background image

INSTALLATION MANUAL

13.4)  LANGUAGE MENU (

language

)

Used to set the programmer’s language on the display. 

13.5) DEFAULT MENU (

default

)

Restores the controller’s DEFAULT factory settings. Following this reset, you will 

need to run the AUTOSET function again. 

 

13.6) AUTOSET MENU (

AUTOset

•  Launch an autoset operation by going to the relevant menu on the panel.

•  As soon as you press the OK button, the “.... .... ....” message is displayed and 

the control unit commands the door to perform a full cycle (opening followed 

by closing), during which the minimum torque value required for the door to 

move is set automatically.

 

The number of cycles required for the autoset function can range from 1 to 3.

  During this stage, it is important to avoid breaking the photocells’ beams and 

not to use the START and STOP commands or the display.

  Once this operation is complete, the control unit will have automatically set 

the optimum torque values. Check them and, where necessary, edit them as 

described in the programming section.

WARNING:  Check  that  the  force  of  impact  measured  at  the  points 

provided for by standard EN 12445 is lower than the value laid down 

by standard EN 12453.

Warning!! While the autoset function is running, the obstacle detection 

function is not active. Consequently, the installer must monitor the 

automated system’s movements and keep people and property out of range 

of the automated system.

14)CONNECTION WITH EXPANSION BOARDS AND UNIVERSAL HANDHELD 

PROGRAMMER (Fig.S)

Refer to specific manual.

15) SCS OPTIONAL MODULES

15.1) SERIAL CONNECTION VIA SCS1 CARD (Fig. U) 

The control panel’s special serial inputs and outputs (SCS1) make the centralized 

connection of a number of automated devices possible. That way, all the automated 

devices connected can be opened or closed with a single command.  

Connect all control panels using twisted pair cabling only, proceeding as shown 

in the diagram in Fig. U. 

When using a telephone cable with more than one pair, it is essential to use wires 

from the same pair.  

The length of the telephone cable between one unit and the next must not 

be greater than 250 m. 

At this point, each control panel needs to be configured appropriately, starting by 

entering a MASTER control panel that will have control over all the others, which 

therefore have to be set as SLAVE units (see logic menu). 

Also set the Zone number (see parameters menu) in the range 0 to 127. 

The zone number allows you to create groups of automated devices, each of which 

answers to the Zone Master. Each zone can have only one Master: the Master of 

zone 0 also controls the Slaves of the other zones. Warning: the control panel 

set as the MASTER must be the first in the series. 

15.2) Opposite sliding leaves (Fig. T) 

By means of a serial connection, it is also possible to obtain centralised control 

of two opposite barriers/gates.

In this case, the Master M1 control panel will simultaneously manage closing and 

opening for the Slave M2 control panel.

SETTING REQUIRED FOR OPERATION:

-  MASTER board: 

zone

=128, 

aster

=ON

-  SLAVE board: 

zone

=128, 

aster

=OFF

WIRING REQUIRED FOR OPERATION:

-  The MASTER and SLAVE control units are interconnected through the 4 wires 

(RX/TX) for the SCS1 interface boards;

-  All  the  activation  controls,  as  well  as  the  remote  controls  must  refer  to  the 

MASTER board;

-  All the photocells (checked or unchecked) must be connected to the MASTER 

control panel;

-  The safety edges (checked or unchecked) of the MASTER leaf must be connected 

to the MASTER control unit;

-  The safety edges (checked or unchecked) of the SLAVE leaf must be connected 

to the SLAVE control unit.

15.3)  EXPANDING  OUTPUTS  FOR  SAFETY  DEVICE TESTING VIA  SCS-MA 

BOARD (FIG. V)

When testing more than 2 devices (Ref. 4, 5, D, E Fig. V), the SCS-MA auxiliary 

board must be used.

15.4) Interface with WIEGAND systems via SCS-WIE module.

Refer to the SCS-WIE module’s instructions.

13.1) TABLE A: PARAMETERS MENU (

PARA

)

Parameter min. max. default personal

Definition

Description

tca

0

120

40

Automatic 

Closing Time

Automatic closing time [s]

slov
speed

15

50

15

Slow-down 

speed

Slow-down speed [%] (Fig.2 Rif. F)

Set the speed the gate must reach slowing down, in percentage to the actuator’s maximum speed.  

WARNING: 

should this parameter be edited, it will be followed by a complete opening/closing cycle 

for setting purposes (reported by the message “SET” appearing on the display), during which obstacle 

detection is not enabled.

op.t slov

1

99

75

Opening 

motor torque

Opening torque [%]

Sets sensitivity to obstacles during opening (1=max., 99=min.) The autoset feature sets this parameter 

automatically to a value of 10%. The user can edit this parameter based on how sensitive the door needs 

to be to obstacles.

cls.t
slov

1

99

75

Closing motor 

torque

Closing torque [%]

Sets sensitivity to obstacles during closing (1=max., 99=min.) The autoset feature sets this parameter 

automatically to a value of 10%. The user can edit this parameter based on how sensitive the door 

needs to be to obstacles.

op speed

15

99

99

Speed during 

opening

Running speed during opening [%] (Fig. 2 Rif. A)

Sets the running speed that the door must reach during opening, as a percentage of the maximum 

speed the actuator can reach. 

