ENGLISH

INSTALLER WARNINGS

Anything that is not explicitly provided for in the installation ma-

nual  is  not  allowed.  The  operator’s  proper  operation  can  only  be 

guaranteed if the information given is complied with. The Firm shall 

not be answerable for damage caused by failure to comply with the 

instructions featured herein.

While we will not alter the product’s essential features, the Firm re-

serves the right, at any time, to make those changes deemed oppor-

tune to improve the product from a technical, design or commercial 

point  of  view,  and  will  not  be  required  to  update  this  publication 

accordingly.

WARNING! Important safety instructions. Carefully read and comply with 

all the warnings and instructions that come with the product as incorrect 

installation can cause injury to people and animals and damage to proper-

ty. The warnings and instructions give important information regarding 

safety, installation, use and maintenance. Keep hold of instructions so that 

you can attach them to the technical file and keep them handy for future 

reference.

GENERAL SAFETY

This product has been designed and built solely for the purpose indicated herein. 

Uses other than those indicated herein might cause damage to the product and 

create a hazard.

- The units making up the machine and its installation must meet the requirements 

of the following European Directives, where applicable: 2004/108/EC, 2006/95/

EC, 2006/42/EC, 89/106/EC, 99/05/EC and later amendments. For all countries 

outside the EEC, it is advisable to comply with the standards mentioned, in 

addition to any national standards in force, to achieve a good level of safety.

- The Manufacturer of this product (hereinafter referred to as the “Firm”) disclaims 

all responsibility resulting from improper use or any use other than that for 

which the product has been designed, as indicated herein, as well as for failure 

to apply Good Practice in the construction of entry systems (doors, gates, etc.) 

and for deformation that could occur during use.

- Installation must be carried out by qualified personnel (professional installer, 

according to EN 12635), in compliance with Good Practice and current code.

- Before commencing installation, check the product for damage.

- Before installing the product, make all structural changes required to produce 

safety gaps and to provide protection from or isolate all crushing, shearing and 

dragging hazard areas and danger zones in general.  Check that the existing 

structure meets the necessary strength and stability requirements.

- The Firm is not responsible for failure to apply Good Practice in the construction 

and maintenance of the doors, gates, etc. to be motorized, or for deformation 

that might occur during use. 

- Make sure the stated temperature range is compatible with the site in which the 

automated system is due to be installed.

- Do not install this product in an explosive atmosphere: the presence of flammable 

fumes or gas constitutes a serious safety hazard.

- Disconnect the electricity supply before performing any work on the system. 

Also disconnect buffer batteries, if any are connected.

- Before connecting the power supply, make sure the product’s ratings match the 

mains ratings and that a suitable residual current circuit breaker and overcurrent 

protection device have been installed upline from the electrical system. Have 

the automated system’s mains power supply fitted with a switch or omnipolar 

thermal-magnetic circuit breaker with a contact separation of at least 3.0mm 

and any other equipment required by code.

- Make sure that upline from the mains power supply there is a residual current 

circuit breaker that trips at no more than 0.03A as well as any other equipment 

required by code.

- Make sure the earth system has been installed correctly: earth all the metal parts 

belonging to the entry system (doors, gates, etc.) and all parts of the system 

featuring an earth terminal.

- Installation must be carried out using safety devices and controls that meet 

standards EN 12978 and EN 12453.

- Impact forces can be reduced by using deformable edges.

- In the event impact forces exceed the values laid down by the relevant standards, 

apply electro-sensitive or pressure-sensitive devices.

- Apply all safety devices (photocells, safety edges, etc.) required to keep the 

area free of impact, crushing, dragging and shearing hazards. Bear in mind the 

standards and directives in force, Good Practice criteria, intended use, the in-

stallation environment, the operating logic of the system and forces generated 

by the automated system.

- Apply all signs required by current code to identify hazardous areas (residual 

risks). All installations must be visibly identified in compliance with the provisions 

of standard EN 13241-1.

