Bernard INTELLIBUS FF Скачать руководство пользователя страница 10

 

 

 

INTELLIBUS 

 

Number  : NR 1157 

 

Revision : B 

 

Page 10/19 

 

Instructions for start-up 

 

 

Function Block DO(1) 

Bit n° 

Value 

Description 

Bit 0 

No command 

 

Close command 

Bit 1 

No command 

 

Open command 

Bit 2 

Stop ( or maintained command mode) 

 

No stop (or Pulse command mode) 

Bit 3  

No command 

 

Auxiliary command 1  

Bit 4 

No command 

 

Auxiliary command 2 

Bit 5 

Relay 1 contact open 

 

Relay 1 contact closed 

Bit 6 

Relay 2 contact open 

 

Relay 2 contact closed 

Bit 7 

Relay 3 contact open 

 

Relay 3 contact closed 

 
OPEN / CLOSE: Open and close command. According to the actuator configuration, it is 
possible to select a priority to the opening or to the closing command (refer to NR1151) 
By default there is no priority given to either opening or closing. 
Priority can be used to: 
- Allow to reverse the actuator rotation direction during a manoeuvre without having to use 
the  stop  command.  In  this  case  it  is  necessary  to  set  a  priority  to  the  opening  or  to  the 
closing direction. 
- Give priority to one or the other rotation direction: if the actuator receives the open and 
close  commands  simultaneously  and  the  priority  has  been  given  to  the  opening,  the 
actuator will run the open position. 
STOP:  if  this  command  is  maintained  at  0  (most  common  case),  the  open  and  close 
commands  have  to  be  maintained.  If  this  command  is  set  to  1,  a  short  duration  open  / 
close command pulse is sufficient to drive the valve to the open or closed position. In this 
case,  the  stop  command  (0)  can  be  used  to  stop  the  actuator  during  the  travel  in  its 
current position. 
AUXILIARY COMMANDS 
By default, auxiliary command 1 is assigned to local control (actuator selector) inhibited. 
By  default,  auxiliary  command  2  is  not  assigned  to  a  Fieldbus  command  but  to  an 
emergency  command  (ESD):  This  command  is  hardwired  (separate  wiring)  and  directly 
connected to the control box main strip. 
These  commands  depend  of  actuator  configuration  (refer  to  NR1151)  and  can  be 
assigned to the following functions. 
LOCAL / REMOTE: substitutes for the local/remote selector of the actuator and is used to 
remotely enable either remote control or local control. 
LOCAL+REMOTE / REMOTE: same definition as above, but local and remote control can 
be enabled simultaneously. 
LOCAL  COMMAND  INHIBIT:  the  local  command  inhibit  is  remotely  controlled.  This 
command  inhibits  the  local  opening  and  closing  commands,  and  enables  remote 
commands, even if the local/remote selector of the actuator is set to local. 
OPEN,  CLOSE  INHIBIT:  this  command  is  used  to  inhibit  opening  or  closing  of  the 
actuator. 
AUTO/ON-OFF: for an actuator used in modulation with positioner function, it is possible 
to  issue  remote  commands  via  proportional  control  (equivalent  to  4-20mA)  or  via 

Содержание INTELLIBUS FF

Страница 1: ...INTELLIBUS Number NR 1157 Revision B Page 1 19 INSTRUCTIONS FOR START UP Instructions for start up INTELLIBUS FF FOUNDATION FIELDBUS FOR INTELLI Intelli 2801...

Страница 2: ...supply 6 4 FUNDATIONAL FIELDBUS TECHNICAL OVERVIEW 6 4 1 Foundation Fieldbus communication 6 4 1 1 Link Active Scheduler 6 4 1 2 Function Block 7 4 1 3 Transducer Block 7 4 1 4 Device description 7 4...

Страница 3: ...ieldbus interface described in this document has been specially designed for the Bernard actuators with INTELLI control Control box with inside Foundation Fieldbus interface could be supplied to conne...

Страница 4: ...ieldbus module INTELLIBUS FF located in the actuator is plugged on to the main Intelli board and no access is needed Connection box INTELLI board Button for local control Display INTELLIBUS board FPX...

Страница 5: ...hielding End of line termination A termination has to be installed at each end of line This termination is not built in the actuator 3 4 Set up The INTELLIBUS module is selected in the menu Use the lo...

Страница 6: ...e The right position is then updated through the fieldbus communication 4 FUNDATIONAL FIELDBUS TECHNICAL OVERVIEW 4 1 Foundation Fieldbus communication 4 1 1 Link Active Scheduler The INTELLIBUS FF in...

Страница 7: ...g torque position curve see 5 4 1 4 Device description To achieve interoperability Device Description DD technology is used The DD is like a driver for a printer L Bernard supply the Device Descriptio...

Страница 8: ...tance x current Total fieldbus length 1 to 7 is less than 1900m Spurs length 3 6 is less than 120m The last actuator has a supply voltage of 24V 1 2 4 5 7 22V 9V that is enough to work 4 2 3 Terminato...

Страница 9: ...ree technologies is to keep the communication speed unaffected and therefore to get a very short response time L Bernard can supply weatherproof or explosion proof repeaters 5 CONTROLS AND INDICATIONS...

Страница 10: ...e open and close commands have to be maintained If this command is set to 1 a short duration open close command pulse is sufficient to drive the valve to the open or closed position In this case the s...

Страница 11: ...rational The test consists to operate the actuator on a partial stroke and return The start position and the stroke can be configured An alarm is emitted if the stroke is not performed in a predetermi...

Страница 12: ...1 0 No command 1 Auxiliary command 2 Bit 2 0 No command 1 Close command Bit 3 0 No command 1 Open command Bit 4 0 Relay 1 contact open 1 Relay 1 contact closed Bit 5 0 Relay 2 contact open 1 Relay 2...

Страница 13: ...allowed from Local controls SELECTOR TO OFF no command allowed in local or from Fieldbus Indications are always available SELECTOR TO LOCAL No command allowed from Fieldbus Indications are always ava...

Страница 14: ...ked motor open Bit 6 0 No locked motor close alarm 1 Locked motor close Bit 7 0 No overtravel alarm 1 Overtravel alarm TORQUE LIMITER ACTION OPEN CLOSE torque limiter action in opening closing directi...

Страница 15: ...n 5 is active ESD input by default The connection depends of actuator type Refer to the actuator wiring diagram ACTUATOR RUNNING the actuator is operated in opening or closing direction STOP MID TRAVE...

Страница 16: ...orque 3 open and close on torque 1 read only 7 Stroke unit 1 number of turns 2 degrees 3 mm 1 read only 8 Set up for auxiliary command 1 Bit state for active command see 4 1 0 not used 1 local 0 remot...

Страница 17: ...nds 2 read write 19 Operating time without timer in seconds 2 read write 20 no local stop in remote mode 0 local stop possible 1 no local stop 1 read write 21 Fail safe position in case of loss of com...

Страница 18: ...t 1 read only 43 locked motor close 0 no fault 1 fault 1 read only 44 torque sensor 0 no fault 1 fault 1 read only 44 position sensor 0 no fault 1 fault 1 read only 46 Closing direction of rotation di...

Страница 19: ...t into fieldbus devices as needed to achieve the desired device functionality For example a simple temperature transmitter may contain an AI function block The control valve actuator might contain a P...

Отзывы: