- Through the REC10 it is possible to access, using the TECHNICAL
menu, a series of parameters that can be programmed to allow you to
personalise the operation of the boiler based on the type of system.
- Then set the parameters according to the desired operating modes.
5.2.1 Boiler configuration
- Access the technical parameters as explained in the section
- Select PARAMETERS with the
“up”
and
“down”
keys, confirming the
selection.
-
TERMOREGOLAZIONE
PARAMETERS
INSTALLATION
THERMOREGULATION
RANGE RATED
TECHNICAL
INSTALLER
CALIBRATION
PARAMETERS
WEATHER COMPENSATION
INSTALLATION
RANGE RATED
CALIBRATION
TECHNICAL
INSTALLER
Select from among the following options with the
“up”
and
“down”
,
keys, confirming the selection.
PARAMETERS
INSTALLER
TIMER OFF CH
RESET TIMERS CH
DHW THERMOSTAT
ANTI-CYCLE FUNCTION
RESET CH TIMERS
DHW THERMOSTAT
PARAMETERS
INSTALLER
-
TIMER OFF CH
This parameter allows you to change the TIMER OFF CH, regarding
the delay time introduced for re-igniting the burner in the face of an off
due to the heating temperature being reached. The factory setting for
this parameter is 3 minutes and can be set to a value between 0 min
and 20 min selecting the desired one with the
“up”
and
“down”
, keys
confirming the selection.
-
TIMER OFF CH
3
MIN
ANTI-CYCLE FUNCTION
RESET TIMERS CH
This parameter allows you to reset the REDUCED HEATING MAXIMUM
OUTPUT TIMING, during which the speed of the fan is limited to 75%
of the maximum heating output that has been set, and the TIMER OFF
CH. The factory setting for this parameter is FUNCTION NON ACTIVE,
select FUNCTION ACTIVE using the keys
“up”
and
“down”
, confirming
the selection for resetting the timings.
FUNCTION NOT ACTIVE
RESET TIMERS CH
FUNCTION ACTIVE
INSTALLER
FUNCTION NOT ACTIVE
FUNCTION ACTIVE
RESET CH TIMERS
INSTALLER
-
SLIDING OUTLET (only if storage tank connected)
This parameter allows activating the SLIDING OUTLET function to modify
the outlet setpoint used by the boiler when receiving a DHW request. The
factory setting for this parameter is FUNCTION NON ACTIVE; this setting
performs a modulation to a fixed outlet value of 80°C in case of DHW
request. Select FUNCTION ACTIVE using the keys
“up”
and
“down”
,
confirming the selection. In this case, the outlet setpoint in DHW request
is no longer fixed at 80°C but variable, and it is calculated automatically
by the boiler based on the difference between the desired DHW setpoint
and the temperature value detected by the storage tank probe.
Note:
we do not recommend activating this function for storage tanks with
a capacity of over 100 litres since the storage tank filling would be too
slow.
Attention:
it may be necessary to set the value of this parameter again
after replacing the setting board.
FUNCTION NOT ACTIVE
SLIDING OUTLET
FUNCTION ACTIVE
INSTALLER
FUNCTION ACTIVE
FUNCTION NOT ACTIVE
SLIDING OUTLET
INSTALLER