35
MENU
INSTALLER
/ MANUFAC-
TURER
Par
No Description
Range
De-
fault
set-
ting
UM
2000
2001 It defines the several functioning modes of the heat thermal
module.
0…5
0
2005
Defines the time in seconds of post-circulation of the thermal
module when working in stand-alone mode; when working in
cascade mode, it defines the post-circulation of the module
after switching off for thermoregulation.
0…900
60
Sec.
2007 Sets the value in degrees beyond the set-point at which the
burner switches off for thermoregulation.
0…20
5
°C
2009
Sets the stand-by time before the appliance is switched on
again after it switches off due to thermoregulation, inde-
pendently from the delivery temperature dropping below the
value indicated in Par. 2010. Parameter valid only in stand-
alone mode.
10…900
120
Sec.
2010 Sets the value in degrees below which the burner switches
on again notwithstanding from the time spent at Par. 2009.
0…20
16
°C
2014 Sets the heating's % max. power.
50…100
100
%
2015 Sets the heating's % min. power.
1…30
1
%
2019 Defines the max. set-point at the minimum outdoor tempera-
ture for climatic regulation.
30…90
80
°C
2020 Defines the minimum outdoor temperature to which the max-
imum set-point can be associated for climatic regulation.
-25…25
0
°C
2021 Defines the minimum set-point at the maximum outdoor
temperature for climatic regulation.
30…90
40
°C
2022
Defines the maximum minimum outdoor temperature to
which the minimum set-point can be associated for climatic
regulation.
0…30
20
°C
2023 Limits the minimum value that can be assigned to the set-
point in heating mode (does not apply to heating mode 4).
4…82
30
°C
2024 Limits the maximum value that can be assigned to the set-
point in heating mode (does not apply to heating mode 4).
27…90
80
°C
2025 Defines the temperature of exclusion of climatic regulation.
Active for heating mode Par. 2001 = 1 or 2
0…35
22
°C
2026
Establishes the set-point temperature increase delta T, if the
heat demand in heating mode is not satisfied after the time
interval specified in Par. 2027 (applies only to stand-alone
mode).
0…30
0
°C
2027
Defines the time interval after which the set-point is in-
creased as defined in Par. 2026 (applies only to stand-alone
mode).
1…120
20
Min.
2028 Use the heating mode Par. 2001= 2 or 3. Defines how many
degrees the flow set point is lowered.
0…30
10
°C
2035 Establishes the domestic hot water circuit's operation mode.
0 Disabled 1 Tank
+ sensor 2 Tank +
thermostat
0
2036 Defines the hysteresis to initiate the domestic hot water
demand.
0…20
5
°C
2037 Defines the hysteresis to stop the domestic hot water de-
mand.
0…20
5
°C
2038
Defines the primary circuit's set-point increase in degrees
compared to the temperature set for the domestic hot water
tank.
0…30
15
°C
2042
Defines the priority type:
On: priority for DHW; Off: priority for CH;
Time: time priority between the two circuits defined by Par.
2043;
Parallel: parallel priority managed on the basis of the primary
circuit's temperature compared to the heating circuit's set-
point.
On Off Time Parallel
On
2043
Establishes the time in minutes during which priority is alter-
natively allocated to the DHW and CH circuits when Par.
2043 is set to "time" mode.
1…255
30
Min.
2044
Defines the time in seconds of post-circulation of the thermal
module when working in stand-alone mode; when working in
cascade mode, it defines the post-circulation of the module
after switching off for thermoregulation.
0…900
60
Sec.