Bernard INTELLIBUS FF Скачать руководство пользователя страница 16

 

 

 

INTELLIBUS 

 

Number  : NR 1157 

 

Revision : B 

 

Page 16/19 

 

Instructions for start-up 

 

 

6  TRANSDUCER BLOCK 

 

Available data through FIELDBUS in the Transducer Block 
 
 
N°  

Data 

Value 

Number 
of bytes 

Type 

Operating class 

1: On - Off 
2: Modulating Classe III 
3 : Modulating Classe II 

read only 

Nut thread 
(If linear system) 

In mm (To calculate the stroke but 
only during set-up). Value is zero if 
no linear system. 

read only 

Locked motor timing 

In seconds  

read only 

Motor supply type 

0: 3 phase  
1: single phase or DC 

read only 

Reverse delay time 

(unit 50ms) 
Ex. 3 = 150ms 

read only 

Closing mode 

0: close on  position 
1: close on torque 
3: open and close on torque 

read only 

Stroke unit 

1: number of turns 
2: degrees 
3: mm 

read only 

Set-up for auxiliary 
command 1 
() Bit state for active 
command 
(see 4.1) 

0: not used 
1:local(0)/remote(1) 
2:local+remote(0) 
 

/remote(1) 

3:local command inhibit(1) 
4:open inhibit(1) 
5:close inhibit(1) 
6:On-off(0) / AUTO(1) 
7:fieldbus emergency closing (1) 
8: fieldbus emergency opening (1) 
9: fieldbus emergency stop (1) 
10: partial stroking (1) 

read / write 

Set-up for auxiliary 
command 2 
coming through the 
fieldbus but for 
emergency commands 
wired separately from 
the fieldbus.  

0: not used 
1:local(0)/remote(1) 
2:local+remote(0) 
 

/remote(1) 

3:local command inhibit(1) 
4:open inhibit(1) 
5:close inhibit(1) 
6:On-off(0) / AUTO(1) 
7:wired emergency closing (1) 
8: wired emergency opening (1) 
9: wired emergency stop (1) 
10: partial stroking (1) 

read / write 

Содержание INTELLIBUS FF

Страница 1: ...INTELLIBUS Number NR 1157 Revision B Page 1 19 INSTRUCTIONS FOR START UP Instructions for start up INTELLIBUS FF FOUNDATION FIELDBUS FOR INTELLI Intelli 2801...

Страница 2: ...supply 6 4 FUNDATIONAL FIELDBUS TECHNICAL OVERVIEW 6 4 1 Foundation Fieldbus communication 6 4 1 1 Link Active Scheduler 6 4 1 2 Function Block 7 4 1 3 Transducer Block 7 4 1 4 Device description 7 4...

Страница 3: ...ieldbus interface described in this document has been specially designed for the Bernard actuators with INTELLI control Control box with inside Foundation Fieldbus interface could be supplied to conne...

Страница 4: ...ieldbus module INTELLIBUS FF located in the actuator is plugged on to the main Intelli board and no access is needed Connection box INTELLI board Button for local control Display INTELLIBUS board FPX...

Страница 5: ...hielding End of line termination A termination has to be installed at each end of line This termination is not built in the actuator 3 4 Set up The INTELLIBUS module is selected in the menu Use the lo...

Страница 6: ...e The right position is then updated through the fieldbus communication 4 FUNDATIONAL FIELDBUS TECHNICAL OVERVIEW 4 1 Foundation Fieldbus communication 4 1 1 Link Active Scheduler The INTELLIBUS FF in...

Страница 7: ...g torque position curve see 5 4 1 4 Device description To achieve interoperability Device Description DD technology is used The DD is like a driver for a printer L Bernard supply the Device Descriptio...

Страница 8: ...tance x current Total fieldbus length 1 to 7 is less than 1900m Spurs length 3 6 is less than 120m The last actuator has a supply voltage of 24V 1 2 4 5 7 22V 9V that is enough to work 4 2 3 Terminato...

Страница 9: ...ree technologies is to keep the communication speed unaffected and therefore to get a very short response time L Bernard can supply weatherproof or explosion proof repeaters 5 CONTROLS AND INDICATIONS...

Страница 10: ...e open and close commands have to be maintained If this command is set to 1 a short duration open close command pulse is sufficient to drive the valve to the open or closed position In this case the s...

Страница 11: ...rational The test consists to operate the actuator on a partial stroke and return The start position and the stroke can be configured An alarm is emitted if the stroke is not performed in a predetermi...

Страница 12: ...1 0 No command 1 Auxiliary command 2 Bit 2 0 No command 1 Close command Bit 3 0 No command 1 Open command Bit 4 0 Relay 1 contact open 1 Relay 1 contact closed Bit 5 0 Relay 2 contact open 1 Relay 2...

Страница 13: ...allowed from Local controls SELECTOR TO OFF no command allowed in local or from Fieldbus Indications are always available SELECTOR TO LOCAL No command allowed from Fieldbus Indications are always ava...

Страница 14: ...ked motor open Bit 6 0 No locked motor close alarm 1 Locked motor close Bit 7 0 No overtravel alarm 1 Overtravel alarm TORQUE LIMITER ACTION OPEN CLOSE torque limiter action in opening closing directi...

Страница 15: ...n 5 is active ESD input by default The connection depends of actuator type Refer to the actuator wiring diagram ACTUATOR RUNNING the actuator is operated in opening or closing direction STOP MID TRAVE...

Страница 16: ...orque 3 open and close on torque 1 read only 7 Stroke unit 1 number of turns 2 degrees 3 mm 1 read only 8 Set up for auxiliary command 1 Bit state for active command see 4 1 0 not used 1 local 0 remot...

Страница 17: ...nds 2 read write 19 Operating time without timer in seconds 2 read write 20 no local stop in remote mode 0 local stop possible 1 no local stop 1 read write 21 Fail safe position in case of loss of com...

Страница 18: ...t 1 read only 43 locked motor close 0 no fault 1 fault 1 read only 44 torque sensor 0 no fault 1 fault 1 read only 44 position sensor 0 no fault 1 fault 1 read only 46 Closing direction of rotation di...

Страница 19: ...t into fieldbus devices as needed to achieve the desired device functionality For example a simple temperature transmitter may contain an AI function block The control valve actuator might contain a P...

Отзывы: