3.
Navigate to
Save
and validate with
OK
on the left knob.
The confirmation screen appears.
4.
Select
YES
and validate with
OK
on the left knob.
The
Analog Input/Output
menu is then displayed.
The 0-10V signal can be obtained using
a 0-20mA combined with a 500-ohm
(or 499 ohm 1%) resistance.
The power supply needs to be 15 to
32V.
5.6.4
Setting the Analog Input/Ouput dead band
The dead band value represents the range over which the actuator
allows the input signal to deviate from the actual actuator position
without making any correction. This setting is made at the factory,
but it is possible to adjust it.
If the dead band is too narrow, the actuator could hunt, moving
back and forth in an attempt to reach the input signal value
without stopping within the dead band.
If the dead band is too wide, positioning operations are less
precise.
The default dead band is 1%.
How to set the dead band
1.
From the
Analog Input/Output
menu, enter
Deadband
.
The following screen appears.
2.
For each digit
•
Select the digit to adjust.
•
Adjust the digit with
or
on the right knob.
•
Validate with
OK
on the left knob.
12
13
14
15
0-10V
15-32V
+
−
+
−