WARNING: 

should this parameter be edited, it will be followed by a 

complete opening/closing cycle for setting purposes (reported by the message “SET” appearing on 

the display), during which obstacle detection is not enabled.

cl speed

15

99

99

Speed during 

closing

Running speed during closing [%] (Fig. 2 Rif. B)

Sets the running speed that the door must reach during closing, as a percentage of the maximum spe-

ed the actuator can reach. The autoset feature sets this parameter automatically. 

WARNING: 

should 

this parameter be edited, it will be followed by a complete opening/closing cycle for setting purposes 

(reported by the buzzer emitting a continuous beeping sound and the message SET appearing on the 

display), during which obstacle detection is not enabled. 

partial
opening

10

99

40

Partial 

opening

Partial opening [%]

Adjusts partial opening percentage compared to total opening in “Partial open” mode.

zone

0

128

0

Zone

Zone []

Sets the zone number of the door included in the serial connection for commands via central control-

lers. Zone 128: Serial connection for opposite Sliding Leaves.

dist.
decel

(special par 

18*)

0

50

0

Slow-down 

distance

Slow-down distance [%] (Fig.2 Rif. C)

Set  the  distance  the  gate  needs  to  go  from  from  high  to  low  speed  in  percentage  to  total  travel. 

WARNING:

should this parameter be edited, it will be followed by a complete opening/closing cycle 

for setting purposes (reported by the message “SET” appearing on the display), during which obstacle 

detection is not enabled.

op.dist.
decel 

(special par 

19*)

5

50

10

Opening dece-

leration space

Opening deceleration space [%] (Fig.2 Rif. D)

Set the opening slow-down distance in percentage to total travel. This distance is covered at low spe-

ed. 

WARNING:

should this parameter be edited, it will be followed by a complete opening/closing 

cycle for setting purposes (reported by the message “SET” appearing on the display), during which 

obstacle detection is not enabled.

cl.dist.
decel 

(special par 

20*)

5

50

10

Closing dece-

leration space

Closing slow-down distance [%] (Fig.2 Rif. E)

Set the closing slow-down distance in percentage to total travel. This distance is covered at low speed.  

WARNING: 

should this parameter be edited, it will be followed by a complete opening/closing cycle 

for setting purposes (reported by the message “SET” appearing on the display), during which obstacle 

detection is not enabled.

*=Refer for universal handheld programmer.

22  -

  ARES

D811692 00100_01

Содержание ARES Series

Страница 1: ...ANTRIEB FÜR ZAHNSTANGEN SCHIEBETORE SERVOMOTOR PARA CANCELAS CORREDERAS DE CREMALLERA ACTUATOR VOOR SCHUIFHEKKEN MET TANDHEUGEL Attenzione Leggere attentamente le Avvertenze all interno Caution Read Warnings inside carefully Attention Veuillez lire attentivement les Avertissements qui se trouvent à l intérieur Achtung Bitte lesen Sie aufmerksam die Hinweise im Inneren Atención Leer atentamente las...

Страница 2: ...tage accessoires overbrenging Fissaggio staffe finecorsa dx e sx Fastening limit switch brackets RH LH Fixation étriers fin de course drt et gch Befestigung Bügel Anschläge rechts und links Fijación abrazaderas final de carrera der e izq Bevestiging stangen aanslag rechts en links Y Y Collegamento morsettiera Terminal board wiring Connexion plaque à bornes Anschluss Klemmleiste Conexión tablero de...

Страница 3: ...II CH 15 JP9 14 15 24 V VSAFE VSAFE 24V 0V 25W max LOGICA test fotocellule OFF Photocell test LOGIC OFF LOGIQUE essai photocellules Désactivée LOGIK Test Fotozellen OFF LÓGICA prueba fotocélulas OFF LOGICA test fotocellen OFF ne ngstasten Display programmeringstoetsen Display tasti programmazio Display programming keys Display Programmieru Pantalla botones programación 1 2 3 4 5 6 7 8 9 10 11 12 1...

Страница 4: ...ing opening 99 99 99 99 99 99 Speed during closing 99 99 99 99 99 99 Partial opening 40 40 40 40 40 40 Zone 0 0 0 0 0 0 Slow down distance 0 0 0 0 0 0 Opening deceleration space 10 10 10 10 10 10 Closing deceleration space 10 10 10 10 10 10 LOGIC Automatic Closing Time OFF ON OFF ON OFF OFF Block Pulses OFF OFF OFF ON ON OFF Impulse lock TCA OFF OFF OFF OFF OFF OFF 3 step OFF ON OFF ON OFF OFF Pre...

Страница 5: ...8888 K N M O P CFZ CP 37 30 12 28 22 22 CVZ 28 60 6 40 KO OK Q R P1 P2 S L O1 100 25 50 25 2mm 2 6 0 1 6 0 1 0 0 300 152 65 2 0 0 Z18 Ø p72 Z25 Ø p100 2 2 4 0 ARES 11 D811692 00100_01 ...

Страница 6: ...20 21 22 23 24 25 26 27 JP2 JP1 31 32 33 34 COM NC BAR2 COM NC SWC NC SWO 24 V 0 V 0 V V Safe V Safe RX RX TX TX 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 JP2 JP1 31 32 33 34 COM NC SWC NC SWO FAULT PHOT FAULT BAR 2 FAULT BAR 1 COM NO 24 V V Safe V Safe RX RX TX TX ANT 24V 25W Max 24V 25W Max SCA 2 CH PED COM NO NO NC NO NC NC ST ART CLOSE STOP PHOT BAR1 OPEN U NO SCS...

Страница 7: ... 3 4 5 6 13 12 21 25 17 Bar 2 1 2 3 4 5 6 13 12 27 21 17 Bar 1 1 2 3 4 5 6 13 12 21 25 17 Bar 2 1 2 3 4 5 6 13 12 5 SCS1 MA 4 SCS1 MA 2 SCS1 MA 1 SCS1 MA 17 Bar 3 1 2 3 4 5 6 13 12 27 21 17 6 SCS1 MA Bar 1 1 2 3 4 5 6 13 12 21 25 17 Bar 2 1 2 3 4 5 6 13 12 17 Bar 4 1 2 3 4 5 6 13 12 27 21 17 Bar 3 1 2 3 4 5 6 13 12 5 SCS1 MA 3 SCS1 MA 6 SCS1 MA 4 SCS1 MA 17 26 27 25 24 23 22 21 20 19 18 COM FAULT ...

Страница 8: ...put activated svo opening limit switch input activated svc closing limit switch input activated set the board is standing by to perform a com plete opening closing cycle uninterrupted by intermediate stops in order to acquire the tor que required for movement WARNING Obstacle detection function is not active Er01 photocell test error check photocell connection and or logic settings Er02 safety edg...

Страница 9: ...nnection to the mains power supply use a multicore cable with a cross section of at least 4x1 5mm2 of the kind provided for by the regulations mentioned above by way of example type H05VV F cable can be used with a cross section of 4x1 5mm2 To connect auxiliary equipment use wires with a cross section of at least 0 75 mm2 Have an omnipolar circuit breaker installed with a contact separation of at ...

Страница 10: ...ys and the auto mated device s various components have been fastened at the predetermined points thenextstepistoconnectthemasdirectedandillustratedinthediagrams containedintherelevantinstructionmanuals Connectthelive neutralandearth wire compulsory The mains cable must be clamped in the relevant cable gland FIG R ref P1 and the accessories wires in the cable gland FIG R ref P2 while the earth wire...

Страница 11: ...iliary board must be used 15 4 Interface with WIEGAND systems via SCS WIE module Refer to the SCS WIE module s instructions 13 1 TABLE A PARAMETERS MENU PARA Parameter min max default personal Definition Description tca 0 120 40 Automatic Closing Time Automatic closing time s slov speed 15 50 15 Slow down speed Slow down speed Fig 2 Rif F Set the speed the gate must reach slowing down in percentag...

Страница 12: ... code mode radio prog ON Remote control programming ON Enables wireless memorizing of transmitters 1 Press in sequence the hidden key P1 and normal key T1 T2 T3 T4 of a transmitter that has already been memorized in standard mode via the radio menu 2 Press within 10 secs the hidden key P1 and normal key T1 T2 T3 T4 of a transmitter to be memorized IMPORTANT Enables the automatic addition of new tr...

Страница 13: ...o supervisione o abbiano ricevuto istruzioni d uso da persone responsabili della loro sicurezza I bambini devono essere controllati affinché non giochino con l applicazione Nonlasciareradiocomandioaltridispositividicomandoallaportatadeibambini onde evitare azionamenti involontari L attivazionedellosbloccomanualepotrebbecausaremovimentiincontrollati della porta se in presenza di guasti meccanici o ...

Страница 14: ...l automatisation en particulier pendant son fonctionnement Cette application n est pas destinée à être utilisée par des personnes y compris les enfants ayant des capacités mentales physiques et sensorielles réduites ni par des personnes dépourvues des connaissances nécessaires à moins d agir sous la supervision de personnes responsables de leur sécurité ou d avoir reçues les instructions nécessair...

Отзывы: