Condensing boiler

Gas type

Gas

category

17 - SERIAL NUMBER PLATE

DHW operation
CH operation

Qn

nominal capacity

Pn

nominal power

IP

protection level

P. min

minimum pressure

Pmw

DHW maximum pressure

Pms

CH maximum pressure

T

temperature

η

ηη

ηη

working efficiency

D

specific capacity

NOx

NOx value class

18 - ADJUSTMENTS

The boiler has already been factory adjusted by the manufacturer. If a new
adjustment is required, for example, after extraordinary maintenance, replacing
the gas valve or converting from natural gas to LPG, proceed as follows.

Maximum and minimum power, minimum and maximum heating,
must be adjusted in the indicated sequence by qualified staff.

- Unscrew the lower cover fixing screw (C, Fig. 1.4)
- Pull the cover towards you and remove (A-B) (Fig. 1.5)
- Loosen the two fixing screws (D) and remove the shell (Fig. 1.2)
- Lift up the panel and turn it forwards
- Loosen the pressure tap screw downline from the gas valve by about two

turns and connect the pressure gauge to it

CALIBRATION & SERVICE operations must be performed with the boiler
in the OFF position. To do this, press the   button until the display shows
“- -” (Fig. E).
During parameter modification operations, the “select functions” button
acts as an ENTER (confirm) button, the   button acts as an ESCAPE
button. If no confirmation is given within 10 seconds, the value is discarded
and returns to the previously set one.

Setting the password

Press and hold down the operating mode button and the   button together for
about 10 seconds. The display will look like Fig. F.
Enter the password for accessing the parameter modifications function by turning
the domestic hot water temperature selector to the required value.
The password is located on the back side of the control panel. Confirm by
pressing ENTER.

Calibration phases

Turn the domestic hot water selector to sequentially scroll the CALIBRATION
& SERVICE phases:
1

gas type

2

boiler power (do not modify this parameter)

10 domestic hot water mode (do not modify this parameter)
3

insulation level of building (only if external sensor is connected)

45 inclination of thermoregulation curve (OTC), only if external sensor is

connected)

47 inclination of thermoregulation curve 2CH (OTC), only if external sensor is

connected)

HP maximum fan speed (do not modify this parameter)
LP minimum fan speed (do not modify this parameter)
SP ignition speed (do not modify this parameter)
HH boiler at maximum power
LL boiler at minimum power
MM fan ignition speed (do not modify this parameter)
23 maximum heating adjustment possibility
24 minimum heating adjustment possibility.

The parameters 2 - 10 - HP - SP - LP - MM - 23 - 24 must be modified,
by professionally qualified personnel, only if absolutely necessary.
The manufacturer refuses any responsibility in the case of incorrect
setting of the parameters.

20

20

30

40

50

60

70

80

90

100

15

10

5

0

-5

-10

-15

-20

P.22

2,5

5

7,5

10

P.21

15

17,5

20

22,5

25

27,5

30

32,5

35

37,5

40

12,5

GRAPH 1

Thermoregulation curves

EXTERNAL TEMPERATURE (°C)

P21 = MAXIMUM HEATING SET POINT
P22 = MINIMUM HEATING SET POINT

DELIVER

Y

 TEMPERA

TURE (°C)

10

20

30

40

50

60

70

80

90

-20

-15

-10

-5

0

5

10

15

20

GRAPH 3

Parallel night reduction

DELIVER

Y

 TEMPERA

TURE (°C)

EXTERNAL TEMPERATURE (°C)

DAY

 temperature curve

NIGHT

temperature curve

0˚C

+5˚C

-5˚C

10

20

30

40

50

60

70

80

90

-20

-15

-10

-5

0

5

10

15

20

25

30

GRAPH 2

Temperature curve correction

DELIVER

Y

 TEMPERA

TURE (°C)

EXTERNAL TEMPERATURE (°C)

Содержание EXCLUSIVE GREEN CSI 16

Страница 1: ...C S I R S I EN INSTALLER AND USER MANUAL ES MANUAL DE INSTALACI N Y USO PT MANUAL PARA INSTALA O E USO HU TELEP T I S FELHASZN L I K ZIK NYV RO MANUAL DE INSTALARE SI UTILIZARE DK INSTALLATIONS OG BR...

Страница 2: ...E jelet RO Centrala EXCLUSIVE GREEN este fabricata in conformitate cu cerintele urmatoarelor Directive Directiva gaz 90 396 EEC Directiva eficienta 92 42 EEC Directiva compatibilitate electromagnetica...

Страница 3: ...s o aqueles referidos quer ao usu rio quer ao instalador Os modelos GREEN C S I e GREEN R S I t m os pain is de comando diferentes veja se o desenho Sugerimos consultar o manual para as instru es rel...

Страница 4: ...m switch before cleaning it is forbidden to modify the safety or adjustment devices without the manufacturer s permission and relative instructions do not pull detach or twist the wires from the boile...

Страница 5: ...and remove the shell Fig 1 2 lift up the panel and turn it forwards open the terminal board covers making them slide in the direction of the arrows Fig 1 8 E high voltage connections 230 V F low volt...

Страница 6: ...leaving the gas cock closed 4 Use the room thermostat or the remote control panel to activate request for heat so that the three way will turn to heating 5 Turn on a tap to activate request for hot w...

Страница 7: ...r s mm m m mm mm m mm m m mm m m class p p m p p m C p p m p p m C 25 21500 24 43 21006 26 13 22468 6 5160 5 86 5041 6 44 5537 25 21500 25 21500 6 5160 6 5160 97 7 97 7 101 2 97 9 104 5 107 3 107 1 13...

Страница 8: ...s diaphragm Burner length CH maximum gas capacity CH minimum gas capacity Numbers of fan revolutions at slow start Maximum number of fan revolutions Minimum number of fan revolutions EXCLUSIVE GREEN R...

Страница 9: ...the winter comfort mode If it was in the OFF mode the display will show two segments in the central area Fig 3 Press the button to enable operation press the function selector until the indicator mov...

Страница 10: ...10 EXCLUSIVE GREEN C S I R S I Open position 1 2 3 4 A 4 5 C 3 C 2 C 1 C 0 C 1 C 2 C 3 C 4 5 C 5 6 7 B 8 9 10 Tap closed 11 12 13...

Страница 11: ...Fig 8 The boiler will remain working until the set temperatures are reached after which it will go on stand by In the event of ignition or operating faults the boiler will perform a safety stop The f...

Страница 12: ...n reference to the second circuit only if it is connected S A R A function Fig 21 If the winter mode is selected the S A R A AutomaticAmbientAdjustment System function can be activated Turn the heatin...

Страница 13: ...er only if water tank connected Info button shows a sequence of information concerning the operating status of the machine Switching on Switch on the boiler as follows access the gas tap through the s...

Страница 14: ...14 EXCLUSIVE GREEN C S I R S I Open position 1 2 3 4 5 6 A 4 5 C 3 C 2 C 1 C 0 C 1 C 2 C 3 C 4 5 C 7 9 D 11 10 8...

Страница 15: ...heating water tank with sensor to adjust domestic hot water temperature storaged in the water tank turn switch D Fig 9 clocwise to increase and anticlockwise to decrease The bar segments light up ever...

Страница 16: ...the word InFO Fig 17 Info 1 only with the external probe connected displays external temperature e g 12 C Fig 18 The values shown on the display range between 30 C and 35 C Beyond these values the dis...

Страница 17: ...ls and appear either together or separately For a description of the faults consult the following table D Permanent T Temporary In this operating status the boiler attempts to eliminate the fault on i...

Страница 18: ...select functions button and the button together for about 10 seconds The display will look like Fig F Enter the password for accessing the parameter modifications function by turning the domestic hot...

Страница 19: ...FREEZE FUNCTION TEMPERATURE ON HEATING ANTIFREEZE FUNC DELIVERY TEMP ON THIS PARAMETER IS NOT USED ON THIS MODEL DO NOT MODIFY EXTERNAL SENSOR REACTIVITY SEMI AUTOMATIC FILLING AUTOMATIC FILLING PRESS...

Страница 20: ...delivery temperature but affect the calculation made to automatically determine its value by modifying the reference tempera ture of the system 0 20 C For boilers fitted with the S A R A BOOSTER funct...

Страница 21: ...n by turning the domestic hot water temperature selector to the required value The password is located on the back side of the control panel Confirm by pressing ENTER Calibration phases Turn the domes...

Страница 22: ...ave set by pressing ENTER MAXIMUM POWER ADJUSTMENT P HH Fig 1 17 Turn the boiler OFF Select the parameter HH and wait for the boiler to come on Check that the maximum CO2 reading on the analyser see p...

Страница 23: ...obes in the designated positions on the air chamber after having removed screw B and cap C Fig 1 20 make sure in the HH and LL parameters that the CO2 values correspond with those indicated in the tab...

Страница 24: ...120 EXCLUSIVE GREEN C S I R S I...

