13
Mynute Boiler Green B.S.I. E
-
Anti-frost device:
when the temperature of the water in the
boiler falls below 5°C, the circulator and, if necessary, the
burner are activated at minimum output levels to bring the water
temperature back to the values for safety (35°C). During the anti-
frost cycle, the symb
ol app
ears on the digital monitor.
-
Circulator anti-blocking function:
an operation cycle is
activated every 24 hours.
Long period switching off
In case of absence for long periods of time, set the mode selector
(
3
- fig. 1a) to (OFF) (fig. 2a).
Then, close the gas tap present on the system. In this case, anti-
frost device is deactivated: empty the systems, in case of risk of
frost.
4A CONTROLS
At the beginning of the heating season, and occasionally during
use, make sure the hydrometer-thermohydrometer indicates cold
system pressure values between 0.6 and 1.5 bar: this avoids
system noise levels due to the presence of air. In case of insufficient
water circulation, the boiler will switch off. Under no circumstances,
water pressure must be below 0.5 bar (red field).
If this condition is checked, it is necessary to restore water pressure
in the boiler proceeding as follows:
- set the mode selector (
3
- fig.1a) to (OFF)
- turn on the filling tap (
I
- fig. 14) until the pressure value is
between 1 and 1.5 bar.
Carefully close the tap. Replace the mode selector on the initial
position. If pressure drop is frequent, contact the Technical
Assistance Service.
5A LIGHT SIGNALS AND FAULTS
The operating status of the boiler is shown on the digital display,
below is a list of the types of displays.
To restore operation (deactivate alarms):
Faults A 01-02-03
Position the function selector to (OFF), wait 5-6 seconds then
set it to the required position
(summer mode) or
(winter
mode). If the reset attempts do not reactivate the boiler, contact the
Technical Assistance Centre.
Fault A 04
In addition to the fault code, the digital display shows the symbol
.
Check the pressure value indicated by the water gauge:
if it is less than 0.3 bar, position the function selector to (OFF)
and adjust the filling tap (
I
- fig. 14) until the pressure reaches a
value between 1 and 1.5 bar.
Then position the mode selector to the desired position
(summer) or
(winter).
If pressure drops are frequent, request the intervention of the
Technical Assistance Service.
Fault A 06
The boiler operates normally but cannot reliably maintain a
constant domestic hot water temperature, which remains set at
around 50°C. Contact the Technical Assistance Centre.
Fault A 07
Contact the Technical Assistance Centre.
Fault A 08
Contact the Technical Assistance Centre.
Fault A 09
Position the function selector to (OFF), wait 5-6 seconds then
set it to the required position
(summer mode) or
(winter
mode). If the reset attempts do not reactivate the boiler, request the
intervention of the Technical Assistance Service.
Fault A 09
The boiler is equipped with an auto-diagnostic system which,
based on the total number of hours in certain operating conditions,
can signal the need to clean the primary exchanger (alarm code 09
and flue gas meter >2,500).
Once the cleaning operation has been completed, using the special
kit supplied as an accessory, the total hour meter will need to be
reset to zero as follows:
- switch off the power supply
- remove the shell
- turning the instrument panel towards you
- unscrew the two screws of the small cover on the electronic
board to have access to the terminals
- while the boiler is powered up, using a small screwdriver included,
press the CO button (fig. 9a) for at least 4 seconds, to check the
meter has been reset, power down then power up the boiler; the
meter reading is shown on the monitor after the “-C-” sign.
Live electrical parts (230 Vac).
Note: the meter resetting procedure should be carried out after
each indepth cleaning of the primary exchanger or if this latter is
replaced. To check the status of the total hour meter, multiply the
reading by 100 (e.g. reading of 18 = 1,800 total hours; reading of 1
= 100 total hours).
The boiler continues to operate normally even when the alarm is
activated.
BOILER STATUS
DISPLAY
Stand-by
-
OFF status
OFF
ACF module lockout alarm
A01
ACF electrical fault alarm
A01
Limit thermostat alarm
A02
Air pressure switch alarm
A03
H
2
O pressure switch alarm
A04
NTC domestic water fault
A06
Primary (flow) thermistor fault - Primary (flow) thermi-
stor over temperature - Temperature differential
A07
Return thermistor fault - Return thermistor overtem-
perature - Temperature differential inverted
A08
Flue thermistor or flue thermistor counter fault -
Flue thermistor over temperature
A09
False flame
A11
Low temperature thermostat fault
A77
Calibration
ADJ
Service operation
ACO
Transient awaiting ignition
88
°C
flashing
H
2
O pressure switch intervention
flashing
Purge cycle mode active
External probe present
Domestic water heat request
60
°C
Heating heat request
80
°C
Anti-freeze heat request
Flame present