9
KICK PUMP FUNCTION
System 2, 9:
No function
System 1, 3, 4, 5, 6, 7, 8, 10, 11, 12, 13:
The kick pump function can be activated dur-
ing periods of the day in which solar heating
is required [P05-P06].
This function ensures that the sensor meas-
ures effective collector temperature even if the
collector pump is off at the time.
The function is disabled when no switching
times have been set (P05=P06=OFF) or the
kick duration is zero (P60=OFF). After each
pause set for the kick function [P61], the cor-
responding collector pump is activated for the
kick time set [P60] (ensuring heat is carried to
the probe). If during the monitoring time [P62]
the collector probe measures a temperature
increase of 0.5°C, the collector pump is oper-
ated for one minute.
The switching conditions for the collector
pump are then monitored.
05 Kick pump function ON time
The temperature monitoring function starts at
this time.
06 Kick pump function OFF time
The temperature monitoring function ends at
this time.
AUXILIARY HEATING FUNCTION
Selectable on most systems as an additional
function (see the paragraph on special func-
tions):
When activating the post-heating function, a
temperature can be set [P47] for the selected
storage cylinder.
During the time the function is enabled [P07-
P08], this temperature is maintained constant
by activating an additional heater.
Supplementary heating is switched on if the
temperature measured by sensor F3 is below
P47- P34 (post-heating control hysteresis)
and P52 (solar supplement tolerance).
It is switched off if the temperature measured
by sensor F3 exceeds nominal temperature
P47 (for solar supplement P47-P52).
07 Supplementary heating function ON
The set temperature [P47] is enabled starting
from this time.
08 Supplementary heating function OFF
The set temperature [P47] is enabled until
this time.
CIRCULATING PUMP
Selectable on most systems as an additional
function (see the paragraph on special func-
tions):
P54=1: During the enabling times P09-P10
the circulating pump is always on.
P54=2: During the enabling times.
P09-P10 the circulating pump is on based on
impulses.
P54=3: Circulating pump for Anti-Legionella
function.
09 Circulating pump ON time
The circulating pump is enabled starting from
this time.
10 Circulating pump OFF time
The circulating pump is enabled until this
time.
11 Anti-legionella function activation time
Anti-legionella function activation time.