Be126               NFPA20 Installation Manual    V4XX  - 03 Nov  -  2018                                               page 1 

 

 

    BE126 Diesel Fire Pump Controller  

  

The information in this document may be subject to change without notice. No part of this document may be copied or 
reproduced in any form or by any means without the prior written consent of Bernini Design Company. Bernini Design 
assumes no responsibility for any errors which may appear in this instruction manual or in the wiring diagrams. Although 
Bernini Design has taken all possible steps to ensure that the User Manual is completely, error free and up-to-date, we 
accept that errors may occur. Any future updates will be included in our official website www.bernini-design.com. If you 
encounter problems with this instruction manual, please contact us. 

 
 
 

Customer Support BERNINI DESIGN SRL ITALY 

 

e-mail:  

[email protected]

       mobile: ++40 721 241 361. Tel:++39 335 7077148. 

 
Warranty

 

  Bernini Design SRL (hereinafter BD) warrants that Be124 shall be free from defect in material or workmanship 
for a period of 3 years from the BD delivery date. BD shall, at its discretion, repair or replace the product without 
charge. BD shall return the Be124 to the buyer with the Default parameters at no extra charge. The buyer shall 
furnish sufficient information on any alleged defects in the product, so as to enable BD to determine there cause 
and existence. If the Be124 is not defective, or the product is defective for reason other than covered by this 
warranty, the buyer will be charged accordingly. This warranty shall not apply if the Be124 has not been used in 
accordance with the User Manual and other operating instructions, particularly if any defects are caused by 
misuse, improper repair attempts, negligence in use or incorrect handling. Then the purchase is non-refundable. 

 

This equipment complies with the EMC protection requirements

 

 

 

 

 

!!   WARNING   !! 

 

   High voltage is present inside the Be124. To avoid any electric-shock hazard, operating personnel must not remove the 

protective cover. Do not disconnect the grounding connection. The Be124 can start the engine at anytime. Do not work on 

equipment, which is controlled by the Be124. When servicing the engine, disconnect the battery and battery charger. We 

recommend that warning signs be placed on equipment indicating the above. 

 

!!   WARNING   !! 

 
 

 
 

 

 

!!! WARNING !!! MAINS VOLTAGE OR POWER UTILITY VOLTAGE MAY BE EXPOSED WITHIN THE  

BE124 AND ANCILLARY CIRCUITRY EVEN WHEN THE LED INDICATORS, PLACED ON THE FRONT 

PANEL, ARE TOTALLY TURNED OFF. 

 

 
 
 
 
 
 
 
 
 
 

Содержание BE126

Страница 1: ...the Be124 to the buyer with the Default parameters at no extra charge The buyer shall furnish sufficient information on any alleged defects in the product so as to enable BD to determine there cause...

Страница 2: ...0 Dimensions 42 0 Display 3 0 Display Languages 27 0 Display Settings 27 0 D Plus Monitoring 37 0 Dynamo Alternator monitoring 37 0 Engine Be126 Status Page 3 0 Engine Running 37 0 Engine Alarms Bypa...

Страница 3: ...serve Fuel 16 0 Service 1 2 3 15 0 Settings Parameters 33 0 Scheduler 8 0 Speed error 14 0 Speed settings 14 0 Speed indication 3 1 Sensors Fuel C Oil 40 3 3 Sensors test 31 0 Service Maintenance 15 0...

Страница 4: ...PTION Page 9 2 4 TEST MODE OF OPERATION DESCRIPTION Page 10 2 4 X UNI EN 12845 NFPA EPM MANUAL TEST FACILITIES Page 10 3 0 LED INDICATORS DISPLAYS DESCRIPTION Page 11 3 1 BE126 STATUS PAGE INSTRUMENTS...

Страница 5: ...R SETTINGS Page 23 20 0 AUXILIARY TEMPERATURE ALARMS SETTINGS Page 24 21 0 MISCELLANEOUS FUNCTIONS SETTINGS Page 25 22 0 MAINS PARAMETERS PROGRAMMING Page 26 23 0 RESTORING FACTORY SETTINGS Page 26 24...

Страница 6: ...ICATIONS Page 38 39 0 SOFTWARE UPGRADES REVISIONS Page 38 40 0 TERMINAL DESCRIPTION Page 39 41 0 TYPICAL WIRING DIAGRAM Page 43 42 0 REAR VIEW AND DIMENSIONS Page 44 WARNING The Be126 can start the en...

Страница 7: ...you connect MCB MOD BUS compatible battery chargers The Be126 monitors the power utility as well You can use the Be126 controller in standard diesel engine pump water station by enabling the Engine Pr...

Страница 8: ...EN applications the Be126 ignores the PREGLOW setting Push the button to open the engine instruments page In case the battery voltage drops below 6 volts the Be126 may reset the software The controlle...

Страница 9: ...t nominal speed When the engine is running use the display arrows to browse the instruments If you get lost during navigation push the HOME button the display will open the System Status Page Based on...

Страница 10: ...e sections 10 9 7 1 2 3 4 5 of the UNI EN 12845 Standard Note If after a minute time the pressure fails to drop down the Be126 will trigger the alarm TEST FAILURE WARNING see the section 21 0 2 to cha...

Страница 11: ...NUAL OFF F START DEMAND OFF WATER PRESSURE 12 1 NOT RUNNING SA 16 16 13 12 09 15 The mode of operation is indicated by a back lighted message in the example MANUAL The START DEMAND OFF means that ther...

Страница 12: ...HOME button and then repeatedly push the button HOURS 18 5 F SERVICE S1 H S2 H S3 H 82 182 282 This page provides information about running hours and maintenance timers When a timer reaches a zero cou...

Страница 13: ...PN106 XXX AIR FILTER BAR SPN107 XXX See above TURBO BAR SPN102 XXX EXHAUST C SPN173 XXX See above LOAD SPN92 XX ECU ENGINE HOURS XXXXXXX See above COOLANT SPN111 XXX COOLANT BAR SPN109 XXXX See above...

Страница 14: ...ENGINE TYPE ENGINE PARAMETERS ROTATIONAL SPEED MAINTENANCE TANK FUEL LEVEL OIL PRESSURE ENGINE TEMPERATURE 12 0 13 0 14 0 15 0 16 0 17 0 18 0 choose the suitable ECU that matches your engine program m...

Страница 15: ...ge in case of an alarm push the HOME button ALARM 1 10 LOW OIL PRESSURE SHUTDOWN 0 8 BAR Day HH MM SS DD MM YY ALARM 2 10 LOW OIL PRESSURE WARNING 2 8 BAR Day HH MM SS DD MM YY Use or to browse additi...

Страница 16: ...s the NODE 1 Battery Charger 2 features the NODE 2 Connect Battery Charger 1 to battery set 1 Battery Charger 2 to battery set 2 Default MODBUS node for BE126 is 3 The nodes 1 2 are reserved for the b...

Страница 17: ...sage CLEAR PASSWORD DONE d From now on you will no longer need a password to program the Be126 Note the password 0000 is not allowed If you have lost the password see section 35 0 for additional help...

Страница 18: ...to JM8 9 terminals Section 13 0 4 PREGLOW TIME OFF PREGLOW mode 1 These parameters are disabled in NFPA APPLICATIONS Section 13 0 5 STOP SOLENOID 2 sec BELT BREAK OFF 1s 5mins 3 30VDC STOP SOLENOID y...

Страница 19: ...AUTO mode after engine starting the engine can run at IDLE SPEED then after an IDLE TIME see 14 0 3 it will reach the nominal speed You can set an IDLE SPEED only supposing your engine has the CANbus...

Страница 20: ...cond bypass alarm delay You are required to connect a resistive sensor to the JM 5 input and to correctly configure the response curve see below IMPORTANT NOTE ABOUT FUEL LEVEL MEASUREMENT In order to...

Страница 21: ...e LOW BAR WARNING By keeping both alarms to OFF the display will not indicate the oil pressure measurement Section 17 0 2 POINT 1 BAR 0 0 BAR POINT 1 OHM 10 OHM POINT 2 BAR 2 0 BAR POINT 2 OHM 51 OHM...

Страница 22: ...PERATURE in addition to the TEMPERATURE sensor connected to JM 3 you are required to set up at least one TEMPERATURE alarm example LOW C WARNING By keeping all alarm with the option to OFF mode the di...

Страница 23: ...the high water pressure alarm When the water pressure drops below the LOW PRESSURE setting the Be126 turns on the low water pressure alarm The alarms are recorded in the Memory Events Register togethe...

Страница 24: ...lows you to select a 4 20mA transmitter or a 0 10V transmitter You can also set up the full scale of the transmitter see next Factory setting is 4 20mA IMPORTANT NOTE ABOUT AUXILIARY TEMPERATURE MEASU...

Страница 25: ...imeout for the drain output terminal JB 5 It works in TEST mode of operation or when the scheduler is active After activating the drain output if the Be126 does not detect a drop of pressure before ex...

Страница 26: ...e see above The range of the setting is in between 60 up to 600Vac The option OFF is provided to totally disable the Voltage alarm monitoring 22 0 3 UNDER HZ OFF OVER HZ OFF When the frequency falls b...

Страница 27: ...ion 24 0 CLEAR THE MEMORY select the CLEAR MEMORY sub menu see section 4 0 Display Instructions for restoring the factory settings Defaults CLEAR MEMORY YES NO HOLD LEFT 5SEC CLEAR MEMORY DONE A Push...

Страница 28: ...le for all applications English Italian Spanish French Section 28 0 PUSH BUTTONS TEST Push the OFF button to enter the OFF mode of operation Push the MENU button to open the Main Menu Use the or arrow...

Страница 29: ...Instructions OUTPUTS TEST KEY UP DOWN SELECTION KEY RIGHT OUTPUT ON JC1 OUT 1 WARNING THIS PROCEDURE MUST BE CARRIED OUT BY QUALIFIED ONLY PERSONNEL THE ENGINE MAY START OR YOU CAN INADVERTENTLY ACTI...

Страница 30: ...HIGH PRESSURE or a LOW PRESSURE alarm The Be126 System Status Page see 3 0 displays the water pressure measurement of the pressure transmitter connected to the terminal JM 1 The Be126 automatically up...

Страница 31: ...you change the days C Push the button to choose the slow mode In this way by using the or arrows you can browse the 288 samples one every five minutes of a chosen day Section 32 1 DOWNLOADING WATER PR...

Страница 32: ...modify the parameter as requested by you C Push the button to return You can push the button to choose an other parameter or push again the button to exit programming D Before quitting the Be126 asks...

Страница 33: ...ously monitors your actions If you forget to make a decision save or quit or you remain in a programming page for over one minute without taking decisions for at least one minute the BE126 automatical...

Страница 34: ...rnings and pre alarms will allow the engine to run In NPFA mode only over speed alarm is allowed to shutdown the engine 36 0 1 Clock Memory and System alarms CLOCK ERROR WARNING Real time clock failur...

Страница 35: ...XXXRPM Engine rotational under speed shutdown You can program the limit and a bypass alarm time for it In NFPA EN applications the alarm does not shut down the engine section 14 0 START 1 FAILURE WARN...

Страница 36: ...ode of operation You can monitor the ambient temperature or other critical part of the system See section 20 0 about the AUXILIARY C sub menu AUX C SENDER OPEN It indicates the failure of the temperat...

Страница 37: ...Be126 terminates the crank when the voltage measured on the D W L terminal rises above the CRANK VDC setting When the engine starts running the voltage of the D WL increases The point to terminate the...

Страница 38: ...Ph Ph Measurement precision 1 F S Impedance 2 M Ohm Resolution 1Vac Mains Frequency nominal frequency 20 0 Hz up to 70 0 Hz Precision 1 F S Accuracy 0 1Hz Digital Inputs open circuit voltage of approx...

Страница 39: ...NOMINAL SPEED REQUEST This output energizes when you are required to run the engine at nominal speed By default the IDLE speed is disabled The output is immediately energized when the Be126 activates...

Страница 40: ...tion of the START 1 pilot driver relay JC 7 RELAYS SUPPLY Positive Out This is the positive supply for the relays lamps connected to the outputs This supply is taken from the battery 1 2 via internal...

Страница 41: ...own the engine after a programmable time see FUEL parameters in the section 16 0 JF 6 MANUAL TEST SWITCH You are required to connect here the manual start button for testing the engine in accordance w...

Страница 42: ...justments and calibration Consult the section 19 0 to set up the pressure measurement JM 2 AUXILIARY TEMPERATURE This input monitors an auxiliary temperature transmitter See section AUXILIARY C submen...

Страница 43: ...JP 1 2 3 4 5 6 L1 L2 L3 N N R S T MAIN PICK UP AUX PICK UP B C 1 FAILURE B C 2 FAILURE TEMPERATURE WATER PRESSURE FUEL LEVEL TEST BUTTON WATER LEVEL EMERGENCY OIL PRESSURE ENGINE PROTECTION DIGITAL I...

Страница 44: ...ection 42 0 REAR VIEW AND DIMENSIONS 250 mm Recommended panel cut out 171mm X 239mm 169 mm Steel Cover Silicon Gasket 185 mm 22 mm 45 mm JB JM JA JF JI JG JN JH JC Supply 36Vdc max DB9 RS232 MODEM JL...

Отзывы: