Programmable parameters
*
Power not available at the moment
**
The value is expressed on the display in revs/min/100 (example 3.600 = 36)
N°
DESCRIPTION PARAMETERS
UNIT OF
MIN
MAX
DEFAULT
PARAMETERS
PAR.
MEASURE
(setted in
(setted by techn.
factory)
assist. centre)
1
GAS TYPE
1 Methane
1
2 LPG
3 Methane France
2
BOILER POWER
10*-16-20*-26-30-34-50*-70*
30
3
INSULATION LEVEL OF BUILDING
min
5
20
5
10
DHW MODE
0 (OFF)
5
1 (Instantaneous)
2 (Mini-tank)
3 (External water-tank with thermostat)
4 (External water-tank with sensor)
5 (Integrated water tank)
11
THIS PARAMETER IS NOT USED ON THIS MODEL. DO NOT MODIFY
60
12
WATER TANK MAXIMUM SET-POINT
° C
40
80
60
13
DELIVERY TERMPERATURE EXT. WATER TANK
° C
50
85
80
14
DELTA EXTERNAL WATER TANK (ON)
° C
0
10
5
20
HEATING MODE
0 (OFF)
1
1 (ON)
2 (not used)
3 (CONNECT AP)
4 (not used)
5 (not used)
6 (CONNECT AT/BT)
21
HEATING CIRCUIT MAXIMUM SET-POINT
° C
40
80
80
22
MINIMUM HEATING SET POINT
° C
20
39
20
23
MAXIMUM HEATING VENTILATOR SPEED
revs/min
36 (3.600**)
MAX
24
MINIMUM HEATING VENTILATOR SPEED
revs/min
36 (3.600**)
MIN
25
DIFFERENTIAL HEATING POSITIVE
° C
2
10
6
26
DIFFERENTIAL HEATING NEGATIVE
° C
2
10
6
28
MAX HEATING POWER REDUCTION TIMER
min
0
20
15
29
FORCED HEATING SHUT DOWN TIMER
min
0
20
5
30
HEATING TIMER RESET FUNCTION
-
0 (NO)
1 (YES)
0
31
MAXIMUM HEATING SET POINT 2CH (II circuit)
° C
40
80
80
32
MINIMUM HEATING SET POINT 2CH (II circuit)
° C
20
39
20
40
THIS PARAMETER IS NOT USED ON THIS MODEL. DO NOT MODIFY
1
41
THIS PARAMETER IS NOT USED ON THIS MODEL. DO NOT MODIFY
1
42
S.A.R.A. FUNCTION
0 (OFF)
1
1 (AUTO)
43
THIS PARAMETER IS NOT USED ON THIS MODEL. DO NOT MODIFY
1
44
THERMOREGULATION FUNCTION
0 (OFF)
1
1 (AUTO)
45
INCLINATION THERMOREGULATION CURVE (OTC)
-
2,5
40
20
46
THERMOREGULATION FUNCTION 2CH
0 (OFF)
1
1 (AUTO)
47
INCLINATION THERMOREGULATION CURVE (OTC) 2CH
-
2,5
40
20
48
THIS PARAMETER IS NOT USED ON THIS MODEL. DO NOT MODIFY
0
50
THIS PARAMETER IS NOT USED ON THIS MODEL. DO NOT MODIFY
1
51
HEAT REQUEST TYPE CH1 (I circuit)
-
0
1
0
52
HEAT REQUEST TYPE CH2 (II circuit)
-
0
1
0
61
THIS PARAMETER IS NOT USED ON THIS MODEL. DO NOT MODIFY
4
62
HEATING ANTIFREEZE FUNC. DELIVERY TEMP. (ON)
°C
0
10
6
63
WATER TANK ANTIFREEZE FUNC. DELIV. TEMP. (ON)
°C
0
10
6
65
EXTERNAL SENSOR REACTIVITY
0 (very fast)
255 (very slow)
255
85
SEMI-AUTOMATIC FILLING
0 (disabled)
1
1 (enabled)
86
AUTOMATIC FILLING PRESSURE (ON)
bar
0.4
1.0
0.6
92
ENABLE POST-CIRCULATION FROM DHW TO HEATING
0
1
0
93
DURATION OF POST-CIRCULATION FROM DHW TO HEATING
1
255
5
94
PUMP IN CONTINUAL MODE CH1 (CIRCUIT 1)
0
1
0
95
PUMP IN CONTINUAL MODE CH2 (CIRCUIT 2)
0
1
0
G20
G31
30kW
56
56
G20
G31
30kW
14
14