- This product cannot be installed on leaves incorporating doors (unless the motor 

can be activated only when the door is closed).

- If the automated system is installed at a height of less than 2.5 m or is accessible, 

the electrical and mechanical parts must be suitably protected.

- Install any fixed controls in a position where they will not cause a hazard, away 

from moving parts. More specifically, hold-to-run controls must be positioned 

within direct sight of the part being controlled and, unless they are key operated, 

must be installed at a height of at least 1.5 m and in a place where they cannot 

be reached by the public.

- Apply at least one warning light (flashing light) in a visible position, and also 

attach a Warning sign to the structure. 

- Attach a label near the operating device, in a permanent fashion, with information 

on how to operate the automated system’s manual release.

- Make sure that, during operation, mechanical risks are avoided or relevant protec-

tive measures taken and, more specifically, that nothing can be banged, crushed, 

caught or cut between the part being operated and surrounding parts.

- Once installation is complete, make sure the motor automation settings are 

correct and that the safety and release systems are working properly.

- Only use original spare parts for any maintenance or repair work. The Firm di-

sclaims all responsibility for the correct operation and safety of the automated 

system if parts from other manufacturers are used.

- Do not make any modifications to the automated system’s components unless 

explicitly authorized by the Firm.

- Instruct the system’s user on what residual risks may be encountered, on the 

control systems that have been applied and on how to open the system manually 

in an emergency. give the user guide to the end user.

- Dispose of packaging materials (plastic, cardboard, polystyrene, etc.) in accor-

dance with the provisions of the laws in force. Keep nylon bags and polystyrene 

out of reach of children.

WIRING

WARNING! 

For connection to the mains power supply, use: a multicore cable 

with a cross-sectional area of at least 5x1.5mm

2

 or 4x1.5mm

2

 when dealing 

with three-phase power supplies or 3x1.5mm

2

 for single-phase supplies (by 

way of example, type H05 VV-F cable can be used with a cross-sectional area 

of 4x1.5mm

2

). To connect auxiliary equipment, use wires with a cross-sectional 

area of at least 0.5 mm

2

.

-  Only use pushbuttons with a capacity of 10A-250V or more.

-  Wires must be secured with additional fastening near the terminals (for example, 

using cable clamps) in order to keep live parts well separated from safety extra 

low voltage parts.

-  During installation, the power cable must be stripped to allow the earth wire 

to be connected to the relevant terminal, while leaving the live wires as short 

as possible.  The earth wire must be the last to be pulled taut in the event the 

cable’s fastening device comes loose.

WARNING!

 safety extra low voltage wires must be kept physically separate from 

low voltage wires.

Only qualified personnel (professional installer) should be allowed to access 

live parts.

CHECKING THE AUTOMATED SYSTEM AND MAINTENANCE

Before the automated system is finally put into operation, and during maintenance 

work, perform the following checks meticulously:

- Make sure all components are fastened securely.

- Check starting and stopping operations in the case of manual control.

- Check the logic for normal or personalized operation.

- For sliding gates only: check that the rack and pinion mesh correctly with 2 mm 

of play; keep the track the gate slides on clean and free of debris at all times.

- Check that all safety devices (photocells, safety edges, etc.) are working properly 

and that the anti-crush safety device is set correctly, making sure that the force 

of impact measured at the points provided for by standard EN 12445 is lower 

than the value laid down by standard EN 12453.

- Make sure that the emergency operation works, where this feature is provi-

ded.

- Check opening and closing operations with the control devices applied.

- Check that electrical connections and cabling are intact, making extra sure that 

insulating sheaths and cable glands are undamaged.

- While performing maintenance, clean the photocells’ optics.

- When the automated system is out of service for any length of time, activate the 

emergency release (see “EMERGENCY OPERATION” section) so that the operated 

part is made idle, thus allowing the gate to be opened and closed manually.

SCRAPPING

Materials must be disposed of in accordance with the regulations in force. There 

are no particular hazards or risks involved in scrapping the automated system. For 

the purpose of recycling, it is best to separate dismantled parts into like materials 

(electrical parts - copper - aluminium - plastic - etc.).

DISMANTLING

If the automated system is being dismantled in order to be reassembled at another 

site, you are required to:

- Cut off the power and disconnect the whole electrical system.

- Remove the actuator from the base it is mounted on.

- Remove all the installation’s components.

- See to the replacement of any components that cannot be removed or happen 

to be damaged.

AVVERTENZE PER L’INSTALLATORE D811766_03

ARES  -  

19

D811692 00100_04

Содержание ARES

Страница 1: ... ANTRIEB FÜR ZAHNSTANGEN SCHIEBETORE SERVOMOTOR PARA CANCELAS CORREDERAS DE CREMALLERA ACTUATOR VOOR SCHUIFHEKKEN MET TANDHEUGEL Attenzione Leggere attentamente le Avvertenze all interno Caution Read Warnings inside carefully Attention Veuillez lire attentivement les Avertissements qui se trouvent à l intérieur Achtung Bitte lesen Sie aufmerksam die Hinweise im Inneren Atención Leer atentamente la...

Страница 2: ... accesorios transmisión Montage accessoires overbrenging Fissaggio staffe finecorsa dx e sx Fastening limit switch brackets RH LH Fixation étriers fin de course drt et gch Befestigung Bügel Anschläge rechts und links Fijación abrazaderas final de carrera der e izq Bevestiging stangen aanslag rechts en links Y Y Collegamento morsettiera Terminal board wiring Connexion plaque à bornes Anschluss Klem...

Страница 3: ... 12 14 SCA II CH 15 JP9 14 15 24 V VSAFE VSAFE 24V 0V 25W max LOGICA test fotocellule OFF Photocell test LOGIC OFF LOGIQUE essai photocellules Désactivée LOGIK Test Fotozellen OFF LÓGICA prueba fotocélulas OFF LOGICA test fotocellen OFF ne ngstasten Display programmeringstoetsen Display tasti programmazio Display programming keys Display Programmieru Pantalla botones programación 1 2 3 4 5 6 7 8 9...

Страница 4: ...ing opening 99 99 99 99 99 99 Speed during closing 99 99 99 99 99 99 Partial opening 40 40 40 40 40 40 Zone 0 0 0 0 0 0 Slow down distance 0 0 0 0 0 0 Opening deceleration space 10 10 10 10 10 10 Closing deceleration space 10 10 10 10 10 10 LOGIC Automatic Closing Time OFF ON OFF ON OFF OFF Block Pulses OFF OFF OFF ON ON OFF Impulse lock TCA OFF OFF OFF OFF OFF OFF 3 step OFF ON OFF ON OFF OFF Pre...

Страница 5: ...8888 K N M O P CFZ CP 37 30 12 28 22 22 CVZ 28 60 6 40 KO OK Q R P1 P2 S L O1 100 25 50 25 2mm 2 6 0 1 6 0 1 0 0 300 152 65 2 0 0 Z18 Ø p72 Z25 Ø p100 2 2 4 0 10 ARES D811692 00100_04 ...

Страница 6: ...20 21 22 23 24 25 26 27 JP2 JP1 31 32 33 34 COM NC BAR2 COM NC SWC NC SWO 24 V 0 V 0 V V Safe V Safe RX RX TX TX 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 JP2 JP1 31 32 33 34 COM NC SWC NC SWO FAULT PHOT FAULT BAR 2 FAULT BAR 1 COM NO 24 V V Safe V Safe RX RX TX TX ANT 24V 25W Max 24V 25W Max SCA 2 CH PED COM NO NO NC NO NC NC ST ART CLOSE STOP PHOT BAR1 OPEN U NO SCS...

Страница 7: ... 3 4 5 6 13 12 21 25 17 Bar 2 1 2 3 4 5 6 13 12 27 21 17 Bar 1 1 2 3 4 5 6 13 12 21 25 17 Bar 2 1 2 3 4 5 6 13 12 5 SCS1 MA 4 SCS1 MA 2 SCS1 MA 1 SCS1 MA 17 Bar 3 1 2 3 4 5 6 13 12 27 21 17 6 SCS1 MA Bar 1 1 2 3 4 5 6 13 12 21 25 17 Bar 2 1 2 3 4 5 6 13 12 17 Bar 4 1 2 3 4 5 6 13 12 27 21 17 Bar 3 1 2 3 4 5 6 13 12 5 SCS1 MA 3 SCS1 MA 6 SCS1 MA 4 SCS1 MA 17 26 27 25 24 23 22 21 20 19 18 COM FAULT ...

Страница 8: ...activated svo opening limit switch input activated svc closing limit switch input activated set the board is standing by to perform a com plete opening closing cycle uninterrupted by intermediate stops in order to acquire the tor que required for movement WARNING Obstacle detection function is not active Er01 photocell test error check photocell connection and or logic settings Er02 safety edge te...

Страница 9: ...s closed If the automated system is installed at a height of less than 2 5 m or is accessible the electrical and mechanical parts must be suitably protected Install any fixed controls in a position where they will not cause a hazard away from moving parts More specifically hold to run controls must be positioned withindirectsightofthepartbeingcontrolledand unlesstheyarekeyoperated must be installe...

Страница 10: ...omponents have been fastened at the predetermined points thenextstepistoconnectthemasdirectedandillustratedinthediagrams containedintherelevantinstructionmanuals Connectthelive neutralandearth wire compulsory The mains cable must be clamped in the relevant cable gland FIG R ref P1 and the accessories wires in the cable gland FIG R ref P2 while the earth wire with the yellow green coloured sheath m...

Страница 11: ...E Fig V the SCS MA auxiliary board must be used 15 4 Interface with WIEGAND systems via SCS WIE module Refer to the SCS WIE module s instructions 13 1 TABLE A PARAMETERS MENU PARA Parameter min max default personal Definition Description tca 0 120 40 Automatic Closing Time Automatic closing time s slov speed 15 50 15 Slow down speed Slow down speed Fig 2 Rif F Set the speed the gate must reach slo...

Страница 12: ... code mode radio prog ON Remote control programming ON Enables wireless memorizing of transmitters 1 Press in sequence the hidden key P1 and normal key T1 T2 T3 T4 of a transmitter that has already been memorized in standard mode via the radio menu 2 Press within 10 secs the hidden key P1 and normal key T1 T2 T3 T4 of a transmitter to be memorized IMPORTANT Enables the automatic addition of new tr...

Страница 13: ...della porta se in presenza di guasti meccanici o di condizioni di squilibrio Incasodiapritapparelle sorvegliarelatapparellainmovimentoetenerelontano le persone finché non è completamente chiusa Porre cura quando si aziona lo sbloccosepresente poichéunatapparellaapertapotrebbecadererapidamente in presenza di usura o rotture Larotturaol usuradiorganimeccanicidellaporta parteguidata qualiadesempio ca...

Страница 14: ... le levier de déverrouillage prévu à cet effet Ne pas entrer dans le rayon d action du portail de la porte motorisé e pendant son mouvement Ranger les radiocommandes ou les autres dispositifs de commande hors de portée des enfants afin d éviter tout actionnement involontaire L activation du déverrouillage manuel risque de provoquer des mouvements incontrôlés de la porte en présence de pannes mécan...

Страница 15: ...puede provocar situaciones de peligro Todo aquello que no expresamente previsto en el manual de uso no está permitido El buen funcionamiento del operador es garantizado sólo si se respetan las prescripciones indicadas en el presente manual La Empresa no se responsabiliza por los daños causados por el incumplimiento de las indicaciones dadas en el presente manual Dejandoinalteradaslascaracterística...

Страница 16: ......

Отзывы: