
INTELLIBUS
Number : NR 1157
Revision : B
Page 17/19
Instructions for start-up
10
Local stop also
inhibited with a local
command inhibit
0: no, local stop is possible
1: yes, local stop and off inhibited
1
read / write
11
Dead band for
positioner function
Unit 0.1%
mini value: 2 (0.2%)
maxi value: 50 (5%)
1
read / write
12
Timing control
0: no timing control
1: timing control
1
read / write
13
Start of closing
temporised zone
0 to100 %
1
read / write
14
End of closing
temporised zone
0 to 100 % (lower than start value)
1
read / write
15
Start of opening
temporised zone
0 to100 %
1
read / write
16
End of opening
temporised zone
0 to 100 % (higher than start value)
1
read / write
17
Timer open time
expected
in seconds
2
read / write
18
Timer close time
expected
in seconds
2
read / write
19
Operating time without
timer
in seconds
2
read / write
20
no local stop in remote
mode
0= local stop possible
1= no local stop
1
read / write
21
Fail safe position in
case of loss of
communication
0= stayput
1= closing
2= opening
1
read / write
22
open priority
0= no priority
1= open priority
1
read / write
23
close priority
0= no priority
1= close priority
1
read / write
24
In case of emergency
command, torque limit
is 100%
0= no
1= yes
1
read / write
25
In case of emergency
command, thermal
overload is by- passed
0= no
1= yes
1
read / write
26
External gear ratio
(format: 1/ )
ex 200 = 1/200
2
read only
27
Actuator number
ASCII characters
16
read only
28
Manufacture date
ASCII characters
12
read only
29
Software version
ASCII characters ex:1.03
6
read only
30
Stroke measured
during set-up
For stroke unit see address 7
2
read only
31
Opening torque curve
Torque in %
Data 1 = closed position
Data 2= 1% open
Data 101= 100% open
101
read only