4

CH2 

RX

24 Vac

4. INSTALLATION SAFETY

3. TECHNICAL SPECIFICATIONS

- Power supply:......................................................230Vac ±10%, 50/60Hz (115Vac on request)

- Flashing light output:...............................................................................................230Vac; 40W max

- Accessory output:...........................................................................................24Vac; 24W - 1A max

      Barriers with standard booms are automatically selected. For special booms (barrier 35 only), before operating the automation, 

make sure to have correctly selected the barrier/boom type as follows:

 

- Press and hold down buttons F and + for 5 seconds.

 

- Select the barrier/boom type using b/-.

 

- Press  together F and + to confi rm.

 

- Only select the actual barrier/boom being used:

The Company is not liable for injury to people or animals or damage to things in the case of wrong selection of the barrier.
Selecting wrong barrier/boom voids warranty.

          5. PRELIMINARY OPERATIONS

6.2 

J4

 FLASHING LIGHT OUTPUT

OUT

LAMP

Output 230Vac, 40W max.

L

N

OUT5

OUT5

BARRIER TYPE SELECTION



MAXIMA ULTRA 68 (auto select)



ATM 90° boom (ULTRA 35 only)



MAXIMA ULTRA 35 (auto select)



ATM 180° boom (ULTRA 35 only)



Carbon boom (ULTRA 35 only)

ENGLISH

Содержание CSB Xtreme (1.2)

Страница 1: ...CENTRALE DI COMANDO pag 3 MANUALE D INSTALLAZIONE ED USO CONTROL UNIT pag 17 INSTALLATION AND OPERATION MANUAL IT EN CSB Xtreme 1 2 ...

Страница 2: ...NSION CONNECTOR 21 6 8 J12 RADIO PROGRAMMER CONNECTOR 21 7 INVERTER CONNECTIONS 21 7 1 INVERTER 21 7 2 J2 POWER SUPPLY 21 7 3 M MOTOR 21 7 4 J9 INVERTER SIGNALS 21 8 PROGRAMMING 22 8 1 BASIC FUNCTIONS 22 8 2 1ST LEVEL PROGRAMMING 23 8 3 2ND LEVEL PROGRAMMING 24 8 4 3RD LEVEL PROGRAMMING 25 8 5 4TH LEVEL PROGRAMMING 26 9 RADIO RECEIVER 27 9 1 RECEIVER TECHNICAL SPECIFICATIONS 27 9 2 RADIO CHANNEL F...

Страница 3: ...puts antenna J8 Boom lights connector J9 Inverter signals J10 Expansion connector J12 Radio programmer connector DL 3 digit LED display START START control button F1 Transformer primary fuse 500 mAT 230Vac 1 AT 115Vac 5x20mm F2 Line fuse control board and inverter 4 AT 230Vac 8 AT 115Vac 5x20 mm F3 F4 Transformer secondaries fuses 2 AT 5x20mm F Programming push buttons PR1 PR2 Radio receiver progr...

Страница 4: ... of the appliance 6 INPUT AND OUTPUT FUNCTIONALITY AND CONNECTIONS OUT24 Output 24Vac 1A max OUT2 Programmable dry relay output max 500mA 24 Vac dc parameter level 2 OUT3 Programmable dry relay output max 500mA 24 Vac dc parameter level 2 OUT4 Programmable dry relay output max 500mA 24 Vac dc parameter level 2 OUT5 CH2 RX Programmable dry relay output max 500mA 24 Vac dc or N O output of the 2nd r...

Страница 5: ...ity over CLOSE command and can be kept always activated until necessary Connect loop detectors clocks daily or weekly timers here where and if necessary FTC COM STOP COM FCA COM FCC COM START COM PDM COM OPEN COM CLOSE COM UPS V BROWN BLACK BLUE SHIELD ANT CLOSE N O input for closing It allows the automation to be closed only if the safety devices have not triggered Operating mode programmable wit...

Страница 6: ...INVERTER CONTROL UNIT INVERTER 7 4 J9 INVERTER SIGNALS 7 2 J2 POWER SUPPLY 7 3 MOTOR M CC Brown F Yellow R White B Gray A Pink GND Green COM Brown FWD Yellow REV White N L 6 6 J8 BOOM LIGHTS CONNECTOR 6 7 J10 EXPANSION CONNECTOR COM GRN RED J2 J9 M FLA OUT NO CC F R S1 S2 P24 FLB FLC CC VI P5 FM B A RS 485 GND COM FWD REV OUT J9 TCP IP SC RS485 ENGLISH ...

Страница 7: ...iting the menu selecting the function with key F PLEASE NOTE If there is a black out when programming all changes will be lost F F F 2nd level arm closed F F F F F F F F F F F F F x 2 x 2 x 5 x 3 x 4 1st level programming Selects each single 1st level function see table par 8 2 Selects each single 2nd level function see table par 8 3 Selects each single 4th level function see table par 8 5 Changes...

Страница 8: ...light when moving and with the arm closed on red light when stopped and on green light when the arm is open Flashing red light when moving off red light when the arm is closed and on green light when the arm is open Flashing red light when moving on red light when the arm is closed and on green light when the arm is open Pause time expres sed in seconds Resetting default parameters see notes after...

Страница 9: ... in factory parameter value set during installation must be indica ted if DEFAULT value is modified Stop due to photocell triggering Opening due to photocell triggering Photocell triggering pause Stop due to encoder triggering Opening due to encoder triggering Pause due to encoder triggering Maximum working time in opening reached Maximum working time in closing reached Par Function Settable data ...

Страница 10: ... or quasi sine wave UPS Internal detector UPS input not connected Pure sinusoidal wave UPS with mains failure output Connect mains failure output to UPS input Pure sinusoidal wave UPS without mains failure output Use 230Vac relais bobbin connected to mains supply close contacts to UPS input Arm locking device configuration To use the arm locking device connect the enabling contact to OUT2 or OUT3 ...

Страница 11: ...en anyway Velocity selection input By enabling this parameter bar speed can be adjusted via the PDM input If the PDM is activated and parameter enabled the barrier moves at a speed equal to 60 of maximum speed both when ope ning and closing Advance electric lock disengagement This parameter adjusts the delay between electo lock deactivation and engine start to allow the resetting of the residual m...

Страница 12: ...ase of standard installations where no advanced functions are required it is possible to proceed to manual storage of the transmitters making reference to programming table A and to the example for basic programming 1 If you wish the transmitter to activate output 1 press pushbutton PR1 otherwise if you wish the transmitter to activate output 2 press pushbutton PR2 2 When LED DL1 starts blinking p...

Страница 13: ... 28 ...

Страница 14: ...ting the barrier closure as long as barrier is occupied ENTRY The recognition system enables bar rier opening IfthecoilS1isnotoccupiedwithinthe pause time the barrier closes again 11 CONTROLLED ENTRY AND AUTOMATIC EXIT S2 S1 PARAMETER DATA DESCRIPTION Automatic The close control closes when pressed and released and also functions as a safety system Advanced Setup controlled entry and automatic exi...

Страница 15: ...ver lights Indicates that scheduled maintenance is required Check the parameters 2ND level 2ND level 2ND level Current from to ground leakage problem the Inverter have a built in high attenuation noise filter and are grounded via a capacitor A switch makes to reduce leakage current from to ground The reducing the load means though non conformity with the EMC standard on the inverter itself Do swit...

Страница 16: ...Signatures 1 Tecnico Technician Cliente Customer 2 Tecnico Technician Cliente Customer 3 Tecnico Technician Cliente Customer 4 Tecnico Technician Cliente Customer 5 Tecnico Technician Cliente Customer 6 Tecnico Technician Cliente Customer 7 Tecnico Technician Cliente Customer 8 Tecnico Technician Cliente Customer 9 Tecnico Technician Cliente Customer 10 Tecnico Technician Cliente Customer REGISTRO...

Страница 17: ...400 Nivelles www bftbenelux be POLAND BFT POLSKA SP Z O O 05 091 ZĄBKI www bft pl CROATIA BFT ADRIA D O O 51218 Drazice Rijeka www bft hr PORTUGAL BFT SA COMERCIO DE AUTOMATISMOS E MATERIAL DE SEGURANCIA 3020 305 Coimbra www bftportugal com CZECH REPUBLIC BFT CZ S R O Praha www bft it TURKEY BFT OTOMATIK KAPI SISTEMELERI SANAY VE Istanbul www bftotomasyon com tr RUSSIA BFT RUSSIA 111020 Moscow www...

Отзывы: