INTELLIBUS 

 

Number  : NR 1157 

 

Revision : B 

 

Page 13/19 

 

Instructions for start-up 

 

 

Function Block DI(1) 

Bit n° 

Value 

Description 

Bit 0 

Valve not closed 

 

Valve closed 

Bit 1 

Valve not open 

 

Valve Open 

Bit 2 

The actuator is not running 

 

Actuator running 

Bit 3 

actuator not closing 

 

Actuator closing 

Bit 4 

actuator not opening 

 

Actuator opening 

Bit 5 

selector not to remote position 

 

Selector to remote position 

Bit 6 

selector not to OFF position 

 

Selector to OFF position 

Bit 7 

selector not to local position 

 

Selector to local position 

 
VALVE OPEN/CLOSE: confirms the valve is open or closed 
ACTUATOR RUNNING: the actuator is operated in opening or closing direction  
ACTUATOR OPENING/CLOSING: the actuator is operated in opening/closing direction 
SELECTOR TO REMOTE: No command allowed from Local controls.  
SELECTOR  TO  OFF:  no  command  allowed  in  local  or  from  Fieldbus.  Indications  are 
always available. 
SELECTOR  TO  LOCAL:  No  command  allowed  from  Fieldbus.  Indications  are  always 
available. 
 
Function Block DI(2) 

Bit n° 

Value 

Description 

Bit 0 

Valve not open 

 

Valve Open 

Bit 1 

Valve not closed 

 

Valve closed 

Bit 2 

actuator not closing 

 

Actuator closing 

Bit 3 

actuator not opening 

 

Actuator opening 

Bit 4 

selector not to remote position 

 

Selector to remote position 

Bit 5 

Actuator available 

 

Actuator fault indication 

Bit 6 

no ESD command  

 

Actuator receives an emergency command ESD 

Bit 7 

No valve jammed alarm 

 

Valve jammed  

 
ACTUATOR FAULT INDICATION: The actuator is not available due to a following event: 
Motor thermal overload, lost phase (in case of 3ph supply), locked rotor. 
Including additional faults(refer to NR1151 to configure): 
Selected option: selector in local, selector in off. 
Options: jammed valve, emergency command, command inhibit, overtravel. 

Содержание INTELLIBUS FF

Страница 1: ...INTELLIBUS Number NR 1157 Revision B Page 1 19 INSTRUCTIONS FOR START UP Instructions for start up INTELLIBUS FF FOUNDATION FIELDBUS FOR INTELLI Intelli 2801...

Страница 2: ...supply 6 4 FUNDATIONAL FIELDBUS TECHNICAL OVERVIEW 6 4 1 Foundation Fieldbus communication 6 4 1 1 Link Active Scheduler 6 4 1 2 Function Block 7 4 1 3 Transducer Block 7 4 1 4 Device description 7 4...

Страница 3: ...ieldbus interface described in this document has been specially designed for the Bernard actuators with INTELLI control Control box with inside Foundation Fieldbus interface could be supplied to conne...

Страница 4: ...ieldbus module INTELLIBUS FF located in the actuator is plugged on to the main Intelli board and no access is needed Connection box INTELLI board Button for local control Display INTELLIBUS board FPX...

Страница 5: ...hielding End of line termination A termination has to be installed at each end of line This termination is not built in the actuator 3 4 Set up The INTELLIBUS module is selected in the menu Use the lo...

Страница 6: ...e The right position is then updated through the fieldbus communication 4 FUNDATIONAL FIELDBUS TECHNICAL OVERVIEW 4 1 Foundation Fieldbus communication 4 1 1 Link Active Scheduler The INTELLIBUS FF in...

Страница 7: ...g torque position curve see 5 4 1 4 Device description To achieve interoperability Device Description DD technology is used The DD is like a driver for a printer L Bernard supply the Device Descriptio...

Страница 8: ...tance x current Total fieldbus length 1 to 7 is less than 1900m Spurs length 3 6 is less than 120m The last actuator has a supply voltage of 24V 1 2 4 5 7 22V 9V that is enough to work 4 2 3 Terminato...

Страница 9: ...ree technologies is to keep the communication speed unaffected and therefore to get a very short response time L Bernard can supply weatherproof or explosion proof repeaters 5 CONTROLS AND INDICATIONS...

Страница 10: ...e open and close commands have to be maintained If this command is set to 1 a short duration open close command pulse is sufficient to drive the valve to the open or closed position In this case the s...

Страница 11: ...rational The test consists to operate the actuator on a partial stroke and return The start position and the stroke can be configured An alarm is emitted if the stroke is not performed in a predetermi...

Страница 12: ...1 0 No command 1 Auxiliary command 2 Bit 2 0 No command 1 Close command Bit 3 0 No command 1 Open command Bit 4 0 Relay 1 contact open 1 Relay 1 contact closed Bit 5 0 Relay 2 contact open 1 Relay 2...

Страница 13: ...allowed from Local controls SELECTOR TO OFF no command allowed in local or from Fieldbus Indications are always available SELECTOR TO LOCAL No command allowed from Fieldbus Indications are always ava...

Страница 14: ...ked motor open Bit 6 0 No locked motor close alarm 1 Locked motor close Bit 7 0 No overtravel alarm 1 Overtravel alarm TORQUE LIMITER ACTION OPEN CLOSE torque limiter action in opening closing directi...

Страница 15: ...n 5 is active ESD input by default The connection depends of actuator type Refer to the actuator wiring diagram ACTUATOR RUNNING the actuator is operated in opening or closing direction STOP MID TRAVE...

Страница 16: ...orque 3 open and close on torque 1 read only 7 Stroke unit 1 number of turns 2 degrees 3 mm 1 read only 8 Set up for auxiliary command 1 Bit state for active command see 4 1 0 not used 1 local 0 remot...

Страница 17: ...nds 2 read write 19 Operating time without timer in seconds 2 read write 20 no local stop in remote mode 0 local stop possible 1 no local stop 1 read write 21 Fail safe position in case of loss of com...

Страница 18: ...t 1 read only 43 locked motor close 0 no fault 1 fault 1 read only 44 torque sensor 0 no fault 1 fault 1 read only 44 position sensor 0 no fault 1 fault 1 read only 46 Closing direction of rotation di...

Страница 19: ...t into fieldbus devices as needed to achieve the desired device functionality For example a simple temperature transmitter may contain an AI function block The control valve actuator might contain a P...

Отзывы: