Chapter 3
Configuration
Page 16
The Load shed current has two timers the first one of which to expire will activate the Load shed
relay output.
The timers begin counting at different current levels and continue to count as long as current stays
above the set point. If it any point the current drops below the measuring point the timer will reset.
The first t1 begins counting as current rises above 120% of Max current. t2 begins counting when
current rises above100% of Max current.
The counter times are set to default vlaues. These can be changed by the following method.
Step 1.
From the ‘AC Current Calibration’ select ‘t1 120% and/or t2 100%’.
Step 2.
Use the soft keyboard to enter new timer value.
Step 3.
When both the timers have been set you are able to ‘Enable Load Shed’ at the ‘Load shed’
function.
Alarms
All inputs have the ability to have a high or low warning alarm. Depending on what type of meter
configuration you are running, some of these alarms will be enabled by default.
Answering Alarms
Label
Alarm
Window
Alarm
Icon
When an alarm is active you will see an Alarm Window for each active alarm and the
buzzer/external alarm will sound. The Alarm Window will tell you which input is alarming and what
type of alarm it is i.e. Low On or Low Voltage. The label for all alarming circuits will be red also.
To remove the Alarm Window from the Status Page you have 2 options:
Disable the alarm
You will get no further alarms from this input until it is re-enabled.
Snooze the alarm