4.5.2
Remote commands
The open and close commands are self-holding (pulse commands)
as a standard configuration.
To remove self-holding, remove wire to terminal
7
.
Dry contact control
Voltage control
S
- Stop
C
- Close
O -
Open
S
- Stop
C -
Close
O
- Open
A jumper must be fitted
across customer terminal
9-
10
.
Remote commands can be used
either in AC or DC voltage:
Use terminal
10
for voltage
from 10 to 60V
Use terminal
11
for voltage
from 90 to 250V
!
It is imperative to comply with
the voltage ranges mentioned
above, otherwise components
will not function or will be
damaged. For AUX1 & AUX2
auxiliary
commands,
these
commands can be assigned to
specific functions (see §5.5.1).