Instructions for start-up 

 

 

If  the  actuator  is  power  off,  then  the  Intellibus  interface  is  power  off  and  there  is  no 
communication  on  Fieldbus  (except  with  the  optional  extra  battery  or  the  emergency 
supply)  . 
ACTUATOR  RECEIVES  AN  EMERGENCY  COMMAND  ESD:  The  actuator  is  not 
available  because  it  receives  an  emergency  command  which  overrides  all  other 
commands 
VALVE JAMMED: Actuation could not be completed due to excess torque. 
 
Function Block DI(3) 

Bit n° 

Value 

Description 

Bit 0 

selector not to remote position 

 

Selector to remote position 

Bit 1 

selector not to OFF position 

 

Selector to OFF position 

Bit 2 

selector not to local position 

 

Selector to local position 

Bit 3 

no action 

 

Torque limiter action in open direction 

Bit 4 

no action 

 

Torque limiter action in close direction 

Bit 5 

No locked motor open alarm  

 

Locked motor open 

Bit 6 

No locked motor close alarm  

 

Locked motor close 

Bit 7 

No overtravel alarm  

 

Overtravel alarm 

 
TORQUE  LIMITER  ACTION  OPEN/CLOSE:  torque  limiter  action  in  opening/closing 
direction even if the valve stops normally on torque.  
LOCKED MOTOR OPEN/CLOSE: The motor locked in the opening/closing direction 
OVERTRAVEL ALARM: Position overshoot > 5% after motor shut down. 
 
Function Block DI(4) 

Bit n° 

Value 

Description 

Bit 0 

Actuator available 

 

Actuator fault indication 

Bit 1 

No motor thermal overload alarm  

 

Motor thermal overload 

Bit 2 

No indication 1 

 

indication 1 (*) is active (option) 

Bit 3 

No indication 2 

 

indication 2 (*) is active (option) 

Bit 4 

No indication 3 

 

indication 3 (*) is active (option) 

Bit 5 

No indication 4  

 

indication 4 (*) is active (option) 

Bit 6 

No battery fault  

 

Battery low or is not present 

Bit 7 

No handwheel action 

 

Handwheel action 

(*)The connection depends of actuator type. Refer to the actuator wiring diagram 

 
MOTOR THERMAL OVERLOAD: The motor thermal contact tripped. The actuator will be 
again available as soon as the motor will cool. 

Содержание INTELLIBUS FF

Страница 1: ...INTELLIBUS Number NR 1157 Revision B Page 1 19 INSTRUCTIONS FOR START UP Instructions for start up INTELLIBUS FF FOUNDATION FIELDBUS FOR INTELLI Intelli 2801...

Страница 2: ...supply 6 4 FUNDATIONAL FIELDBUS TECHNICAL OVERVIEW 6 4 1 Foundation Fieldbus communication 6 4 1 1 Link Active Scheduler 6 4 1 2 Function Block 7 4 1 3 Transducer Block 7 4 1 4 Device description 7 4...

Страница 3: ...ieldbus interface described in this document has been specially designed for the Bernard actuators with INTELLI control Control box with inside Foundation Fieldbus interface could be supplied to conne...

Страница 4: ...ieldbus module INTELLIBUS FF located in the actuator is plugged on to the main Intelli board and no access is needed Connection box INTELLI board Button for local control Display INTELLIBUS board FPX...

Страница 5: ...hielding End of line termination A termination has to be installed at each end of line This termination is not built in the actuator 3 4 Set up The INTELLIBUS module is selected in the menu Use the lo...

Страница 6: ...e The right position is then updated through the fieldbus communication 4 FUNDATIONAL FIELDBUS TECHNICAL OVERVIEW 4 1 Foundation Fieldbus communication 4 1 1 Link Active Scheduler The INTELLIBUS FF in...

Страница 7: ...g torque position curve see 5 4 1 4 Device description To achieve interoperability Device Description DD technology is used The DD is like a driver for a printer L Bernard supply the Device Descriptio...

Страница 8: ...tance x current Total fieldbus length 1 to 7 is less than 1900m Spurs length 3 6 is less than 120m The last actuator has a supply voltage of 24V 1 2 4 5 7 22V 9V that is enough to work 4 2 3 Terminato...

Страница 9: ...ree technologies is to keep the communication speed unaffected and therefore to get a very short response time L Bernard can supply weatherproof or explosion proof repeaters 5 CONTROLS AND INDICATIONS...

Страница 10: ...e open and close commands have to be maintained If this command is set to 1 a short duration open close command pulse is sufficient to drive the valve to the open or closed position In this case the s...

Страница 11: ...rational The test consists to operate the actuator on a partial stroke and return The start position and the stroke can be configured An alarm is emitted if the stroke is not performed in a predetermi...

Страница 12: ...1 0 No command 1 Auxiliary command 2 Bit 2 0 No command 1 Close command Bit 3 0 No command 1 Open command Bit 4 0 Relay 1 contact open 1 Relay 1 contact closed Bit 5 0 Relay 2 contact open 1 Relay 2...

Страница 13: ...allowed from Local controls SELECTOR TO OFF no command allowed in local or from Fieldbus Indications are always available SELECTOR TO LOCAL No command allowed from Fieldbus Indications are always ava...

Страница 14: ...ked motor open Bit 6 0 No locked motor close alarm 1 Locked motor close Bit 7 0 No overtravel alarm 1 Overtravel alarm TORQUE LIMITER ACTION OPEN CLOSE torque limiter action in opening closing directi...

Страница 15: ...n 5 is active ESD input by default The connection depends of actuator type Refer to the actuator wiring diagram ACTUATOR RUNNING the actuator is operated in opening or closing direction STOP MID TRAVE...

Страница 16: ...orque 3 open and close on torque 1 read only 7 Stroke unit 1 number of turns 2 degrees 3 mm 1 read only 8 Set up for auxiliary command 1 Bit state for active command see 4 1 0 not used 1 local 0 remot...

Страница 17: ...nds 2 read write 19 Operating time without timer in seconds 2 read write 20 no local stop in remote mode 0 local stop possible 1 no local stop 1 read write 21 Fail safe position in case of loss of com...

Страница 18: ...t 1 read only 43 locked motor close 0 no fault 1 fault 1 read only 44 torque sensor 0 no fault 1 fault 1 read only 44 position sensor 0 no fault 1 fault 1 read only 46 Closing direction of rotation di...

Страница 19: ...t into fieldbus devices as needed to achieve the desired device functionality For example a simple temperature transmitter may contain an AI function block The control valve actuator might contain a P...

Отзывы: