17
P108 0% speed voltage
Only available if P101 = 0…10V
P108 = 0.0 – 10 V: The minimum pump speed
setting.
P109 100% speed voltage
Only available if P101 = 0…10V
P109 = 0.0 – 10 V: The maximum pump speed
setting.
P110 OFF voltage
Only available if P101 = 0…10V
P110 = 0.0 – 10 V: The voltage at which the
pump and its control relay are switched off.
OTHER FUNCTIONS
Anti-block function
This function effectively prevents the pumps
from blocking due to excessive inactivity. The
integrated anti-block function means that all
pumps that have not operated over the last
24 hours are started for 5 seconds each day,
between 12.00 and 12.01.
Stop pumps (temperature monitoring)
The filling of the second storage cylinder (2)
(measured by probe F3) is stopped for 60
sec. every 30 min.
After this time, the conditions to start filling
the main storage cylinder (probe F4) are
checked. This function is only performed if
the main storage cylinder has not reached the
maximum temperature [F4 < ([P50]-5°C)].