Mounting and connecting the Glass sensor
Use the double installation socket (accessory). Mounting on single concealed sockets is not
possible.
Optional: For increased dismantling protection or to increase the shadow gap to the wall, use
the enclosed mounting frame (10). For this, lock the mounting frame onto the device from
behind. Observe marking
TOP
= TOP.
Bus voltage and an additional power supply are available at the installation location.
i
The yellow and white wire pair of the KNX bus line can be used to provide an additional
power supply.
o
If necessary, measure the surface compensation. With deeper installation sockets,
adjusting the retaining pegs (14) on the threaded pins (15) allows a surface compensation
of up to 20 mm. Unscrew the retaining pegs (14) by the surface compensation
x
, so that
they are at a distance of 15 mm + x from the socket for the threaded pins
i
When the mounting frame is used, the distance for the surface compensation is 20 mm + x
from the socket for the threaded pins.
Figure 13
(10) Mounting frame
(14) Retaining peg
(15) Threaded pin
(16) Friction spring
(17) Double installation socket (accessory)
o
Connect power supply to the terminal (5).
o
Connect the KNX bus voltage to the terminal (7).
o
Optional: Connect the external temperature sensor to the terminal (6).
i
Programming button and LED are accessible only from the back of the device. If possible,
load the physical address into the device before the final installation (see chapter 5.3.
Commissioning).
o
Insert the device with the threaded pins (15) into the friction springs (16) of the appliance
box (17) and push it in until the retaining pegs noticeably lock into place.
o
Align the device and push it in in the area of the retaining points to fix it.
Mounting the Glass sensor with increased dismantling protection
For increased dismantling protection, the mounting frame is firmly screwed to the appliance box
or the wall and the device secured using a retaining screw on the bottom of the mounting frame.
Seite 10/13
15.02.2013
32586901
97-09635-000
KNX
Touch/Glass sensor 2gang / 3gang with room thermostat