Section 3.2 - MAINS INSTRUMENTS
T
o display this page push the
[HOME]
button and then, repeatedly push the
[ ↓ ]
button.
FREQ (HZ)
50.0
CCW (*)
MAINS
L1(V) L2(V) L3(V)
406 399 400
This page provides you basic information about power utility: frequency, voltage
and phase rotation. You can program limits for Over/Under voltage, frequency
and other. The Be126 will trigger an alarm and will record the event in the LOG
EVENT MEMORY. To browse other pages push the
[ ↓ ]
arrow. To return to the
‘System Status’ page push the
[ HOME ]
button.
Consult section 22.0 to see the MAINS adjustable parameters.
(*)
This message indicates the rotation of the phases: CCW or CW
Section 3.3 - BATTERY INSTRUMENTS
T
o display this page push the
[HOME]
button and then, repeatedly push the
[ ↓ ]
arrow button.
HOURS
18.5
F
SERVICE
S1(H) S2(H) S3(H)
82 182 282
BATTERY 1
BATTERY 2
N° OF START 1
N° OF START 2
13.8
14.0
42
40
This page provides voltage indication of battery voltage 1 & 2.
This page displays also the counter of the starts made by the circuit number 1
and number 2.
To browse other pages push the
[ ↓ ]
arrow. To return to the
‘System Status
Page
’ push the
[ HOME ]
button or repeatedly push the
[ ↑ ]
arrow.
Section 3.4 - MAINTENANCE INSTRUMENTS
T
o display this page push the
[HOME]
button and then, repeatedly push the
[ ↓ ]
button.
HOURS
18.5
F
SERVICE
S1(H) S2(H) S3(H)
82 182 282
This page provides information about running hours and maintenance timers.
When a timer reaches a zero count, the Be126 triggers the
[SERVICE 1]
(or
[SERVICE 2]
or
[SERVICE 3]
) alarm (see section 36.0.9). In this case you are
required to carry out the engine or system maintenance. After that, you can
cancel the alarm by pushing and holding the
[HOME]
push-button for about 5
seconds. As an option you can modify the settings of the timers (see section
15.0).
To browse other pages push the
[ ↓ ]
arrow. To return to the
‘System Status
Page
’ push the
[ HOME ]
button or repeatedly push the
[ ↑ ]
arrow.
Section 3.5 - MISCELLANEOUS INSTRUMENTS
T
o display this page push the
[HOME]
button and then, repeatedly push the
[ ↓ ]
button.
WATER (BAR)
FUEL %
CHARG.ALT.V.
AUX. °C
13.8
92.0
14.5
68
The
[WATER BAR]
indicates the water pressure supposing you have connected
and configured a pressure transmitter (see
[WATER PRESSURE]
in section 19.0).
The
[FUEL %]
is the measurement of fuel level (see
[TANK FUEL LEVEL]
in
section 16.0). The
[CHARG.ALT.V.]
is the measurement of the D+/W.L. terminal or
rotational speed transducer voltage.
The
[AUX. °C]
indicates the auxiliary temperature if you have connected a
temperature sensor to terminal JM-2 and configured an alarm (
[AUXILIARY °C]
section 20.0).
When using a standard engine, this is the last page of the instruments. In case of
CAN-BUS engine, push the
[ ↓ ]
arrow to open the CAN-BUS instrument pages.