24
EXCLUSIVE
- select STOP FUNCTION with the
“up”
and
“down”
keys, confirming
the selection
VENT CYCLE
STOP FUNCTION
INSTALLER
DISABLE FUNCTION
ENABLE FUNCTION
STOP FUNCTION
ENABLE FUNCTION
DISABLE FUNCTION
AIR PURGING CYCLE
INSTALLER
The REC10 will briefly display a wait message after which you will
automatically be taken to the main screen.
18/05/2013
12:17
INFO
SET
30
°C
.3
MENU
FRI
STATE
PLANT
HOT WATER TEMPERATURE
1.3 bar
MENU
STATE
SET
INFO
PLANT
HOT WATER TEMPERATURE
FRI
SUMMER
(only if a storage tank is connected):
selecting SUMMER
operating mode in the STATE menu and then BOILER, the traditional
function of just domestic hot water will be activated. The REC10 normally
displays the temperature of the domestic hot water stocked in the storage
tank (only in case of storage tank with probe).
In case of storage tank with thermostat or domestic hot water request in
progress, the delivery boiler temperature is displayed.
BOILER
OFF
SUMMER
WINTER
OFF
HOT WATER ONLY
HEATING AND HOT WATER
BOILER
WINTER
/ :
selecting WINTER in the STATE menu and then
BOILER, the heating and domestic hot water functions are activated.
REC10 normally displays the domestic hot water temperature unless
there is a heating request in progress, in which case the delivery boiler
temperature is displayed.
BOILER
OFF
SUMMER
WINTER
OFF
HOT WATER ONLY
HEATING AND HOT WATER
BOILER
5.4 Adjusting the heating water temperature without
an outdoor temperature sensor connected
When there is no outdoor temperature sensor, the boiler operates at a
fixed-point, the HEATING setpoint in this case can be set selecting SET
on the main screen of the REC10 and choosing the desired value within
the range [40°C - 80.5°C] for high temperature systems rather than [20°C
- 45°C] for low temperature systems.
HOT WATER
SET
HEATING
SET
HEATING
DHW
5.5 Adjusting the heating water temperature with an
outdoor temperature sensor connected
When an outdoor temperature sensor is installed, the outlet temperature
is automatically selected by the system, which quickly adjusts the ambient
temperature according to the variations in the outdoor temperature. If you
want to change the temperature, raising it or lowering it with respect to that
automatically calculated by the electronic board, it is possible to change the
HEATING setpoint by selecting SET on the main screen of the REC10 and
selecting within the range (-5 - +5) the desired comfort level (see section
“5.2.5 Setting the thermoregulation”).
Note:
when there is an outdoor temperature sensor connected it is still
possible to have the boiler operate at a fixed point setting the values of MIN
SP HEAT and MAX SP HEAT at the desired HEATING setpoint.
5.6 Adjustment of the domestic hot water
temperature
CASE A:
only heating with no external storage tank connected - adjustment
not applicable.
CASE B:
only heating with an external storage tank managed by a
thermostat - adjustment not applicable.
CASE C:
only heating with an external storage tank managed by a
probe - to adjust the domestic hot water temperature stocked
in the storage tank. Set the DOMESTIC HOT WATER setpoint
selecting SET on the main screen of the REC10 and choosing
the desired value within the range [37.5°C - 60°C].
SET
HEATING
HOT WATER
SET
HEATING
DHW
5.7 Adding devices
- Access the technical parameters as explained in the section
- Select ADD STORAGE TANK with the
“up”
and
“down”
keys,
confirming the selection
EXHAUST PROBE RESET
ADD STORAGE TANK
TECHNICAL
INSTALLER
CALIBRATION
RANGE RATED
SWEEPER
CALIBRATION
RANGE RATED
COMBUSTION ANALYSIS
EXHAUST PROBE RESET
ADD HW TANK
TECHNICAL
INSTALLER
Complete the storage tank configuration referring to the specific paragraph.
b
After adding the storage tank, in the “PROGRAMM” screen “DHW”
appears. This function allows you to make the sanitary programming