When a display has a technical fault, a numeric error code
appears that will enable the maintenance operator to iden-
tify the possible cause.
There are 3 categories of errors:
1 Permanent: errors that require a manual reset
2 Temporary: errors that are automatically reset once the
cause that generated them is removed or stopped
3 Notices: simple warnings that do not block the appli-
ance's operation
3 4 1 Permanent Errors
Nr Error
Description
0
E2PROM_READ_
ERROR
Internal software error
1
IGNIT_ERROR
Three unsuccessful ignition
attempts in a row
2
GV_RELAY_ER-
ROR
Failure detected in the GV
relay
3
SAFETY_RELAY_
ERROR
Failure detected in safety relay
4
BLOCKING_
TOO_LONG
Control had a blocking error
for more than 20 hours
5
FAN_ERROR_
NOT_RUNNING
Fan is not running for more
than 60 seconds
6
FAN_ERROR_
TOO_SLOW
Fan runs too slow for more
than 60 seconds
7
FAN_ERROR_
TOO_FAST
Fan runs too fast for more than
60 seconds
8
RAM_ERROR
Internal software error
9
WRONG_EE-
PROM_SIGNA-
TURE
Contents of Eeprom is not up
to date
10 E2PROM_ERROR Wrong safety parameters in
Eeprom
11 STATE_ERROR
Internal software error
12 ROM_ERROR
Internal software error
15 MAX_TEMP_ER-
ROR
The external overheat pro-
tection is enabled or the
T_Supply sensor measures
a temperature of over 100°C
(212°F)
16 FLUE_GAS_ER-
ROR
Flue temperature exceeded
the maximum flue temperature
17 STACK_ERROR
Internal software error
18 INSTRUCTION_
ERROR
Internal software error
19 ION_CHECK_
FAILED
Internal software error
20 FLAME_OUT_
TOO_LATE
Flame still present 10 seconds
after closing the gas valve
21 FLAME_BE-
FORE_IGNIT
Flame is detected before
ignition
23 CORRUPTED_
ERROR_NR
Error code RAM byte was
corrupted to an unknown error
code
29 PSM_ERROR
Internal software error
30 REGISTER_ER-
ROR
Internal software error
3 4 2 Temporary Errors
Nr Error
Description
100 WD_ERROR_RAM Internal software error
101 WD_ERROR_ROM Internal software error
102 WD_ERROR_
STACK
Internal software error
103 WD_ERROR_REG-
ISTER
Internal software error
106 REFHI_TOO_HIGH
/ REFHI_TOO_LOW Internal software error
107 REFHI_TOO_HIGH
/ REFHI_TOO_LOW Internal software error
108 REFHI_TOO_HIGH
/ REFHI_TOO_LOW Internal software error
109 REFHI_TOO_HIGH
/ REFHI_TOO_LOW Internal software error
110 REFHI_TOO_HIGH
/ REFHI_TOO_LOW Internal software error
111 REFHI_TOO_HIGH
/ REFHI_TOO_LOW Internal software error
112 REFHI_TOO_HIGH
/ REFHI_TOO_LOW Internal software error
113 REFHI_TOO_HIGH
/ REFHI_TOO_LOW Internal software error
114 FALSE_FLAME
Flame is detected in a state in
which no flame is allowed to
be seen.
115
LOW_WATER_
PRESSURE_ER-
ROR
Low water pressure error
118 WD_COMM_ER-
ROR
Watchdog communication
error
119 RETURN_OPEN
Return sensor open
120 SUPPLY_OPEN
Supply sensor open
122 DHW_OPEN
DHW sensor open
123 FLUE_OPEN
Flue sensor open
126 RETURN_SHORT-
ED
Return sensor shorted
127 SUPPLY_SHORT-
ED
Supply sensor shorted
129 DHW_SHORTED
DHW sensor shorted
130 FLUE_SHORTED
Flue sensor shorted
133 RESET_BUTTON_
ERROR
Too many resets in a short time
period
163 T_SELECTION1_
OPEN
Heat exchanger's flow rate too
low
3 4 3 Warnings
Nr Error
Description
200 CC_LOSS_COM-
MUNICATION
Cascade system: the burner of
the managing module has lost
the signal of one of the depend-
ing thermal module burner
201 CC_LOSS_COM-
MUNICATION
Cascade system: the managing
module has lost the signal of
one of the depending thermal
module
202 OUTDOOR_
WRONG
Outdoor sensor is open of
shorted
203 T_SYSTEM_
WRONG
T_System sensor is open of
shorted
204 T_CASCADE_
WRONG
T_Cascade sensor is open of
shorted