Setting the open and closed positions
The AT LOGIC features a position sensor. To set end positions, the
OPEN and CLOSED positions need to be set one after another,
depending on the first one set.
How to set CLOSED and OPEN position
1.
Enter the menu, then navigate to
Settings
>
Actuator
Commissioning
>
Set closed position
(depending on your
needs).
The following screen appears.
2.
Close the valve using the closing knob .
3.
When the valve is closed, validate
Save
with
OK
on the left
knob.
The following screen appears.
4.
Select
Confirm
with
OK
on the left knob.
The following screen appears.