Страница 25: ...21 Br nder 22 Hoved veksler 23 Bl ser 24 Mixer 25 Gas dyse 26 Ekspansionsbeholder 27 Manometer 28 Ikke DK 29 Ikke DK 30 Gas armatur 31 Kondensafl b EN BOILER OPERATING ELEMENTS 1 Filling tap C S I 2...

Страница 26: ...tr s vias I Bomba circuladora J V lvula de sangria ar inferior K Tanque de expans o L Sonda NTC retorno M Permutador circuito prim rio N V lvula de sangria ar superior O Sonda NTC sa da P Transdutor d...

Страница 27: ...e de expans o P Sonda NTC retorno Q Permutador circuito prim rio R V lvula de sangria ar superior S Sonda NTC sa da T Transdutor de press o U Hidr metro V Boiler pode se fornecer a pedido HU V ZKERING...

Страница 28: ...4 EXCLUSIVE GREEN C S I R S I EXCLUSIVE GREEN C S I EN MULTI WIRE DIAGRAM ES ESQUEMA EL CTRICO MULTIHILO PT DIAGRAMA EL CTRICO MULTIFILAR HU KAPCSOL SI RAJZ RO SCHEMA ELECTRICA MULTIFILARA DK EL DIAGR...

Страница 29: ...5 EXCLUSIVE GREEN C S I R S I EXCLUSIVE GREEN R S I EN MULTI WIRE DIAGRAM ES ESQUEMA EL CTRICO MULTIHILO PT DIAGRAMA EL CTRICO MULTIFILAR HU KAPCSOL SI RAJZ RO SCHEMA ELECTRICA MULTIFILARA DK EL DIAGR...

Страница 30: ...1 Transformador principal TRX Transformador para ventilador TSC2 Transformador de encendido V Ventilador PT DIAGRAMA EL CTRICO MULTIFILAR SUGERE SE A POLARIZA O L N Blu Azul Marrone Castanha Nero Pret...

Страница 31: ...circuit apa calda menajera NTC C S I T BOLL Termostat rezervor apa R S I T F Termostat de fum T L A Termostat limita pentru supra temperatura apei T P Traductor de presiune TR1 Transformator principal...

Страница 32: ...28 EXCLUSIVE GREEN C S I R S I a b c f GREEN C S I GREEN C S I GREEN R S I GREEN C S I GREEN R S I GREEN C S I GREEN R S I GREEN R S I d e g GREEN C S I GREEN R S I 2 1 1 2 1 3 4 5 6 4 5 1 7 10 P2 8 9...

Страница 33: ...l circulador suplementario en la regleta de 2 polos en la zona dimensionada para V 230 Voltios La caldera es capaz de gestionar un circulador suplementario conectado hidr ulicamente como se muestra en...

Страница 34: ...u functiile de voltaj redus la bornele corespunzatoare cu 10 poli de la nivelul tabloului de conexiune M10 dupa cum este indicat Montati P O S DHW ceas de control conform figurii dupa de ati indeparta...

Страница 35: ...e que a caldeira funciona correctamente se no permutador do aquecimento houver uma circula o de gua suficiente Para esta finalidade a caldeira dotada de um by pass autom tico que prov quaisquer que se...

Страница 36: ...en RO dimensiuni in mm DK m lt i mm A EN A condensate outlet C water gas ES A descarga condensado C agua gas PT A descarga condensado C gua g s HU A kondenzv z elvezet s C v z g z RO A scurgere apa de...

Страница 37: ...133 EXCLUSIVE GREEN C S I R S I C S I E F E F G R S I 1 8 G B F C A D A D F G E 1 9 C S I R S I 1 6 1 7 A...

Страница 38: ...IRA O AR HU KONCENTRIKUS F STG ZELVEZET S LEVEG BESZ V S RO TUBULATURA CONCENTRICA ADMISIE EVACUARE DK BALANCERET AFTR K AFKAST LUFTINDTAG EN SPLIT DUCTS FOR FUMES OUTLET AIR INTAKE ES CONDUCTO DESDOB...

Страница 39: ...0 180 190 200 B 25 C S I R S I A 0 10 20 30 40 50 60 70 0 10 20 30 40 50 60 70 80 90 100 35 C S I R S I B A 0 10 20 30 40 50 60 70 80 90 0 10 20 30 40 50 60 70 80 90 100 110 120 130 1 16 1 17 A B EN A...

Страница 40: ...Via Risorgimento 13 23900 Lecco LC ITALY Cod 20001690 06 08 Ed 1...

Отзывы: