Chapter 3
Configuration
Page 14
Gauge Min
This is the minimum scale for Gauge View
Gauge Max
This is the maximum scale for Gauge View
AC Current
Label
AC Current Value
Loadshed Status
Current Calibration
Current Calibration is factory set. If you need to alter the calibration follow the steps below:
Go to Main Menu > Setup > Input(s) > ‘
Choose Current Input’
> Calibration
Step 1
Select ‘Zero’. Ensure there is zero current then select ‘Yes’ to confirm.
Step 2
Turn on a steady load on the line you are calibrating i.e. lights. The maximum load possible will
give the best results. Please wait for at least 10 seconds for the ‘Raw’ value to settle, then check
current draw with a calibrated Ammeter at the CT.