background image

43

 

Bentone 

Cause of fault

Action

Burner control faulty

Replace

Air pressure gauge incorrectly set or faulty

Check the settings and reset, or replace

No acknowledgement signal due to incorrect adjustment or 
misalignment of the control motor cams.

Check the settings and realign.

Burner trips after safety time limit despite flame propagation

No ionisation current or UV cell incorrectly positioned

Adjust ionisation electrode and UV cell 
Check cables and connectors

Burner control monitor faulty

Replace burner control

Voltage lower than 185 V

Contact an electrician

Ignition electrodes disrupting ionisation current

Adjust ignition electrodes. Re-polarise the 
transformer

Poor earth connection

Ensure adequate earth connection

Phase and neutral swapped around

Check wiring diagram and change 
accordingly

Burner trips during pre-aeration.

Air sensor faulty or incorrectly set

Increase/decrease air setting. Reduce air 
volume

Ignition load incorrectly set

Increase/decrease gas supply Reduce 
airflow

Gas pressure too low

Increase pressure. If necessary, contact gas 
supplier

Pulsations at start-up

Ignition electrodes incorrectly set

Adjust 

Gas pressure too high

Check and adjust using pressure gauge and 
pressure control valve

Flue gas side blocked

Check the chimney flue

Burner pulsates during operation

Burner incorrectly set

Adjust

Burner dirty

Clean the burner

Incorrect chimney

Check and modify dimensions if necessary

Burner functioning properly but with occasional blockage

Ionisation current too low

Check. Must be at least 6 µA, but should 
ideally lie between 8 and 20 µA

UV cell incorrectly positioned

Adjust

Voltage drop at certain times

Must not drop below 15% of rated voltage. 
Contact an electrician if necessary

Incorrectly set or faulty air sensor

Check the settings and reset, or replace

Ignition electrode overload

Replace

Burner control ambient temperature too high

Insulate for heat, Max. 60 °

Ignition spark too weak

Check the transformer

Poor combustion

Poor draught conditions

Check the chimney

Содержание BG 650

Страница 1: ...Providing sustainable energy solutions worldwide 178 088 82 1 2018 03 28 Installation and maintenance instruction BG 650 M...

Страница 2: ...2 Bentone...

Страница 3: ...per __________________________________________ 20 4 12 Damper motor air volume ____________________________________ 20 4 13 Adjustment of gas flow_______________________________________ 20 5 Setting t...

Страница 4: ...dry environment max 80 relative humidity no condensation Temperature 20 to 60 C Check that the burner is compatible with the boiler s output range All components must be installed without being bent...

Страница 5: ...be put into operation without proper safety and protection devices A Class BE fire extinguisher is recommended It is forbidden to alter thedesign or use accessories which have not been approved by Ene...

Страница 6: ...ge check 1 year 3000 hrs Filter 1 year replacement at p 10 mbar 3000 hrs replacement at p 10 mbar Electrodes Replacement Cleaning 1 year Replacement Cleaning 3000 hrs Brake disc Replacement Cleaning 1...

Страница 7: ...g on the components used the measurements may vary Min recommended distance to floor K L M BG 650 M12 210 254 280 190 C I H A D E F G B J Type Length of burner tube Flange measure A Burner tube measur...

Страница 8: ...antity and capacity vary according to grade of gas and connection pressure BG650 G20 200 1125 21 118 360 G25 200 1125 24 4 137 360 G30 200 1125 6 2 34 6 360 G31 200 1125 8 1 45 7 360 kWh Nm3 MJ Nm3 kc...

Страница 9: ...ir duct that opens into an appropriate location Installation must be done so it does not prevent air supply to the burner 2 2 4 Electric Specification EN 60335 2 102 Burner correspond to IP20 2 2 5 Wo...

Страница 10: ...tor 11 Connection gas fittings 12 Ignition transformer 13 Air damper 14 Air damper motor 15 Air pressure switch 16 Fuse holder 17 Indicating lamp Stage 2 18 Switch I II 19 Indicating lamp Stage I 20 S...

Страница 11: ...ation electrode 10 Motor 11 Connection gas fittings 12 Ignition transformer 13 Air damper 14 Air damper motor 15 Air pressure switch 16 Fuse holder 17 Change over switch increase decrease 18 Change ov...

Страница 12: ...f the gas burner and the whole installation The supplier must instruct the user 3 4 Inspection and maintenance See service schedule 3 5 Start up After the burner has been fitted to the boiler and the...

Страница 13: ...of the installation If not please contact the supplier 2 Check that the gas components of the burner are approved for indicated gas pressure 3 The gas supply system should be installed in accordance w...

Страница 14: ...witch mini 5b Gas pressure switch maxi 6a Main valve 2 stage When modulaing operation is required this valve is equipped with controls for variable opening 6b Safety valve 1 7 Valve proving system 9 A...

Страница 15: ...15 Bentone 4 6 Handling and lifting instruction Figure 1 The lifting aid used here is available as spare part Figure 1 172 515 34...

Страница 16: ...ate from the fan housing 3 Loosen screw D on the nozzle assembly 4 Disconnect the electrical cables to the valve assembly and gas damper motor 5 Undo the screws B on both sides 6 Undo the end stops C...

Страница 17: ...there is enough slack in the electrical cables to the valve assembly and gas damper motor to pull out the burner body in the rear position on the guides If there is not enough slack the cables can be...

Страница 18: ...tral are not reversed The gas shut off cock should be closed To prevent the gas pressure switch from locking out it should be linked temporarily After the main switch has been switched on and the ther...

Страница 19: ...19 Bentone 4 10 Gas nozzle 45 Natural gas Propan Biogas UV detector...

Страница 20: ...s not flicker increase N When the flame is established adjust the gas flow by means of the screw N Use a flue gas instrument Change over to max load press the switch increase Adjust the gas flow with...

Страница 21: ...The best position is among other things dependent on the input power and overpressure in the boiler A general rule of thumb is that the smaller the capacity the smaller the gap should be between the b...

Страница 22: ...ch clockwise until the air pressure switch stops the burner Is the tolerance on the scale for the min air pressure switch approx 15 4 Try to find the pressure at which the burner stops for both the mi...

Страница 23: ...o the burner during normal operation at the highest input power 5 Based on the desired connection pressure set determine the connection pressure at which the gas pressure switch should stop the burner...

Страница 24: ...ilter 7 Data plate 8 Connection 1 8 PL 9 Adjustment screw V for ratio PBr PL max load 10 Test point connection 1 8 before V1 before governor 11 Connection for measurement of burner presssure after V2...

Страница 25: ...and PBr Impulse lines should preferably be made of steel Inside diameter 4 mm steel tube 6 4 For PL other material can be used Impulse lines PL and PBR are ready from factory Impulse lines shall be m...

Страница 26: ...ps 5 4 2 Electrical connection 1 2 3 4 5 G1 8 screwed seal plug 9 Test nipple 6 7 8 Pulse lines PL PF and PBr MB VEF 415 MB VEF 420 MB VEF 425 S 10 S 30 P1 L1 Mp N P1 L1 MP N 2 1 P1 L1 P2 L2 Mp N S 12...

Страница 27: ...ed excess air when using default setting Grade of gas Excess air flue gases Max CO2 O2 CO2 Lambda 1 2 Natural gas 3 5 10 11 9 Propane 3 5 11 5 13 9 Butane 3 5 11 5 14 1 Liquefied petroleum gas LPG 3 5...

Страница 28: ...58 5 Nm3 h Hu 9 5 0 90 Example C V 0C Q 500 58 9 Nm3 h Hu 0 00116 8126 0 00116 0 90 If the barometer reading altitude pressure and temperature of the gas deviate significantly from normal values this...

Страница 29: ...ally to measure how long it takes for the burner to consume a certain quantity of gas To measure t Time for a certain quantity of gas consumed by the burner h M Quantity of gas consumed m3 V Actual ga...

Страница 30: ...e Euro plugs from the burner 2 Remove the cover and disconnect the ignition cable ionisation cable and control arm D from the gas nozzle 3 Loosen the nuts B and pull the burner body out of the guides...

Страница 31: ...t the air intake 5 Remove the screws G securing the damper motor mounting plate 6 Lift up the damper motor 7 Clean the air damper and the intake Lubricate any damper shaft 8 Re install the damper moto...

Страница 32: ...e 9 Install the new damper motor on the mounting plate 10 Fit the control arm on the damper motor shaft It is important that the screw is perpendicular to the plane of the shaft 11 Re install the damp...

Страница 33: ...vibration level are 5 0 mm s Check all bolts and nuts for correct torque Check fan wheel for damage and contamination Change when dirty unbalanced Check motor bearings If worn change motor bearings U...

Страница 34: ...lectrode and gas burner control Connect the ammeter according to the diagram The minimum required ionisation current is shown in the table In practice this current must be significantly higher prefera...

Страница 35: ...s LMExx xxxx2 use of UV ancillary unit AGQ3 A27 is mandatory Correct functioning of aged UV cells can be checked as UV test with a higher supply voltage across the UV cell after controlled shutdown un...

Страница 36: ...dependent on three factors electricity gas and air supply Should there be any changes in the ratio between these three factors there is a risk of break downs It has been proved that most break downs...

Страница 37: ...r are installed in to Se local regulations for information Safety system cables must be run in separate cables outgoing signal must not come in same cable as incoming signal Signals must be in differe...

Страница 38: ...38 Bentone 9 2 Wiring diagram LME Design without A3 AGQ Option...

Страница 39: ...d light in the gas burner control is lit The burner is restarted by pushing the reset button A1 Gas burner control A2 Power control A3 Valve leak tester Dungs VPS 504 B1 Ionization electrode F1 Operat...

Страница 40: ...ng green Illegal flame signal during start up Green Red Undervoltage Yellow Red Fault alarm Red Blinking code for fault codes Blinking red Interface diagnostics Red flicking 9 4 1 1 Diagnosing alarm c...

Страница 41: ...g defective or fouled fuel valves defective or fouled flame monitoring Blinking 8 x Free Blinking 9 x Free Blinking 10 x Connection fault or internal fault outgoing contacts or other faults Blinking 1...

Страница 42: ...fault Action Burner does not start No gas Make sure all gas taps are open No power Check the fuse thermostat and electrical connections Burner motor does not start Motor protection has tripped Motor...

Страница 43: ...Reduce air volume Ignition load incorrectly set Increase decrease gas supply Reduce airflow Gas pressure too low Increase pressure If necessary contact gas supplier Pulsations at start up Ignition el...

Страница 44: ...g natural gas and liquefied petroleum propane butane Choke the air supply Poor air supply Open the air supply Check flue gas damper Holes in gas nozzle clogged Clean Poor fresh air intake Check and in...

Страница 45: ...172 905 04 2018 02 15 12 EU Declaration of conformity Bentone Gasburners...

Страница 46: ...rmostats etc are correctly adjusted 10 Read the instructions and follow the directions given for the burner as to starting up and service 13 5 2 Maintenance 1 Switch off the current with the main swit...

Страница 47: ...room Chimney Measu rement C A Before After mbar mbar Small Flame Large Flame Measures Date Nm3 gas h Governor CO2 CO Fluegas temp Ionisation current Pressure Efficiency Fire room Chimney Measu rement...

Страница 48: ...Enertech AB P O Box 309 SE 341 26 Ljungby www bentone se www bentone com...

Отзывы: