9.4.1.3 Alarm code table
Red blinking code
on
signal lamp (LED)
Possible causes
Blinking 2 x
..
No flame creation at End of “TSA”
- defective or fouled flame monitoring
- defective or fouled fuel valves
- poor burner setting
- defective firing device
Blinking 3 x
...
“LP” defective
- No air pressure switch signal after “t10”
- “LP” is welded in open position
Blinking 4 x
....
Illegal flame signal during start-up
Blinking 5 x
.....
Time out “LP”
- “LP” is welded in open position
Blinking 6 x
......
Free
Blinking 7 x
.......
Too many flame disappearances during operation
- poor burner setting
- defective or fouled fuel valves
- defective or fouled flame monitoring
Blinking 8 x
........
Free
Blinking 9 x
.........
Free
Blinking 10 x
..........
Connection fault or internal fault, outgoing contacts
or other faults
Blinking 14 x
..........
....
CPI contact not closed
During the diagnosing of the alarm cause, the control outputs are voltage-
free.
• The burner is disconnected
• Exception, alarm signal «AL» at board 10
• Reconnection of the burner happens after resetting only.
• Press the reset button 0.5...3 s
9.4.1.4 Interface diagnostics
To change to interface mode, press and hold the reset button longer than
3 s. To go back to the normal position, press and hold the reset button
longer than 3 s. If the gas burner control is in the alarm position, it is reset by
pressing the reset button 0.5...3 s.
Содержание BG 650
Страница 2: ...2 Bentone...
Страница 19: ...19 Bentone 4 10 Gas nozzle 45 Natural gas Propan Biogas UV detector...
Страница 38: ...38 Bentone 9 2 Wiring diagram LME Design without A3 AGQ Option...
Страница 45: ...172 905 04 2018 02 15 12 EU Declaration of conformity Bentone Gasburners...
Страница 48: ...Enertech AB P O Box 309 SE 341 26 Ljungby www bentone se www bentone com...